DEHNguard modular with integrated Backup Fuse

  • Arrester backup fuse integrated in the protection module
  • Prewired complete unit consisting of a base part and plug-in protection modules
  • Energy coordination with other arresters of the Red/Line product family
  • High discharge capacity
  • High reliability due to "Thermo Dynamic Control" SPD monitoring device
  • Easy replacement of protection modules without tools due to module locking system with module release button

Weiterführende Informationen

DEHNguard M TNC CI ... (FM)

Modular surge arrester with integrated backup fuses for TN-C systems with a nominal voltage of 230 / 400 V (3+0 configuration); FM version with floating remote signalling contact.

2 Produkte

Art.-Nr. 952304 DG M TNC CI 275

GTIN 4013364128361, Zolltarifnr.: 85363030, Bruttogewicht: 396.70 g, VPE: 1.00 pc(s)


Abbildungen

Weitere Information

DEHNguard M TNC CI 275 surge arrester
Modular and pluggable three-pole surge arrester with integrated
backup fuse for 230/400 V TN-C systems, width: 3 modules
Type 2 SPD according to EN 61643-11
Mechanical fault indication for the arrester
and integrated backup fuse
Max. continuous operating voltage: 275 V a.c.
Voltage protection level: <= 1.5 kV
Nominal discharge current: 12.5 kA
Rated breaking capacity of the integrated backup protection: 25 kA
Energy-coordinated according to IEC 62305-4
with arresters of the Red/Line series

Brand: DEHN
Type: DG M TNC CI 275
Part No.: 952304
or equivalent.

Zertifikate

 

Technische Daten

SPD according to EN 61643-11 / IEC 61643-11 type 2 / class II
Max. continuous operating voltage (a.c.) (UC ) 275 V (50 / 60 Hz)
Nominal discharge current (8/20 µs) (In ) 12.5 kA
Max. discharge current (8/20 µs) (Imax ) 25 kA
Voltage protection level (UP ) ≤ 1.5 kV
Max. mains-side overcurrent protection not required
Approvals KEMA, VDE

Artikel 952304 wurde zum Merkzettel hinzugefügt.

Zum Merkzettel

Artikel 952304 wurde zum Warenkorb hinzugefügt.

Zum Warenkorb

Art.-Nr. 952309 DG M TNC CI 275 FM

GTIN 4013364128378, Zolltarifnr.: 85363030, Bruttogewicht: 403.40 g, VPE: 1.00 pc(s)


Abbildungen

Weitere Information

DEHNguard M TNC CI 275 FM surge arrester
Modular and pluggable three-pole surge arrester with integrated
backup fuse for 230/400 V TN-C systems, width: 3 modules
Type 2 SPD according to EN 61643-11
Mechanical fault indication for the arrester
and integrated backup fuse
Max. continuous operating voltage: 275 V a.c.
Voltage protection level: <= 1.5 kV
Nominal discharge current: 12.5 kA
Rated breaking capacity of the integrated backup protection: 25 kA
Energy-coordinated according to IEC 62305-4
with arresters of the Red/Line series

Brand: DEHN
Type: DG M TNC CI 275 FM
Part No.: 952309
or equivalent.

Zertifikate

 

Technische Daten

SPD according to EN 61643-11 / IEC 61643-11 type 2 / class II
Max. continuous operating voltage (a.c.) (UC ) 275 V (50 / 60 Hz)
Nominal discharge current (8/20 µs) (In ) 12.5 kA
Max. discharge current (8/20 µs) (Imax ) 25 kA
Voltage protection level (UP ) ≤ 1.5 kV
Max. mains-side overcurrent protection not required
Approvals KEMA, VDE
Type of remote signalling contact changeover contact

Artikel 952309 wurde zum Merkzettel hinzugefügt.

Zum Merkzettel

Artikel 952309 wurde zum Warenkorb hinzugefügt.

Zum Warenkorb

DEHNguard M TNS CI ... (FM)

Modular surge arrester with integrated backup fuses for TN-S systems with a nominal voltage of 230 / 400 V (4+0 configuration); FM version with floating remote signalling contact.

2 Produkte

Art.-Nr. 952401 DG M TNS CI 275

GTIN 4013364128347, Zolltarifnr.: 85363030, Bruttogewicht: 500.70 g, VPE: 1.00 pc(s)


Abbildungen

Weitere Information

DEHNguard M TNS CI 275 surge arrester
Modular and pluggable four-pole surge arrester with integrated
backup fuse for 230/400 V TN-S systems, width: 4 modules
Type 2 SPD according to EN 61643-11
Mechanical fault indication for the arrester
and integrated backup fuse
Max. continuous operating voltage: 275 V a.c.
Voltage protection level: <= 1.5 kV
Nominal discharge current: 12.5 kA
Rated breaking capacity of the integrated backup protection: 25 kA
Energy-coordinated according to IEC 62305-4
with arresters of the Red/Line series

Brand: DEHN
Type: DG M TNS CI 275
Part No.: 952401
or equivalent.

Zertifikate

 

Technische Daten

SPD according to EN 61643-11 / IEC 61643-11 type 2 / class II
Max. continuous operating voltage (a.c.) (UC ) 275 V (50 / 60 Hz)
Nominal discharge current (8/20 µs) (In ) 12.5 kA
Max. discharge current (8/20 µs) (Imax ) 25 kA
Voltage protection level [L-PE] / [N-PE] (UP ) ≤ 1.5 / ≤ 1.5 kV
Max. mains-side overcurrent protection not required
Approvals KEMA, VDE

Artikel 952401 wurde zum Merkzettel hinzugefügt.

Zum Merkzettel

Artikel 952401 wurde zum Warenkorb hinzugefügt.

Zum Warenkorb

Art.-Nr. 952406 DG M TNS CI 275 FM

GTIN 4013364128354, Zolltarifnr.: 85363030, Bruttogewicht: 498.70 g, VPE: 1.00 pc(s)


Abbildungen

Weitere Information

DEHNguard M TNS CI 275 FM surge arrester
Modular and pluggable four-pole surge arrester with integrated
backup fuse for 230/400 V TN-S systems, width: 4 modules
With remote signalling contact
Type 2 SPD according to EN 61643-11
Mechanical fault indication for the arrester
and integrated backup fuse
Max. continuous operating voltage: 275 V a.c.
Voltage protection level: <= 1.5 kV
Nominal discharge current: 12.5 kA
Rated breaking capacity of the integrated backup protection: 25 kA
Energy-coordinated according to IEC 62305-4
with arresters of the Red/Line series

Brand: DEHN
Type: DG M TNS CI 275 FM
Part No.: 952406
or equivalent.

Zertifikate

 

Technische Daten

SPD according to EN 61643-11 / IEC 61643-11 type 2 / class II
Max. continuous operating voltage (a.c.) (UC ) 275 V (50 / 60 Hz)
Nominal discharge current (8/20 µs) (In ) 12.5 kA
Max. discharge current (8/20 µs) (Imax ) 25 kA
Voltage protection level [L-PE] / [N-PE] (UP ) ≤ 1.5 / ≤ 1.5 kV
Max. mains-side overcurrent protection not required
Approvals KEMA, VDE
Type of remote signalling contact changeover contact

Artikel 952406 wurde zum Merkzettel hinzugefügt.

Zum Merkzettel

Artikel 952406 wurde zum Warenkorb hinzugefügt.

Zum Warenkorb

DEHNguard M TT CI ... (FM)

Modular surge arrester with integrated backup fuses for TT and TN-S systems with a nominal voltage of 230 / 400 V (3+1 configuration); FM version with floating remote signalling contact.

2 Produkte

Art.-Nr. 952322 DG M TT CI 275

GTIN 4013364128385, Zolltarifnr.: 85363030, Bruttogewicht: 492.40 g, VPE: 1.00 pc(s)


Abbildungen

Weitere Information

DEHNguard M TT CI 275 surge arrester
Modular and pluggable four-pole surge arrester with integrated
backup fuse for 230/400 V TT and TN-S systems,
Width: 4 modules
Type 2 SPD according to EN 61643-11
Mechanical fault indication for the arrester
and integrated backup fuse
Max. continuous operating voltage: 275 V a.c.
Voltage protection level: <= 1.5 kV
Nominal discharge current: 12.5 kA
Rated breaking capacity of the integrated backup protection: 25 kA
Energy-coordinated according to IEC 62305-4
with arresters of the Red/Line series

Brand: DEHN
Type: DG M TT CI 275
Part No.: 952322
or equivalent.

Zertifikate

 

Technische Daten

SPD according to EN 61643-11 / IEC 61643-11 type 2 / class II
Max. continuous operating voltage (a.c.) [L-N] (UC ) 275 V (50 / 60 Hz)
Nominal discharge current (8/20 µs) [L-N] (In ) 12.5 kA
Max. discharge current (8/20 µs) [L-N] (Imax ) 25 kA
Voltage protection level [L-N] / [N-PE] (UP ) ≤ 1.5 / ≤ 1.5 kV
Max. mains-side overcurrent protection not required
Approvals KEMA, VDE

Artikel 952322 wurde zum Merkzettel hinzugefügt.

Zum Merkzettel

Artikel 952322 wurde zum Warenkorb hinzugefügt.

Zum Warenkorb

Art.-Nr. 952327 DG M TT CI 275 FM

GTIN 4013364128392, Zolltarifnr.: 85363030, Bruttogewicht: 500.60 g, VPE: 1.00 pc(s)


Abbildungen

Weitere Information

DEHNguard M TT CI 275 FM surge arrester
Modular and pluggable four-pole surge arrester with integrated
backup fuse for 230/400 V TT and TN-S systems,
Width: 4 modules
With remote signalling contact
Type 2 SPD according to EN 61643-11
Mechanical fault indication for the arrester
and integrated backup fuse
Max. continuous operating voltage: 275 V a.c.
Voltage protection level: <= 1.5 kV
Nominal discharge current: 12.5 kA
Rated breaking capacity of the integrated backup protection: 25 kA
Energy-coordinated according to IEC 62305-4
with arresters of the Red/Line series


Brand: DEHN
Type: DG M TT CI 275 FM
Part No.: 952327
or equivalent.

Zertifikate

 

Technische Daten

SPD according to EN 61643-11 / IEC 61643-11 type 2 / class II
Max. continuous operating voltage (a.c.) [L-N] (UC ) 275 V (50 / 60 Hz)
Nominal discharge current (8/20 µs) [L-N] (In ) 12.5 kA
Max. discharge current (8/20 µs) [L-N] (Imax ) 25 kA
Voltage protection level [L-N] / [N-PE] (UP ) ≤ 1.5 / ≤ 1.5 kV
Max. mains-side overcurrent protection not required
Approvals KEMA, VDE
Type of remote signalling contact changeover contact

Artikel 952327 wurde zum Merkzettel hinzugefügt.

Zum Merkzettel

Artikel 952327 wurde zum Warenkorb hinzugefügt.

Zum Warenkorb

DEHNguard M TN CI ... (FM)

Modular surge arrester with integrated backup fuses for single-phase 230 V TN systems (2+0 configuration); FM version with floating remote signalling contact.

2 Produkte

Art.-Nr. 952173 DG M TN CI 275

GTIN 4013364128408, Zolltarifnr.: 85363030, Bruttogewicht: 273.20 g, VPE: 1.00 pc(s)


Abbildungen

Weitere Information

DEHNguard M TN CI 275 surge arrester
Modular and pluggable two-pole surge arrester with integrated
backup fuse for single-phase 230 V TN systems,
Width: 2 modules
Type 2 SPD according to EN 61643-11
Mechanical fault indication for the arrester
and integrated backup fuse
Max. continuous operating voltage: 275 V a.c.
Voltage protection level: <= 1.5 kV
Nominal discharge current: 12.5 kA
Rated breaking capacity of the integrated backup protection: 25 kA
Energy-coordinated according to IEC 62305-4
with arresters of the Red/Line series

Brand: DEHN
Type: DG M TN CI 275
Part No.: 952173
or equivalent.

Zertifikate

 

Technische Daten

SPD according to EN 61643-11 / IEC 61643-11 type 2 / class II
Max. continuous operating voltage (a.c.) (UC ) 275 V (50 / 60 Hz)
Nominal discharge current (8/20 µs) (In ) 12.5 kA
Max. discharge current (8/20 µs) (Imax ) 25 kA
Voltage protection level [L-PE] / [N-PE] (UP ) ≤ 1.5 / ≤ 1.5 kV
Max. mains-side overcurrent protection not required
Approvals KEMA, VDE

Artikel 952173 wurde zum Merkzettel hinzugefügt.

Zum Merkzettel

Artikel 952173 wurde zum Warenkorb hinzugefügt.

Zum Warenkorb

Art.-Nr. 952178 DG M TN CI 275 FM

GTIN 4013364128415, Zolltarifnr.: 85363030, Bruttogewicht: 279.60 g, VPE: 1.00 pc(s)


Abbildungen

Weitere Information

DEHNguard M TN CI 275 FM surge arrester with backup fuses
Modular and pluggable two-pole surge arrester with integrated
backup fuse for single-phase 230 V TN systems
Width: 2 modules
With remote signalling contact
Type 2 SPD according to EN 61643-11
Mechanical fault indication for the arrester
and integrated backup fuse
Max. continuous operating voltage: 275 V a.c.
Voltage protection level: <= 1.5 kV
Nominal discharge current: 12.5 kA
Rated breaking capacity of the integrated backup protection: 25 kA
Energy-coordinated according to IEC 62305-4
with arresters of the Red/Line series

Brand: DEHN
Type: DG M TN CI 275 FM
Part No.: 952178
or equivalent.

Zertifikate

 

Technische Daten

SPD according to EN 61643-11 / IEC 61643-11 type 2 / class II
Max. continuous operating voltage (a.c.) (UC ) 275 V (50 / 60 Hz)
Nominal discharge current (8/20 µs) (In ) 12.5 kA
Max. discharge current (8/20 µs) (Imax ) 25 kA
Voltage protection level [L-PE] / [N-PE] (UP ) ≤ 1.5 / ≤ 1.5 kV
Max. mains-side overcurrent protection not required
Approvals KEMA, VDE
Type of remote signalling contact changeover contact

Artikel 952178 wurde zum Merkzettel hinzugefügt.

Zum Merkzettel

Artikel 952178 wurde zum Warenkorb hinzugefügt.

Zum Warenkorb

DEHNguard M TT 2P CI ... (FM)

Modular surge arrester with integrated backup fuses for single-phase 230 V TT and TN systems (1+1 configuration); FM version with floating remote signalling contact.

2 Produkte

Art.-Nr. 952171 DG M TT 2P CI 275

GTIN 4013364128422, Zolltarifnr.: 85363030, Bruttogewicht: 253.50 g, VPE: 1.00 pc(s)


Abbildungen

Weitere Information

DEHNguard M TT 2P CI 275 surge arrester
Modular and pluggable two-pole surge arrester with integrated
backup fuse for single-phase 230 V TT and TN systems,
Width: 2 modules
Type 2 SPD according to EN 61643-11
Mechanical fault indication for the arrester
and integrated backup fuse
Max. continuous operating voltage: 275 V a.c.
Voltage protection level: <= 1.5 kV
Nominal discharge current: 12.5 kA
Rated breaking capacity of the integrated backup protection: 25 kA
Energy-coordinated according to IEC 62305-4
with arresters of the Red/Line series

Brand: DEHN
Type: DG M TT 2P CI 275
Part No.: 952171
or equivalent.

Zertifikate

 

Technische Daten

SPD according to EN 61643-11 / IEC 61643-11 type 2 / class II
Max. continuous operating voltage (a.c.) [L-N] (UC ) 275 V (50 / 60 Hz)
Nominal discharge current (8/20 µs) [L-N] (In ) 12.5 kA
Max. discharge current (8/20 µs) [L-N] (Imax ) 25 kA
Voltage protection level [L-N] / [N-PE] (UP ) ≤ 1.5 / ≤ 1.5 kV
Max. mains-side overcurrent protection not required
Approvals KEMA, VDE

Artikel 952171 wurde zum Merkzettel hinzugefügt.

Zum Merkzettel

Artikel 952171 wurde zum Warenkorb hinzugefügt.

Zum Warenkorb

Art.-Nr. 952176 DG M TT 2P CI 275 FM

GTIN 4013364128439, Zolltarifnr.: 85363030, Bruttogewicht: 276.30 g, VPE: 1.00 pc(s)


Abbildungen

Weitere Information

Modular and pluggable two-pole surge arrester with integrated
backup fuse for single-phase 230 V TT and TN systems
Width: 2 modules
With remote signalling contact
Type 2 SPD according to EN 61643-11
Mechanical fault indication for the arrester
and integrated backup fuse
Max. continuous operating voltage: 275 V a.c.
Voltage protection level: <= 1.5 kV
Nominal discharge current: 12.5 kA
Rated breaking capacity of the integrated backup protection: 25 kA
Energy-coordinated according to IEC 62305-4
with arresters of the Red/Line series

Brand: DEHN
Type: DG M TT 2P CI 275 FM
Part No.: 952176
or equivalent.

Zertifikate

 

Technische Daten

SPD according to EN 61643-11 / IEC 61643-11 type 2 / class II
Max. continuous operating voltage (a.c.) [L-N] (UC ) 275 V (50 / 60 Hz)
Nominal discharge current (8/20 µs) [L-N] (In ) 12.5 kA
Max. discharge current (8/20 µs) [L-N] (Imax ) 25 kA
Voltage protection level [L-N] / [N-PE] (UP ) ≤ 1.5 / ≤ 1.5 kV
Max. mains-side overcurrent protection not required
Approvals KEMA, VDE
Type of remote signalling contact changeover contact

Artikel 952176 wurde zum Merkzettel hinzugefügt.

Zum Merkzettel

Artikel 952176 wurde zum Warenkorb hinzugefügt.

Zum Warenkorb

DEHNguard S CI ... (FM)

Pluggable single-pole surge arrester consisting of a base part and plug-in protection module; with integrated backup fuse; FM version with floating remote signalling contact.

2 Produkte

Art.-Nr. 952079 DG S CI 275

GTIN 4013364128446, Zolltarifnr.: 85363030, Bruttogewicht: 151.50 g, VPE: 1.00 pc(s)


Abbildungen

Weitere Information

DEHNguard S CI 275 surge arrester
Modular and pluggable single-pole surge arrester with integrated
backup fuse, Width: 1 module
Type 2 SPD according to EN 61643-11
Mechanical fault indication for the arrester
and integrated backup fuse
Max. continuous operating voltage: 275 V a.c./350 V d.c.
Voltage protection level: <= 1.5 kV
Nominal discharge current: 12.5 kA
Rated breaking capacity of the integrated backup protection: 25 kA
Energy-coordinated according to IEC 62305-4
with arresters of the Red/Line series

Brand: DEHN
Type: DG S CI 275
Part No.: 952079
or equivalent.

Zertifikate

 

Technische Daten

SPD according to EN 61643-11 / IEC 61643-11 type 2 / class II
Max. continuous operating voltage (a.c.) (UC ) 275 V (50 / 60 Hz)
Nominal discharge current (8/20 µs) (In ) 12.5 kA
Max. discharge current (8/20 µs) (Imax ) 25 kA
Voltage protection level (UP ) ≤ 1.5 kV
Max. mains-side overcurrent protection not required
Approvals KEMA, VDE

Artikel 952079 wurde zum Merkzettel hinzugefügt.

Zum Merkzettel

Artikel 952079 wurde zum Warenkorb hinzugefügt.

Zum Warenkorb

Art.-Nr. 952099 DG S CI 275 FM

GTIN 4013364128453, Zolltarifnr.: 85363030, Bruttogewicht: 144.40 g, VPE: 1.00 pc(s)


Abbildungen

Weitere Information

DEHNguard S CI 275 FM surge arrester
Modular and pluggable single-pole surge arrester with integrated
backup fuse, Width: 1 module
With remote signalling contact
Type 2 SPD according to EN 61643-11
Mechanical fault indication for the arrester and integrated backup fuse
Max. continuous operating voltage: 275 V a.c./350 V d.c.
Voltage protection level: <= 1.5 kV
Nominal discharge current: 12.5 kA
Rated breaking capacity of the integrated backup protection: 25 kA
Energy-coordinated according to IEC 62305-4
with arresters of the Red/Line series

Brand: DEHN
Type: DG S CI 275 FM
Part No.: 952099
or equivalent.

Zertifikate

 

Technische Daten

SPD according to EN 61643-11 / IEC 61643-11 type 2 / class II
Max. continuous operating voltage (a.c.) (UC ) 275 V (50 / 60 Hz)
Nominal discharge current (8/20 µs) (In ) 12.5 kA
Max. discharge current (8/20 µs) (Imax ) 25 kA
Voltage protection level (UP ) ≤ 1.5 kV
Max. mains-side overcurrent protection not required
Approvals KEMA, VDE
Type of remote signalling contact changeover contact

Artikel 952099 wurde zum Merkzettel hinzugefügt.

Zum Merkzettel

Artikel 952099 wurde zum Warenkorb hinzugefügt.

Zum Warenkorb

nach oben

Cookie-Einstellungen

Wir verwenden Cookies, um Ihnen ein optimales Webseiten-Erlebnis zu bieten. Dazu zählen Cookies, die für den Betrieb der Seite und für die Steuerung unserer kommerziellen Unternehmensziele notwendig sind, sowie solche, die lediglich zu anonymen Statistikzwecken, für Komforteinstellungen oder zur Anzeige personalisierter Inhalte genutzt werden. Sie können selbst entscheiden, welche Kategorien Sie zulassen möchten. Bitte beachten Sie, dass auf Basis Ihrer Einstellungen womöglich nicht mehr alle Funktionalitäten der Seite zur Verfügung stehen. Weitere Informationen finden Sie in unseren Datenschutzerklärung.
Wenn Sie in die Nutzung von Cookies eingewilligt haben, können Sie dies jederzeit nach Klick auf den Link "Cookie-Einstellungen ändern" im Footer der Seite widerrufen.

  • Details anzeigen Details ausblenden
    Notwendig

    Diese Cookies sind für den Betrieb der Seite unbedingt notwendig und ermöglichen beispielsweise sicherheitsrelevante Funktionalitäten. Außerdem können wir mit dieser Art von Cookies ebenfalls erkennen, ob Sie in Ihrem Profil eingeloggt bleiben möchten, um Ihnen unsere Dienste bei einem erneuten Besuch unserer Seite schneller zur Verfügung zu stellen.

    Statistik & Marketing

    Um unser Angebot und unsere Webseite weiter zu verbessern, erfassen wir anonymisierte Daten für Statistiken und Analysen. Mithilfe dieser Cookies können wir beispielsweise die Besucherzahlen und den Effekt bestimmter Seiten unseres Web-Auftritts ermitteln und unsere Inhalte optimieren.