Art.-Nr. 909531 DSH ZP 2 TT 255
GTIN 4013364424807, Zolltarifnr.: 85363090, Bruttogewicht: 610.48 g, VPE: 1.00 pc(s)
VorgängerTechnische Daten
SPD according to EN 61643-11 / IEC 61643-11 | type 1 + type 2 + type 3 / class I + class II + class III |
Max. continuous operating voltage (a.c.) (UC ) | 255 V (50 / 60 Hz) |
Lightning impulse current (10/350 µs) [L1+L2+L3+N-PE] (Itotal ) | 50 kA |
Lightning impulse current (10/350 µs) [L-N] (Iimp ) | 12.5 kA |
Lightning impulse current (10/350 µs) [N-PE] (Iimp ) | 50 kA |
Voltage protection level [L-N] (UP ) | ≤ 1.5 kV |
Voltage protection level [N-PE] (UP ) | ≤ 1.5 kV |
Open-circuit voltage of the combination wave generator (UOC ) | 20 kV |
Max. mains-side overcurrent protection | 160 A gG |
Approvals | VDE |
DEHNshield ZP 2 SG TT 255
Combined arrester for TT and TN-S systems for use in the main power supply system (3+1 configuration) of residential buildings with external lightning protection (class of LPS III/IV) including overcurrent-protected 230 V power supply for the compartment for additional applications / termination point meter mounting board according to VDE-AR-N 4100.
1 Produkt
Art.-Nr. 909631 DSH ZP 2 SG TT 255
GTIN 4013364424739, Zolltarifnr.: 85363090, Bruttogewicht: 652.09 g, VPE: 1.00 pc(s)
VorgängerTechnische Daten
SPD according to EN 61643-11 / IEC 61643-11 | type 1 + type 2 + type 3 / class I + class II + class III |
Max. continuous operating voltage (a.c.) (UC ) | 255 V (50 / 60 Hz) |
Lightning impulse current (10/350 µs) [L1+L2+L3+N-PE] (Itotal ) | 50 kA |
Lightning impulse current (10/350 µs) [L-N] (Iimp ) | 12.5 kA |
Lightning impulse current (10/350 µs) [N-PE] (Iimp ) | 50 kA |
Voltage protection level [L-N] (UP ) | ≤ 1.5 kV |
Voltage protection level [N-PE] (UP ) | ≤ 1.5 kV |
Open-circuit voltage of the combination wave generator (UOC ) | 20 kV |
Max. mains-side overcurrent protection | 160 A gG |
Approvals | VDE |
Art.-Nr. 909331 DSH ZP B2 TT 255
GTIN 4013364422728, Zolltarifnr.: 85363090, Bruttogewicht: 598.27 g, VPE: 1.00 pc(s)
VorgängerTechnische Daten
SPD according to EN 61643-11 / IEC 61643-11 | type 1 + type 2 + type 3 / class I + class II + class III |
Max. continuous operating voltage (a.c.) (UC ) | 255 V (50 / 60 Hz) |
Lightning impulse current (10/350 µs) [L1+L2+L3+N-PE] (Itotal ) | 30 kA |
Lightning impulse current (10/350 µs) [L-N] (Iimp ) | 7.5 kA |
Lightning impulse current (10/350 µs) [N-PE] (Iimp ) | 30 kA |
Voltage protection level [L-N] (UP ) | ≤ 1.5 kV |
Voltage protection level [N-PE] (UP ) | ≤ 1.5 kV |
Open-circuit voltage of the combination wave generator (UOC ) | 20 kV |
Max. mains-side overcurrent protection | 160 A gG |
Approvals | VDE |
DEHNshield ZP B2 SG TT 255
Combined arrester for TT and TN-S systems for use in the main power supply system (3+1 configuration) of residential buildings without external lightning protection (also with overhead line supply) including overcurrent-protected 230 V power supply for the compartment for additional applications / termination point meter mounting board according to VDE-AR-N 4100.
1 Produkt
Art.-Nr. 909396 DSH ZP B2 SG TT 255
GTIN 4013364409859, Zolltarifnr.: 85363090, Bruttogewicht: 646.13 g, VPE: 1.00 pc(s)
VorgängerTechnische Daten
SPD according to EN 61643-11 / IEC 61643-11 | type 1 + type 2 + type 3 / class I + class II + class III |
Max. continuous operating voltage (a.c.) (UC ) | 255 V (50 / 60 Hz) |
Lightning impulse current (10/350 µs) [L1+L2+L3+N-PE] (Itotal ) | 30 kA |
Lightning impulse current (10/350 µs) [L-N] (Iimp ) | 7.5 kA |
Lightning impulse current (10/350 µs) [N-PE] (Iimp ) | 30 kA |
Voltage protection level [L-N] (UP ) | ≤ 1.5 kV |
Voltage protection level [N-PE] (UP ) | ≤ 1.5 kV |
Open-circuit voltage of the combination wave generator (UOC ) | 20 kV |
Max. mains-side overcurrent protection | 160 A gG |
Approvals | VDE |
Art.-Nr. 909540 DSH ZP 2 TNS 255
GTIN 4013364424784, Zolltarifnr.: 85363090, Bruttogewicht: 577.05 g, VPE: 1.00 pc(s)
Technische Daten
SPD according to EN 61643-11 / IEC 61643-11 | type 1 + type 2 + type 3 / class I + class II + class III |
Max. continuous operating voltage (a.c.) (UC ) | 255 V (50 / 60 Hz) |
Lightning impulse current (10/350 µs) [L1+L2+L3+N-PE] (Itotal ) | 50 kA |
Lightning impulse current (10/350 µs) [L, N-PE] (Iimp ) | 12.5 kA |
Voltage protection level [L-PE] (UP ) | ≤ 1.5 kV |
Voltage protection level [N-PE] (UP ) | ≤ 1.5 kV |
Open-circuit voltage of the combination wave generator (UOC ) | 20 kV |
Max. mains-side overcurrent protection | 160 A gG |
Approvals | VDE |
DEHNshield ZP 2 SG TNS 255
Combined arrester for TN-S systems for use in the main power supply system (4+0 configuration) of residential buildings with external lightning protection (class of LPS III/IV) including overcurrent-protected 230 V power supply for the compartment for additional applications / termination point meter mounting board according to VDE-AR-N 4100.
1 Produkt
Art.-Nr. 909640 DSH ZP 2 SG TNS 255
GTIN 4013364424715, Zolltarifnr.: 85363090, Bruttogewicht: 617.65 g, VPE: 1.00 pc(s)
Technische Daten
SPD according to EN 61643-11 / IEC 61643-11 | type 1 + type 2 + type 3 / class I + class II + class III |
Max. continuous operating voltage (a.c.) (UC ) | 255 V (50 / 60 Hz) |
Lightning impulse current (10/350 µs) [L1+L2+L3+N-PE] (Itotal ) | 50 kA |
Lightning impulse current (10/350 µs) [L, N-PE] (Iimp ) | 12.5 kA |
Voltage protection level [L-PE] (UP ) | ≤ 1.5 kV |
Voltage protection level [N-PE] (UP ) | ≤ 1.5 kV |
Open-circuit voltage of the combination wave generator (UOC ) | 20 kV |
Max. mains-side overcurrent protection | 160 A gG |
Approvals | VDE |
Art.-Nr. 909340 DSH ZP B2 TNS 255
GTIN 4013364424876, Zolltarifnr.: 85363090, Bruttogewicht: 579.68 g, VPE: 1.00 pc(s)
Technische Daten
SPD according to EN 61643-11 / IEC 61643-11 | type 1 + type 2 + type 3 / class I + class II + class III |
Max. continuous operating voltage (a.c.) (UC ) | 255 V (50 / 60 Hz) |
Lightning impulse current (10/350 µs) [L1+L2+L3+N-PE] (Itotal ) | 30 kA |
Lightning impulse current (10/350 µs) [L, N-PE] (Iimp ) | 7.5 kA |
Voltage protection level [L-PE] (UP ) | ≤ 1.5 kV |
Voltage protection level [N-PE] (UP ) | ≤ 1.5 kV |
Open-circuit voltage of the combination wave generator (UOC ) | 20 kV |
Max. mains-side overcurrent protection | 160 A gG |
Approvals | VDE |
DEHNshield ZP B2 SG TNS 255
Combined arrester for TN-S systems for use in the main power supply system (4+0 configuration) of residential buildings without external lightning protection (also with overhead line suppy) including overcurrent-protected 230 V power supply for the compartment for additional applications / termination point meter mounting board according to VDE-AR-N 4100.
1 Produkt
Art.-Nr. 909440 DSH ZP B2 SG TNS 255
GTIN 4013364409866, Zolltarifnr.: 85363090, Bruttogewicht: 621.62 g, VPE: 1.00 pc(s)
Technische Daten
SPD according to EN 61643-11 / IEC 61643-11 | type 1 + type 2 + type 3 / class I + class II + class III |
Max. continuous operating voltage (a.c.) (UC ) | 255 V (50 / 60 Hz) |
Lightning impulse current (10/350 µs) [L1+L2+L3+N-PE] (Itotal ) | 30 kA |
Lightning impulse current (10/350 µs) [L, N-PE] (Iimp ) | 7.5 kA |
Voltage protection level [L-PE] (UP ) | ≤ 1.5 kV |
Voltage protection level [N-PE] (UP ) | ≤ 1.5 kV |
Open-circuit voltage of the combination wave generator (UOC ) | 20 kV |
Max. mains-side overcurrent protection | 160 A gG |
Approvals | VDE |
Art.-Nr. 909530 DSH ZP 2 TNC 255
GTIN 4013364424753, Zolltarifnr.: 85363090, Bruttogewicht: 520.31 g, VPE: 1.00 pc(s)
VorgängerTechnische Daten
SPD according to EN 61643-11 / IEC 61643-11 | type 1 + type 2 + type 3 / class I + class II + class III |
Max. continuous operating voltage (a.c.) (UC ) | 255 V (50 / 60 Hz) |
Lightning impulse current (10/350 µs) [L1+L2+L3-PEN] (Itotal ) | 37.5 kA |
Lightning impulse current (10/350 µs) [L-PEN] (Iimp ) | 12.5 kA |
Voltage protection level (UP ) | ≤ 1.5 kV |
Open-circuit voltage of the combination wave generator (UOC ) | 20 kV |
Max. mains-side overcurrent protection | 160 A gG |
Approvals | VDE |
DEHNshield ZP 2 SG TNC 255
Combined arrester for TN-C systems for use in the main power supply system (3+0 configuration) of residential buildings with external lightning protection (class of LPS III/IV) including overcurrent-protected 230 V power supply for the compartment for additional applications / termination point meter mounting board according to VDE-AR-N 4100.
1 Produkt
Art.-Nr. 909630 DSH ZP 2 SG TNC 255
GTIN 4013364424692, Zolltarifnr.: 85363090, Bruttogewicht: 562.36 g, VPE: 1.00 pc(s)
VorgängerTechnische Daten
SPD according to EN 61643-11 / IEC 61643-11 | type 1 + type 2 + type 3 / class I + class II + class III |
Max. continuous operating voltage (a.c.) (UC ) | 255 V (50 / 60 Hz) |
Lightning impulse current (10/350 µs) [L1+L2+L3-PEN] (Itotal ) | 37.5 kA |
Lightning impulse current (10/350 µs) [L-PEN] (Iimp ) | 12.5 kA |
Voltage protection level (UP ) | ≤ 1.5 kV |
Open-circuit voltage of the combination wave generator (UOC ) | 20 kV |
Max. mains-side overcurrent protection | 160 A gG |
Approvals | VDE |
Art.-Nr. 909330 DSH ZP B2 TNC 255
GTIN 4013364424852, Zolltarifnr.: 85363090, Bruttogewicht: 522.37 g, VPE: 1.00 pc(s)
VorgängerTechnische Daten
SPD according to EN 61643-11 / IEC 61643-11 | type 1 + type 2 + type 3 / class I + class II + class III |
Max. continuous operating voltage (a.c.) (UC ) | 255 V (50 / 60 Hz) |
Lightning impulse current (10/350 µs) [L1+L2+L3-PEN] (Itotal ) | 22.5 kA |
Lightning impulse current (10/350 µs) [L-PEN] (Iimp ) | 7.5 kA |
Voltage protection level (UP ) | ≤ 1.5 kV |
Open-circuit voltage of the combination wave generator (UOC ) | 20 kV |
Max. mains-side overcurrent protection | 160 A gG |
Approvals | VDE |
DEHNshield ZP B2 SG TNC 255
Combined arrester for TN-C systems for use in the main power supply system (3+0 configuration) of residential buildings without external lightning protection (also with overhead line suppy) including overcurrent-protected 230 V power supply for the compartment for additional applications / termination point meter mounting board according to VDE-AR-N 4100.
1 Produkt
Art.-Nr. 909430 DSH ZP B2 SG TNC 255
GTIN 4013364409842, Zolltarifnr.: 85363090, Bruttogewicht: 564.86 g, VPE: 1.00 pc(s)
VorgängerTechnische Daten
SPD according to EN 61643-11 / IEC 61643-11 | type 1 + type 2 + type 3 / class I + class II + class III |
Max. continuous operating voltage (a.c.) (UC ) | 255 V (50 / 60 Hz) |
Lightning impulse current (10/350 µs) [L1+L2+L3-PEN] (Itotal ) | 22.5 kA |
Lightning impulse current (10/350 µs) [L-PEN] (Iimp ) | 7.5 kA |
Voltage protection level (UP ) | ≤ 1.5 kV |
Open-circuit voltage of the combination wave generator (UOC ) | 20 kV |
Max. mains-side overcurrent protection | 160 A gG |
Approvals | VDE |
Art.-Nr. 909831 DSH ZP 2 LSG TT 255
GTIN 4013364449732, Zolltarifnr.: 85363090, Bruttogewicht: 765.00 g, VPE: 1.00 pc(s)
Technische Daten
SPD according to EN 61643-11 / IEC 61643-11 | type 1 + type 2 + type 3 / class I + class II + class III |
Max. continuous operating voltage (a.c.) (UC ) | 255 V (50 / 60 Hz) |
Lightning impulse current (10/350 µs) [L1+L2+L3+N-PE] (Itotal ) | 50 kA |
Lightning impulse current (10/350 µs) [L-N] (Iimp ) | 12.5 kA |
Lightning impulse current (10/350 µs) [N-PE] (Iimp ) | 50 kA |
Voltage protection level [L-N] (UP ) | ≤ 1.5 kV |
Voltage protection level [N-PE] (UP ) | ≤ 1.5 kV |
Open-circuit voltage of the combination wave generator (UOC ) | 20 kV |
Max. mains-side overcurrent protection | 160 A gG |
Approvals | VDE |
Art.-Nr. 909731 DSH ZP B2 LSG TT 255
GTIN 4013364449725, Zolltarifnr.: 85363090, Bruttogewicht: 765.00 g, VPE: 1.00 pc(s)
Technische Daten
SPD according to EN 61643-11 / IEC 61643-11 | type 1 + type 2 + type 3 / class I + class II + class III |
Max. continuous operating voltage (a.c.) (UC ) | 255 V (50 / 60 Hz) |
Lightning impulse current (10/350 µs) [L1+L2+L3+N-PE] (Itotal ) | 30 kA |
Lightning impulse current (10/350 µs) [L-N] (Iimp ) | 7.5 kA |
Lightning impulse current (10/350 µs) [N-PE] (Iimp ) | 30 kA |
Voltage protection level [L-N] (UP ) | ≤ 1.5 kV |
Voltage protection level [N-PE] (UP ) | ≤ 1.5 kV |
Open-circuit voltage of the combination wave generator (UOC ) | 20 kV |
Max. mains-side overcurrent protection | 160 A gG |
Approvals | VDE |
Art.-Nr. 909231 DSH ZP 2 LSG A TT 255
GTIN 4013364449756, Zolltarifnr.: 85363090, Bruttogewicht: 873.00 g, VPE: 1.00 pc(s)
Technische Daten
SPD according to EN 61643-11 / IEC 61643-11 | type 1 + type 2 + type 3 / class I + class II + class III |
Max. continuous operating voltage (a.c.) (UC ) | 255 V (50 / 60 Hz) |
Lightning impulse current (10/350 µs) [L1+L2+L3+N-PE] (Itotal ) | 50 kA |
Lightning impulse current (10/350 µs) [L-N] (Iimp ) | 12.5 kA |
Lightning impulse current (10/350 µs) [N-PE] (Iimp ) | 50 kA |
Voltage protection level [L-N] (UP ) | ≤ 1.5 kV |
Voltage protection level [N-PE] (UP ) | ≤ 1.5 kV |
Open-circuit voltage of the combination wave generator (UOC ) | 20 kV |
Max. mains-side overcurrent protection | 160 A gG |
Approvals | VDE |
Art.-Nr. 909131 DSH ZP B2 LSG A TT 255
GTIN 4013364449749, Zolltarifnr.: 85363090, Bruttogewicht: 873.00 g, VPE: 1.00 pc(s)
Technische Daten
SPD according to EN 61643-11 / IEC 61643-11 | type 1 + type 2 + type 3 / class I + class II + class III |
Max. continuous operating voltage (a.c.) (UC ) | 255 V (50 / 60 Hz) |
Lightning impulse current (10/350 µs) [L1+L2+L3+N-PE] (Itotal ) | 30 kA |
Lightning impulse current (10/350 µs) [L-N] (Iimp ) | 7.5 kA |
Lightning impulse current (10/350 µs) [N-PE] (Iimp ) | 30 kA |
Voltage protection level [L-N] (UP ) | ≤ 1.5 kV |
Voltage protection level [N-PE] (UP ) | ≤ 1.5 kV |
Open-circuit voltage of the combination wave generator (UOC ) | 20 kV |
Max. mains-side overcurrent protection | 160 A gG |
Approvals | VDE |