SPD+POP+MCB / POP+MCB

  • Comprehensive protection against transient and power frequency overvoltage (SPD+POP)
  • Fulfils the requirements of EN 50550 "Power frequency overvoltage protective device"
  • Prewired complete unit, individual devices do not have to be additionally wired
  • Easy installation and retrofitting thanks to low space requirements
  • High reliability due to "Thermo Dynamic Control" monitoring system integrated in the SPD
  • Application-optimised discharge capacity of 5 kA (In) / 15 kA (Imax) (8/20 µs) per pole
  • Energy coordination with other arresters of the Red/Line series
  • Operating state / fault indication by green / red indicator flag in the inspection window of the SPD

Two-pole SPD+POP+MCB

3 Produkte

Art.-Nr. 900780 SPD+POP 2 255 C25

GTIN 4013364156203, Zolltarifnr.: 85363030, Bruttogewicht: 404.00 g, VPE: 1.00 pc(s)


Abbildungen

Weitere Information

Surge arrester SPD+POP 2 255 C25
Compact surge arrester for transients and
mains-frequency surges with integrated
miniature circuit breaker
Type 2 SPD according to EN 61643-11,
POP according to EN 50550
Comprehensive protection against transients and
mains-frequency surges
Prewired complete unit, the individual devices
do not have to be additionally wired
Number of poles 1P + N
Tripping characteristic MCB / nominal current MCB C 25 A
Max. continuous operating voltage: 275 V a.c.
Voltage protection level: <= 1.5 kV
Nominal discharge current: 5 kA / 20 kA
Energy coordination according to
EN 62305-4 with type 1 and
type 3 arresters of the Red/Line series
SPD monitoring: Thermo Dynamic Control
Operating state and fault indication
DIN rail mounted device according to DIN 43880, 4 modules

Brand: DEHN
Type: SPD+POP 2 255 C25
Part No.: 900780
or equivalent.

Zertifikate

 

Technische Daten

SPD
Nominal discharge current (8/20 µs) [L-N] (In ) 5 kA
General
Number of poles 1P + N
Nominal a.c. voltage (UN ) 230 V
MCB
Tripping characteristic C
Nominal alternating current (In ) 25 A

Artikel 900780 wurde zum Merkzettel hinzugefügt.

Zum Merkzettel

Artikel 900780 wurde zum Warenkorb hinzugefügt.

Zum Warenkorb

Art.-Nr. 900781 SPD+POP 2 255 C32

GTIN 4013364156210, Zolltarifnr.: 85363030, Bruttogewicht: 425.00 g, VPE: 1.00 pc(s)


Abbildungen

Weitere Information

Surge arrester SPD+POP 2 255 C32
Compact surge arrester for transients and mains-frequency
surges with integrated miniature circuit breaker
Type 2 SPD according to EN 61643-11, POP according to EN 50550
Comprehensive protection against transients and
mains-frequency surges
Prewired complete unit, the individual devices do not
have to be additionally wired
Number of poles 1P + N
Tripping characteristic MCB / nominal current MCB C 32 A
Max. continuous operating voltage: 275 V a.c.
Voltage protection level: <= 1.5 kV
Nominal discharge current: 5 kA / 20 kA
Energy coordination according to
EN 62305-4 with type 1 and
type 3 arresters of the Red/Line series
SPD monitoring: Thermo Dynamic Control
Operating state and fault indication
DIN rail mounted device according to DIN 43880, 4 modules

Brand: DEHN
Type: SPD+POP 2 255 C32
Part No.: 900781
or equivalent.

Zertifikate

 

Technische Daten

SPD
Nominal discharge current (8/20 µs) [L-N] (In ) 5 kA
General
Number of poles 1P + N
Nominal a.c. voltage (UN ) 230 V
MCB
Tripping characteristic C
Nominal alternating current (In ) 32 A

Artikel 900781 wurde zum Merkzettel hinzugefügt.

Zum Merkzettel

Artikel 900781 wurde zum Warenkorb hinzugefügt.

Zum Warenkorb

Art.-Nr. 900782 SPD+POP 2 255 C40

GTIN 4013364156227, Zolltarifnr.: 85363030, Bruttogewicht: 424.00 g, VPE: 1.00 pc(s)


Abbildungen

Weitere Information

Surge arrester SPD+POP 2 255 C40
Compact surge arrester for transients and mains-frequency
surges with integrated miniature circuit breaker
Type 2 SPD according to EN 61643-11, POP according to EN 50550
Comprehensive protection against transients and
mains-frequency surges
Prewired complete unit, the individual devices do not have to
be additionally wired
Number of poles 1P + N
Tripping characteristic MCB / nominal current MCB C 40 A
Max. continuous operating voltage: 275 V a.c.
Voltage protection level: <= 1.5 kV
Nominal discharge current: 5 kA / 20 kA
Energy coordination according to
EN 62305-4 with type 1 and
type 3 arresters of the Red/Line series
SPD monitoring: Thermo Dynamic Control
Operating state and fault indication
DIN rail mounted device according to DIN 43880, 4 modules

Brand: DEHN
Type: SPD+POP 2 255 C40
Part No.: 900782
or equivalent.

Zertifikate

 

Technische Daten

SPD
Nominal discharge current (8/20 µs) [L-N] (In ) 5 kA
General
Number of poles 1P + N
Nominal a.c. voltage (UN ) 230 V
MCB
Tripping characteristic C
Nominal alternating current (In ) 40 A

Artikel 900782 wurde zum Merkzettel hinzugefügt.

Zum Merkzettel

Artikel 900782 wurde zum Warenkorb hinzugefügt.

Zum Warenkorb

Four-pole SPD+POP+MCB

4 Produkte

Art.-Nr. 900785 SPD+POP 4 255 C25

GTIN 4013364156234, Zolltarifnr.: 85363030, Bruttogewicht: 730.00 g, VPE: 1.00 pc(s)


Abbildungen

Weitere Information

Surge arrester SPD+POP 4 255 C25
Compact surge arrester for transients and mains-frequency surges with integrated miniature circuit breaker
Type 2 SPD according to EN 61643-11, POP according to EN 50550
Comprehensive protection against transients and mains-frequency surges
Prewired complete unit, the individual devices do not have to be additionally wired
Number of poles 3P + N
Tripping characteristic MCB / nominal current MCB C 25 A
Max. continuous operating voltage: 275 V a.c.
Voltage protection level: <= 1.5 kV
Nominal discharge current: 5 kA / 20 kA
Energy coordination according to
EN 62305-4 with type 1 and
type 3 arresters of the Red/Line series
SPD monitoring: Thermo Dynamic Control
Operating state and fault indication
DIN rail mounted device according to DIN 43880, 7 modules

Brand: DEHN
Type: SPD+POP 4 255 C25
Part No.: 900785
or equivalent.

Zertifikate

 

Technische Daten

General
Number of poles 3P + N
Nominal a.c. voltage (UN ) 230 / 400 V
SPD
Nominal discharge current (8/20 µs) [L-N] (In ) 5 kA
MCB
Tripping characteristic C
Nominal alternating current (In ) 25 A

Artikel 900785 wurde zum Merkzettel hinzugefügt.

Zum Merkzettel

Artikel 900785 wurde zum Warenkorb hinzugefügt.

Zum Warenkorb

Art.-Nr. 900786 SPD+POP 4 255 C32

GTIN 4013364156241, Zolltarifnr.: 85363030, Bruttogewicht: 763.00 g, VPE: 1.00 pc(s)


Abbildungen

Weitere Information

Surge arrester SPD+POP 4 255 C32
Compact surge arrester for transients and mains-frequency surges with integrated miniature circuit breaker
Type 2 SPD according to EN 61643-11, POP according to EN 50550
Comprehensive protection against transients and mains-frequency surges
Prewired complete unit, the individual devices do not have to be additionally wired
Number of poles 3P + N
Tripping characteristic MCB / nominal current MCB C 32 A
Max. continuous operating voltage: 275 V a.c.
Voltage protection level: <= 1.5 kV
Nominal discharge current: 5 kA / 20 kA
Energy coordination according to
EN 62305-4 with type 1 and
type 3 arresters of the Red/Line series
SPD monitoring: Thermo Dynamic Control
Operating state and fault indication
DIN rail mounted device according to DIN 43880, 7 modules

Brand: DEHN
Type: SPD+POP 4 255 C32
Part No.: 900786
or equivalent.

Zertifikate

 

Technische Daten

General
Number of poles 3P + N
Nominal a.c. voltage (UN ) 230 / 400 V
SPD
Nominal discharge current (8/20 µs) [L-N] (In ) 5 kA
MCB
Tripping characteristic C
Nominal alternating current (In ) 32 A

Artikel 900786 wurde zum Merkzettel hinzugefügt.

Zum Merkzettel

Artikel 900786 wurde zum Warenkorb hinzugefügt.

Zum Warenkorb

Art.-Nr. 900787 SPD+POP 4 255 C40

GTIN 4013364156258, Zolltarifnr.: 85363030, Bruttogewicht: 769.00 g, VPE: 1.00 pc(s)


Abbildungen

Weitere Information

Surge arrester SPD+POP 4 255 C40
Compact surge arrester for transients and mains-frequency surges with integrated miniature circuit breaker
Type 2 SPD according to EN 61643-11, POP according to EN 50550
Comprehensive protection against transients and mains-frequency surges
Prewired complete unit, the individual devices do not have to be additionally wired
Number of poles 3P + N
Tripping characteristic MCB / nominal current MCB C 40 A
Max. continuous operating voltage: 275 V a.c.
Voltage protection level: <= 1.5 kV
Nominal discharge current: 5 kA / 20 kA
Energy coordination according to
EN 62305-4 with type 1 and
type 3 arresters of the Red/Line series
SPD monitoring: Thermo Dynamic Control
Operating state and fault indication
DIN rail mounted device according to DIN 43880, 7 modules

Brand: DEHN
Type: SPD+POP 4 255 C40
Part No.: 900787
or equivalent.

Zertifikate

 

Technische Daten

General
Number of poles 3P + N
Nominal a.c. voltage (UN ) 230 / 400 V
SPD
Nominal discharge current (8/20 µs) [L-N] (In ) 5 kA
MCB
Tripping characteristic C
Nominal alternating current (In ) 40 A

Artikel 900787 wurde zum Merkzettel hinzugefügt.

Zum Merkzettel

Artikel 900787 wurde zum Warenkorb hinzugefügt.

Zum Warenkorb

Art.-Nr. 900788 SPD+POP 4 255 C63

GTIN 4013364156265, Zolltarifnr.: 85363030, Bruttogewicht: 773.00 g, VPE: 1.00 pc(s)


Abbildungen

Weitere Information

Surge arrester SPD+POP 4 255 C63
Compact surge arrester for transients and mains-frequency surges with integrated miniature circuit breaker
Type 2 SPD according to EN 61643-11, POP according to EN 50550
Comprehensive protection against transients and mains-frequency surges
Prewired complete unit, the individual devices do not have to be additionally wired
Number of poles 3P + N
Tripping characteristic MCB / nominal current MCB C 63 A
Max. continuous operating voltage: 275 V a.c.
Voltage protection level: <= 1.5 kV
Nominal discharge current: 5 kA / 20 kA
Energy coordination according to
EN 62305-4 with type 1 and
type 3 arresters of the Red/Line series
SPD monitoring: Thermo Dynamic Control
Operating state and fault indication
DIN rail mounted device according to DIN 43880, 7 modules

Brand: DEHN
Type: SPD+POP 4 255 C63
Part No.: 900788
or equivalent.

Zertifikate

 

Technische Daten

General
Number of poles 3P + N
Nominal a.c. voltage (UN ) 230 / 400 V
SPD
Nominal discharge current (8/20 µs) [L-N] (In ) 5 kA
MCB
Tripping characteristic C
Nominal alternating current (In ) 63 A

Artikel 900788 wurde zum Merkzettel hinzugefügt.

Zum Merkzettel

Artikel 900788 wurde zum Warenkorb hinzugefügt.

Zum Warenkorb

Two-pole POP+MCB

3 Produkte

Art.-Nr. 900760 POP 2 255 C25

GTIN 4013364156135, Zolltarifnr.: 85363030, Bruttogewicht: 297.00 g, VPE: 1.00 pc(s)


Abbildungen

Weitere Information

Protective device POP 2 255 C25
Protective device for mains-frequency surges with integrated miniature circuit breaker
POP according to EN 50550
Prewired complete unit, individual devices do not have to be additionally wired
Number pf poles 1P + N
Tripping characteristic MCB / nominal current MCB C 25 A
Rated breaking capacity according to EN 60898 6 kA
DIN rail mounted device according to DIN 43880, 3 modules

Brand: DEHN
Type: POP 2 255 C25
Part No.: 900760
or equivalent.

Zertifikate

 

Technische Daten

General
Number of poles 1P + N
Nominal a.c. voltage (UN ) 230 V
MCB
Tripping characteristic C
Nominal alternating current (In ) 25 A

Artikel 900760 wurde zum Merkzettel hinzugefügt.

Zum Merkzettel

Artikel 900760 wurde zum Warenkorb hinzugefügt.

Zum Warenkorb

Art.-Nr. 900761 POP 2 255 C32

GTIN 4013364156142, Zolltarifnr.: 85363030, Bruttogewicht: 317.00 g, VPE: 1.00 pc(s)


Abbildungen

Weitere Information

Protective device POP 2 255 C32
Protective device for mains-frequency surges with integrated miniature circuit breaker
POP according to EN 50550
Prewired complete unit, individual devices do not have to be additionally wired
Number pf poles 1P + N
Tripping characteristic MCB / nominal current MCB C 32 A
Rated breaking capacity according to EN 60898 6 kA
DIN rail mounted device according to DIN 43880, 3 modules

Brand: DEHN
Type: POP 2 255 C32
Part No.: 900761
or equivalent.

Zertifikate

 

Technische Daten

General
Number of poles 1P + N
Nominal a.c. voltage (UN ) 230 V
MCB
Tripping characteristic C
Nominal alternating current (In ) 32 A

Artikel 900761 wurde zum Merkzettel hinzugefügt.

Zum Merkzettel

Artikel 900761 wurde zum Warenkorb hinzugefügt.

Zum Warenkorb

Art.-Nr. 900762 POP 2 255 C40

GTIN 4013364156159, Zolltarifnr.: 85363030, Bruttogewicht: 317.00 g, VPE: 1.00 pc(s)


Abbildungen

Weitere Information

Protective device POP 2 255 C40
Protective device for mains-frequency surges with integrated miniature circuit breaker
POP according to EN 50550
Prewired complete unit, individual devices do not have to be additionally wired
Number pf poles 1P + N
Tripping characteristic MCB / nominal current MCB C 40 A
Rated breaking capacity according to EN 60898 6 kA
DIN rail mounted device according to DIN 43880, 3 modules

Brand: DEHN
Type: POP 2 255 C40
Part No.: 900762
or equivalent.

Zertifikate

 

Technische Daten

General
Number of poles 1P + N
Nominal a.c. voltage (UN ) 230 V
MCB
Tripping characteristic C
Nominal alternating current (In ) 40 A

Artikel 900762 wurde zum Merkzettel hinzugefügt.

Zum Merkzettel

Artikel 900762 wurde zum Warenkorb hinzugefügt.

Zum Warenkorb

Four-pole POP+MCB

4 Produkte

Art.-Nr. 900765 POP 4 255 C25

GTIN 4013364156166, Zolltarifnr.: 85363030, Bruttogewicht: 547.00 g, VPE: 1.00 pc(s)


Abbildungen

Weitere Information

Protective device POP 4 255 C25
Protective device for mains-frequency surges with integrated miniature circuit breaker
POP according to EN 50550
Prewired complete unit, individual devices do not have to be additionally wired
Number pf poles 3P + N
Tripping characteristic MCB / nominal current MCB C 25 A
Rated breaking capacity according to EN 60898 6 kA
DIN rail mounted device according to DIN 43880, 5 modules

Brand: DEHN
Type: POP 4 255 C25
Part No.: 900765
or equivalent.

Zertifikate

 

Technische Daten

General
Number of poles 3P + N
Nominal a.c. voltage (UN ) 230 / 400 V
MCB
Tripping characteristic C
Nominal alternating current (In ) 25 A

Artikel 900765 wurde zum Merkzettel hinzugefügt.

Zum Merkzettel

Artikel 900765 wurde zum Warenkorb hinzugefügt.

Zum Warenkorb

Art.-Nr. 900766 POP 4 255 C32

GTIN 4013364156173, Zolltarifnr.: 85363030, Bruttogewicht: 580.00 g, VPE: 1.00 pc(s)


Abbildungen

Weitere Information

Protective device POP 4 255 C32
Protective device for mains-frequency surges with integrated miniature circuit breaker
POP according to EN 50550
Prewired complete unit, individual devices do not have to be additionally wired
Number pf poles 3P + N
Tripping characteristic MCB / nominal current MCB C 32 A
Rated breaking capacity according to EN 60898 6 kA
DIN rail mounted device according to DIN 43880, 5 modules

Brand: DEHN
Type: POP 4 255 C32
Part No.: 900766
or equivalent.

Zertifikate

 

Technische Daten

General
Number of poles 3P + N
Nominal a.c. voltage (UN ) 230 / 400 V
MCB
Tripping characteristic C
Nominal alternating current (In ) 32 A

Artikel 900766 wurde zum Merkzettel hinzugefügt.

Zum Merkzettel

Artikel 900766 wurde zum Warenkorb hinzugefügt.

Zum Warenkorb

Art.-Nr. 900767 POP 4 255 C40

GTIN 4013364156180, Zolltarifnr.: 85363030, Bruttogewicht: 586.00 g, VPE: 1.00 pc(s)


Abbildungen

Weitere Information

Protective device POP 4 255 C40
Protective device for mains-frequency surges with integrated miniature circuit breaker
POP according to EN 50550
Prewired complete unit, individual devices do not have to be additionally wired
Number pf poles 3P + N
Tripping characteristic MCB / nominal current MCB C 40 A
Rated breaking capacity according to EN 60898 6 kA
DIN rail mounted device according to DIN 43880, 5 modules

Brand: DEHN
Type: POP 4 255 C40
Part No.: 900767
or equivalent.

Zertifikate

 

Technische Daten

General
Number of poles 3P + N
Nominal a.c. voltage (UN ) 230 / 400 V
MCB
Tripping characteristic C
Nominal alternating current (In ) 40 A

Artikel 900767 wurde zum Merkzettel hinzugefügt.

Zum Merkzettel

Artikel 900767 wurde zum Warenkorb hinzugefügt.

Zum Warenkorb

Art.-Nr. 900768 POP 4 255 C63

GTIN 4013364156197, Zolltarifnr.: 85363030, Bruttogewicht: 591.00 g, VPE: 1.00 pc(s)


Abbildungen

Weitere Information

Protective device POP 4 255 C63
Protective device for mains-frequency surges with integrated miniature circuit breaker
POP according to EN 50550
Prewired complete unit, individual devices do not have to be additionally wired
Number pf poles 3P + N
Tripping characteristic MCB / nominal current MCB C 63 A
Rated breaking capacity according to EN 60898 6 kA
DIN rail mounted device according to DIN 43880, 5 modules

Brand: DEHN
Type: POP 4 255 C63
Part No.: 900768
or equivalent.

Zertifikate

 

Technische Daten

General
Number of poles 3P + N
Nominal a.c. voltage (UN ) 230 / 400 V
MCB
Tripping characteristic C
Nominal alternating current (In ) 63 A

Artikel 900768 wurde zum Merkzettel hinzugefügt.

Zum Merkzettel

Artikel 900768 wurde zum Warenkorb hinzugefügt.

Zum Warenkorb

nach oben

Cookie-Einstellungen

Wir verwenden Cookies, um Ihnen ein optimales Webseiten-Erlebnis zu bieten. Dazu zählen Cookies, die für den Betrieb der Seite und für die Steuerung unserer kommerziellen Unternehmensziele notwendig sind, sowie solche, die lediglich zu anonymen Statistikzwecken, für Komforteinstellungen oder zur Anzeige personalisierter Inhalte genutzt werden. Sie können selbst entscheiden, welche Kategorien Sie zulassen möchten. Bitte beachten Sie, dass auf Basis Ihrer Einstellungen womöglich nicht mehr alle Funktionalitäten der Seite zur Verfügung stehen. Weitere Informationen finden Sie in unseren Datenschutzerklärung.
Wenn Sie in die Nutzung von Cookies eingewilligt haben, können Sie dies jederzeit nach Klick auf den Link "Cookie-Einstellungen ändern" im Footer der Seite widerrufen.

  • Details anzeigen Details ausblenden
    Notwendig

    Diese Cookies sind für den Betrieb der Seite unbedingt notwendig und ermöglichen beispielsweise sicherheitsrelevante Funktionalitäten. Außerdem können wir mit dieser Art von Cookies ebenfalls erkennen, ob Sie in Ihrem Profil eingeloggt bleiben möchten, um Ihnen unsere Dienste bei einem erneuten Besuch unserer Seite schneller zur Verfügung zu stellen.

    Statistik & Marketing

    Um unser Angebot und unsere Webseite weiter zu verbessern, erfassen wir anonymisierte Daten für Statistiken und Analysen. Mithilfe dieser Cookies können wir beispielsweise die Besucherzahlen und den Effekt bestimmter Seiten unseres Web-Auftritts ermitteln und unsere Inhalte optimieren.