DEHNguard modular

  • Prewired complete unit consisting of a base part and plug-in protection modules
  • Energy coordination with other arresters of the Red/Line product family
  • High discharge capacity due to heavy-duty zinc oxide varistors / spark gaps
  • High reliability due to "Thermo Dynamic Control" SPD monitoring device
  • Easy replacement of protection modules without tools due to module locking system with module release button
  • Vibration and shock-tested according to EN 60068-2

Details

3+1 configuration with an increased discharge capacity 4 x 20 kA = 80 kA.
lorem ipsum
lorem ipsum

DEHNguard M TNC ...

Modular surge arrester for use in TN-C systems (3+0 configuration).

4 Produkte

Art.-Nr. 952313 DG M TNC 150

GTIN 4013364123939, Zolltarifnr.: 85363030, Bruttogewicht: 319.70 g, VPE: 1.00 pc(s)


Abbildungen

Weitere Information

DEHNguard M TNC 150 surge arrester
Modular and pluggable three-pole surge arrester
for TN-C systems, width: 3 modules
Type 2 SPD according to EN 61643-11
Fault indication
Max. continuous operating voltage: 150 V a.c.
Voltage protection level: <= 0.7 kV
Nominal discharge current: 15 kA
Short circuit strength: 50 kArms
Energy-coordinated according to IEC 62305-4
with arresters of the Red/Line series

Brand: DEHN
Type: DG M TNC 150
Part No.: 952313
or equivalent.

Zertifikate

 

Technische Daten

SPD according to EN 61643-11 / IEC 61643-11 type 2 / class II
Max. continuous operating voltage (a.c.) (UC ) 150 V (50 / 60 Hz)
Nominal discharge current (8/20 µs) (In ) 15 kA
Max. discharge current (8/20 µs) (Imax ) 40 kA
Voltage protection level (UP ) ≤ 0.7 kV
Max. mains-side overcurrent protection 125 A gG
Approvals KEMA, UL

Artikel 952313 wurde zum Merkzettel hinzugefügt.

Zum Merkzettel

Artikel 952313 wurde zum Warenkorb hinzugefügt.

Zum Warenkorb

Art.-Nr. 952300 DG M TNC 275

GTIN 4013364108431, Zolltarifnr.: 85363030, Bruttogewicht: 355.40 g, VPE: 1.00 pc(s)

Vorgänger

Abbildungen

Weitere Information

DEHNguard M TNC 275 surge arrester
Modular and pluggable three-pole surge arrester
for TN-C systems, width: 3 modules
Type 2 SPD according to EN 61643-11
Fault indication
Max. continuous operating voltage: 275 V a.c.
Voltage protection level: <= 1.5 kV
Nominal discharge current: 20 kA
Short circuit strength: 50 kArms
Energy-coordinated according to IEC 62305-4
with arresters of the Red/Line series

Brand: DEHN
Type: DG M TNC 275
Part No.: 952300
or equivalent.

Zertifikate

 

Technische Daten

SPD according to EN 61643-11 / IEC 61643-11 type 2 / class II
Max. continuous operating voltage (a.c.) (UC ) 275 V (50 / 60 Hz)
Nominal discharge current (8/20 µs) (In ) 20 kA
Max. discharge current (8/20 µs) (Imax ) 40 kA
Voltage protection level (UP ) ≤ 1.5 kV
Max. mains-side overcurrent protection 125 A gG
Approvals KEMA, VDE, UL

Artikel 952300 wurde zum Merkzettel hinzugefügt.

Zum Merkzettel

Artikel 952300 wurde zum Warenkorb hinzugefügt.

Zum Warenkorb

Art.-Nr. 952314 DG M TNC 385

GTIN 4013364124028, Zolltarifnr.: 85363030, Bruttogewicht: 362.50 g, VPE: 1.00 pc(s)

Vorgänger

Abbildungen

Weitere Information

DEHNguard M TNC 385 surge arrester
Modular and pluggable three-pole surge arrester
for TN-C systems, width: 3 modules
Type 2 SPD according to EN 61643-11
Fault indication
Max. continuous operating voltage: 385 V a.c.
Voltage protection level: <= 1.75 kV
Nominal discharge current: 20 kA
Short circuit strength: 25 kArms
Energy-coordinated according to IEC 62305-4
with arresters of the Red/Line series

Brand: DEHN
Type: DG M TNC 385
Part No.: 952314
or equivalent.

Zertifikate

 

Technische Daten

SPD according to EN 61643-11 / IEC 61643-11 type 2 / class II
Max. continuous operating voltage (a.c.) (UC ) 385 V (50 / 60 Hz)
Nominal discharge current (8/20 µs) (In ) 20 kA
Max. discharge current (8/20 µs) (Imax ) 40 kA
Voltage protection level (UP ) ≤ 1.75 kV
Max. mains-side overcurrent protection 125 A gG
Approvals KEMA, UL

Artikel 952314 wurde zum Merkzettel hinzugefügt.

Zum Merkzettel

Artikel 952314 wurde zum Warenkorb hinzugefügt.

Zum Warenkorb

Art.-Nr. 952303 DG M TNC 440

GTIN 4013364120709, Zolltarifnr.: 85363030, Bruttogewicht: 376.30 g, VPE: 1.00 pc(s)


Abbildungen

Weitere Information

DEHNguard M TNC 440 surge arrester
Modular and pluggable three-pole surge arrester
for 400/690 V TN-C systems, width: 3 modules
Type 2 SPD according to EN 61643-11
Fault indication
Max. continuous operating voltage: 440 V a.c.
Voltage protection level: <= 2 kV
Nominal discharge current: 20 kA
Short circuit strength: 25 kArms
Energy-coordinated according to IEC 62305-4
with arresters of the Red/Line series

Brand: DEHN
Type: DG M TNC 440
Part No.: 952303
or equivalent.

Zertifikate

 

Technische Daten

SPD according to EN 61643-11 / IEC 61643-11 type 2 / class II
Max. continuous operating voltage (a.c.) (UC ) 440 V (50 / 60 Hz)
Nominal discharge current (8/20 µs) (In ) 20 kA
Max. discharge current (8/20 µs) (Imax ) 40 kA
Voltage protection level (UP ) ≤ 2 kV
Max. mains-side overcurrent protection 125 A gG
Approvals KEMA, UL

Artikel 952303 wurde zum Merkzettel hinzugefügt.

Zum Merkzettel

Artikel 952303 wurde zum Warenkorb hinzugefügt.

Zum Warenkorb

DEHNguard M TNC ... FM

Modular surge arrester for use in TN-C systems (3+0 configuration); with floating changeover contact.

4 Produkte

Art.-Nr. 952318 DG M TNC 150 FM

GTIN 4013364124011, Zolltarifnr.: 85363030, Bruttogewicht: 326.80 g, VPE: 1.00 pc(s)


Abbildungen

Weitere Information

DEHNguard M TNC 150 FM surge arrester
Modular and pluggable three-pole surge arrester
for TN-C systems, width: 3 modules
With remote signalling contact
Type 2 SPD according to EN 61643-11
Fault indication
Max. continuous operating voltage: 150 V a.c.
Voltage protection level: <= 0.7 kV
Nominal discharge current: 15 kA
Short circuit strength: 50 kArms
Energy-coordinated according to IEC 62305-4
with arresters of the Red/Line series

Brand: DEHN
Type: DG M TNC 150 FM
Part No.: 952318
or equivalent.

Zertifikate

 

Technische Daten

SPD according to EN 61643-11 / IEC 61643-11 type 2 / class II
Max. continuous operating voltage (a.c.) (UC ) 150 V (50 / 60 Hz)
Nominal discharge current (8/20 µs) (In ) 15 kA
Max. discharge current (8/20 µs) (Imax ) 40 kA
Voltage protection level (UP ) ≤ 0.7 kV
Max. mains-side overcurrent protection 125 A gG
Approvals KEMA, UL
Type of remote signalling contact changeover contact

Artikel 952318 wurde zum Merkzettel hinzugefügt.

Zum Merkzettel

Artikel 952318 wurde zum Warenkorb hinzugefügt.

Zum Warenkorb

Art.-Nr. 952305 DG M TNC 275 FM

GTIN 4013364108448, Zolltarifnr.: 85363030, Bruttogewicht: 348.80 g, VPE: 1.00 pc(s)

Vorgänger

Abbildungen

Weitere Information

DEHNguard M TNC 275 FM surge arrester
Modular and pluggable three-pole surge arrester
for 230/400 V TN-C systems, width: 3 modules
With remote signalling contact
Type 2 SPD according to EN 61643-11
Fault indication
Max. continuous operating voltage: 275 V a.c.
Voltage protection level: <= 1.5 kV
Nominal discharge current: 20 kA
Short circuit strength: 50 kArms
Energy-coordinated according to IEC 62305-4
with arresters of the Red/Line series

Brand: DEHN
Type: DG M TNC 275 FM
Part No.: 952305
or equivalent.

Zertifikate

 

Technische Daten

SPD according to EN 61643-11 / IEC 61643-11 type 2 / class II
Max. continuous operating voltage (a.c.) (UC ) 275 V (50 / 60 Hz)
Nominal discharge current (8/20 µs) (In ) 20 kA
Max. discharge current (8/20 µs) (Imax ) 40 kA
Voltage protection level (UP ) ≤ 1.5 kV
Max. mains-side overcurrent protection 125 A gG
Approvals KEMA, VDE, UL
Type of remote signalling contact changeover contact

Artikel 952305 wurde zum Merkzettel hinzugefügt.

Zum Merkzettel

Artikel 952305 wurde zum Warenkorb hinzugefügt.

Zum Warenkorb

Art.-Nr. 952319 DG M TNC 385 FM

GTIN 4013364124035, Zolltarifnr.: 85363030, Bruttogewicht: 370.70 g, VPE: 1.00 pc(s)

Vorgänger

Abbildungen

Weitere Information

DEHNguard M TNC 385 FM surge arrester
Modular and pluggable three-pole surge arrester
for TN-C systems, width: 3 modules
With remote signalling contact
Type 2 SPD according to EN 61643-11
Fault indication
Max. continuous operating voltage: 385 V a.c.
Voltage protection level: <= 1.75 kV
Nominal discharge current: 20 kA
Short circuit strength: 25 kArms
Energy-coordinated according to IEC 62305-4
with arresters of the Red/Line series

Brand: DEHN
Type: DG M TNC 385 FM
Part No.: 952319
or equivalent.

Zertifikate

 

Technische Daten

SPD according to EN 61643-11 / IEC 61643-11 type 2 / class II
Max. continuous operating voltage (a.c.) (UC ) 385 V (50 / 60 Hz)
Nominal discharge current (8/20 µs) (In ) 20 kA
Max. discharge current (8/20 µs) (Imax ) 40 kA
Voltage protection level (UP ) ≤ 1.75 kV
Max. mains-side overcurrent protection 125 A gG
Approvals KEMA, UL
Type of remote signalling contact changeover contact

Artikel 952319 wurde zum Merkzettel hinzugefügt.

Zum Merkzettel

Artikel 952319 wurde zum Warenkorb hinzugefügt.

Zum Warenkorb

Art.-Nr. 952308 DG M TNC 440 FM

GTIN 4013364120716, Zolltarifnr.: 85363030, Bruttogewicht: 383.20 g, VPE: 1.00 pc(s)


Abbildungen

Weitere Information

DEHNguard M TNC 440 FM surge arrester
Modular and pluggable three-pole surge arrester
for 400/690 V TN-C systems, width: 3 modules
With remote signalling contact
Type 2 SPD according to EN 61643-11
Fault indication
Max. continuous operating voltage: 440 V a.c.
Voltage protection level: <= 2 kV
Nominal discharge current: 20 kA
Short circuit strength: 25 kArms
Energy-coordinated according to IEC 62305-4
with arresters of the Red/Line series

Brand: DEHN
Type: DG M TNC 440 FM
Part No.: 952308
or equivalent.

Zertifikate

 

Technische Daten

SPD according to EN 61643-11 / IEC 61643-11 type 2 / class II
Max. continuous operating voltage (a.c.) (UC ) 440 V (50 / 60 Hz)
Nominal discharge current (8/20 µs) (In ) 20 kA
Max. discharge current (8/20 µs) (Imax ) 40 kA
Voltage protection level (UP ) ≤ 2 kV
Max. mains-side overcurrent protection 125 A gG
Approvals KEMA, UL
Type of remote signalling contact changeover contact

Artikel 952308 wurde zum Merkzettel hinzugefügt.

Zum Merkzettel

Artikel 952308 wurde zum Warenkorb hinzugefügt.

Zum Warenkorb

DEHNguard M TNS ...

Modular surge arrester for use in TN-S systems (4+0 configuration).

3 Produkte

Art.-Nr. 952403 DG M TNS 150

GTIN 4013364128569, Zolltarifnr.: 85363030, Bruttogewicht: 443.20 g, VPE: 1.00 pc(s)


Abbildungen

Weitere Information

DEHNguard M TNS 150 surge arrester
Modular and pluggable four-pole surge arrester
for TN-S systems, width: 4 modules
Type 2 SPD according to EN 61643-11
Fault indication
Max. continuous operating voltage: 150 V a.c.
Voltage protection level: <= 0.7 kV
Nominal discharge current: 15 kA
Short circuit strength: 50 kArms
Energy-coordinated according to IEC 62305-4
with arresters of the Red/Line series

Brand: DEHN
Type: DG M TNS 150
Part No.: 952403
or equivalent.

Zertifikate

 

Technische Daten

SPD according to EN 61643-11 / IEC 61643-11 type 2 / class II
Max. continuous operating voltage (a.c.) (UC ) 150 V (50 / 60 Hz)
Nominal discharge current (8/20 µs) (In ) 15 kA
Max. discharge current (8/20 µs) (Imax ) 40 kA
Voltage protection level [L-PE]/[N-PE] (UP ) ≤ 0.7 / ≤ 0.7 kV
Max. mains-side overcurrent protection 125 A gG
Approvals KEMA, UL

Artikel 952403 wurde zum Merkzettel hinzugefügt.

Zum Merkzettel

Artikel 952403 wurde zum Warenkorb hinzugefügt.

Zum Warenkorb

Art.-Nr. 952400 DG M TNS 275

GTIN 4013364108455, Zolltarifnr.: 85363030, Bruttogewicht: 444.00 g, VPE: 1.00 pc(s)

Vorgänger

Abbildungen

Weitere Information

DEHNguard M TNS 275 surge arrester
Modular and pluggable four-pole surge arrester
for 230/400 V TN-S systems, width: 4 modules
Type 2 SPD according to EN 61643-11
Fault indication
Max. continuous operating voltage: 275 V a.c.
Voltage protection level: <= 1.5 kV
Nominal discharge current: 20 kA
Short circuit strength: 50 kArms
Energy-coordinated according to IEC 62305-4
with arresters of the Red/Line series

Brand: DEHN
Type: DG M TNS 275
Part No.: 952400
or equivalent.

Zertifikate

 

Technische Daten

SPD according to EN 61643-11 / IEC 61643-11 type 2 / class II
Max. continuous operating voltage (a.c.) (UC ) 275 V (50 / 60 Hz)
Nominal discharge current (8/20 µs) (In ) 20 kA
Max. discharge current (8/20 µs) (Imax ) 40 kA
Voltage protection level [L-PE]/[N-PE] (UP ) ≤ 1.5 / ≤ 1.5 kV
Max. mains-side overcurrent protection 125 A gG
Approvals KEMA, VDE, UL

Artikel 952400 wurde zum Merkzettel hinzugefügt.

Zum Merkzettel

Artikel 952400 wurde zum Warenkorb hinzugefügt.

Zum Warenkorb

Art.-Nr. 952404 DG M TNS 385

GTIN 4013364128545, Zolltarifnr.: 85363030, Bruttogewicht: 499.50 g, VPE: 1.00 pc(s)

Vorgänger

Abbildungen

Weitere Information

DEHNguard M TNS 385 surge arrester
Modular and pluggable four-pole surge arrester
for TN-S systems, width: 4 modules
Type 2 SPD according to EN 61643-11
Fault indication
Max. continuous operating voltage: 385 V a.c.
Voltage protection level: <= 1.75 kV
Nominal discharge current: 20 kA
Short circuit strength: 25 kArms
Energy-coordinated according to IEC 62305-4
with arresters of the Red/Line series

Brand: DEHN
Type: DG M TNS 385
Part No.: 952404
or equivalent.

Zertifikate

 

Technische Daten

SPD according to EN 61643-11 / IEC 61643-11 type 2 / class II
Max. continuous operating voltage (a.c.) (UC ) 385 V (50 / 60 Hz)
Nominal discharge current (8/20 µs) (In ) 20 kA
Max. discharge current (8/20 µs) (Imax ) 40 kA
Voltage protection level [L-PE]/[N-PE] (UP ) ≤ 1.75 / ≤ 1.75 kV
Max. mains-side overcurrent protection 125 A gG
Approvals KEMA, UL

Artikel 952404 wurde zum Merkzettel hinzugefügt.

Zum Merkzettel

Artikel 952404 wurde zum Warenkorb hinzugefügt.

Zum Warenkorb

DEHNguard M TNS ... FM

Modular surge arrester for use in TN-S systems (4+0 configuration); with floating changeover contact.

3 Produkte

Art.-Nr. 952408 DG M TNS 150 FM

GTIN 4013364128576, Zolltarifnr.: 85363030, Bruttogewicht: 451.60 g, VPE: 1.00 pc(s)


Abbildungen

Weitere Information

DEHNguard M TNS 150 FM surge arrester
Modular and pluggable four-pole surge arrester
for TN-S systems, width: 4 modules
With remote signalling contact
Type 2 SPD according to EN 61643-11
Fault indication
Max. continuous operating voltage: 150 V a.c.
Voltage protection level: <= 0.7 kV
Nominal discharge current: 15 kA
Short circuit strength: 50 kArms
Energy-coordinated according to IEC 62305-4
with arresters of the Red/Line series

Brand: DEHN
Type: DG M TNS 150 FM
Part No.: 952408
or equivalent.

Zertifikate

 

Technische Daten

SPD according to EN 61643-11 / IEC 61643-11 type 2 / class II
Max. continuous operating voltage (a.c.) (UC ) 150 V (50 / 60 Hz)
Nominal discharge current (8/20 µs) (In ) 15 kA
Max. discharge current (8/20 µs) (Imax ) 40 kA
Voltage protection level [L-PE]/[N-PE] (UP ) ≤ 0.7 / ≤ 0.7 kV
Max. mains-side overcurrent protection 125 A gG
Approvals KEMA, UL
Type of remote signalling contact changeover contact

Artikel 952408 wurde zum Merkzettel hinzugefügt.

Zum Merkzettel

Artikel 952408 wurde zum Warenkorb hinzugefügt.

Zum Warenkorb

Art.-Nr. 952405 DG M TNS 275 FM

GTIN 4013364108462, Zolltarifnr.: 85363030, Bruttogewicht: 479.00 g, VPE: 1.00 pc(s)

Vorgänger

Abbildungen

Weitere Information

DEHNguard M TNS 275 FM surge arrester
Modular and pluggable four-pole surge arrester
for 230/400 V TN-S systems, width: 4 modules
With remote signalling contact
Type 2 SPD according to EN 61643-11
Fault indication
Max. continuous operating voltage: 275 V a.c.
Voltage protection level: <= 1.5 kV
Nominal discharge current: 20 kA
Short circuit strength: 50 kArms
Energy-coordinated according to IEC 62305-4
with arresters of the Red/Line series

Brand: DEHN
Type: DG M TNS 275 FM
Part No.: 952405
or equivalent.

Zertifikate

 

Technische Daten

SPD according to EN 61643-11 / IEC 61643-11 type 2 / class II
Max. continuous operating voltage (a.c.) (UC ) 275 V (50 / 60 Hz)
Nominal discharge current (8/20 µs) (In ) 20 kA
Max. discharge current (8/20 µs) (Imax ) 40 kA
Voltage protection level [L-PE]/[N-PE] (UP ) ≤ 1.5 / ≤ 1.5 kV
Max. mains-side overcurrent protection 125 A gG
Approvals KEMA, VDE, UL
Type of remote signalling contact changeover contact

Artikel 952405 wurde zum Merkzettel hinzugefügt.

Zum Merkzettel

Artikel 952405 wurde zum Warenkorb hinzugefügt.

Zum Warenkorb

Art.-Nr. 952409 DG M TNS 385 FM

GTIN 4013364128552, Zolltarifnr.: 85363030, Bruttogewicht: 508.40 g, VPE: 1.00 pc(s)

Vorgänger

Abbildungen

Weitere Information

DEHNguard M TNS 385 FM surge arrester
Modular and pluggable four-pole surge arrester
for TN-S systems, width: 4 modules
With remote signalling contact
Type 2 SPD according to EN 61643-11
Fault indication
Max. continuous operating voltage: 385 V a.c.
Voltage protection level: <= 1.75 kV
Nominal discharge current: 20 kA
Short circuit strength: 25 kArms
Energy-coordinated according to IEC 62305-4
with arresters of the Red/Line series

Brand: DEHN
Type: DG M TNS 385 FM
Part No.: 952409
or equivalent.

Zertifikate

 

Technische Daten

SPD according to EN 61643-11 / IEC 61643-11 type 2 / class II
Max. continuous operating voltage (a.c.) (UC ) 385 V (50 / 60 Hz)
Nominal discharge current (8/20 µs) (In ) 20 kA
Max. discharge current (8/20 µs) (Imax ) 40 kA
Voltage protection level [L-PE]/[N-PE] (UP ) ≤ 1.75 / ≤ 1.75 kV
Max. mains-side overcurrent protection 125 A gG
Approvals KEMA, UL
Type of remote signalling contact changeover contact

Artikel 952409 wurde zum Merkzettel hinzugefügt.

Zum Merkzettel

Artikel 952409 wurde zum Warenkorb hinzugefügt.

Zum Warenkorb

DEHNguard M H TT ... (FM)

Modular surge arrester with a high total discharge capacity in the N-PE path for TT and TN-S systems (3+1 configuration); meets the increased safety requirements according to the new VDE 0100-534 standard for use at the origin at the electrical installation; with floating remote signalling contact.

2 Produkte

Art.-Nr. 952381 DG M H TT 275

GTIN 4013364318144, Zolltarifnr.: 85363030, Bruttogewicht: 435.03 g, VPE: 1.00 pc(s)


Abbildungen

Weitere Information

DEHNguard M H TT 275 surge arrester
4-pole, modular surge arrester with an increased
discharge capacity for 230/400 V TT and TN-S systems
Width: 4 modules, Fault indication
SPD Type 2 according to EN 61643-11
Max. continuous voltage: 275 V ac
Voltage protection level: <= 1.5 kV
Nominal discharge current [L-N]: 20 kA
Nominal discharge current [N-PE]: 80 kA
Short circuit withstand capability: 50 kArms
Energy-coordinated according to
IEC 62305-4 with SPDs of the Red/Line family

Brand: DEHN
Type: DG M H TT 275
Part No.: 952381
or equivalent.

Zertifikate

 

Technische Daten

SPD according to EN 61643-11 / IEC 61643-11 type 2 / class II
Max. continuous operating voltage (a.c.) [L-N] (UC ) 275 V (50 / 60 Hz)
Nominal discharge current (8/20 µs) [L-N] (In ) 20 kA
Nominal discharge current (8/20 µs) [N-PE] (In ) 80 kA
Max. discharge current (8/20 µs) [L-N] (Imax ) 40 kA
Max. discharge current (8/20 µs) [N-PE] (Imax ) 120 kA
Lightning impulse current (10/350 µs) [N-PE] (Iimp ) 40 kA
Voltage protection level [L-N]/[N-PE] (UP ) ≤ 1.5 / ≤ 1.5 kV
Max. mains-side overcurrent protection 125 A gG
Approvals KEMA

Artikel 952381 wurde zum Merkzettel hinzugefügt.

Zum Merkzettel

Artikel 952381 wurde zum Warenkorb hinzugefügt.

Zum Warenkorb

Art.-Nr. 952385 DG M H TT 275 FM

GTIN 4013364318137, Zolltarifnr.: 85363030, Bruttogewicht: 441.30 g, VPE: 1.00 pc(s)


Abbildungen

Weitere Information

DEHNguard M H TT 275 FM surge arrester
4-pole, modular surge arrester with an increased
discharge capacity for 230/400 V TT and TN-S systems,
Width: 4 modules, Fault indication
With remote signalling contact for control device
SPD Type 2 according to EN 61643-11
Max. continuous voltage: 275 V ac
Voltage protection level: <= 1.5 kV
Nominal discharge current [L-N]: 20 kA
Nominal discharge current [N-PE]: 80 kA
Short circuit withstand capability: 50 kArms
Energy-coordinated according to
IEC 62305-4 of the Red/Line family

Brand: DEHN
Type: DG M H TT 275 FM
Part No.: 952385
or equivalent.

Zertifikate

 

Technische Daten

SPD according to EN 61643-11 / IEC 61643-11 type 2 / class II
Max. continuous operating voltage (a.c.) [L-N] (UC ) 275 V (50 / 60 Hz)
Nominal discharge current (8/20 µs) [L-N] (In ) 20 kA
Nominal discharge current (8/20 µs) [N-PE] (In ) 80 kA
Max. discharge current (8/20 µs) [L-N] (Imax ) 40 kA
Max. discharge current (8/20 µs) [N-PE] (Imax ) 120 kA
Lightning impulse current (10/350 µs) [N-PE] (Iimp ) 40 kA
Voltage protection level [L-N]/[N-PE] (UP ) ≤ 1.5 / ≤ 1.5 kV
Max. mains-side overcurrent protection 125 A gG
Approvals KEMA
Type of remote signalling contact changeover contact

Artikel 952385 wurde zum Merkzettel hinzugefügt.

Zum Merkzettel

Artikel 952385 wurde zum Warenkorb hinzugefügt.

Zum Warenkorb

DEHNguard M TT ...

Modular surge arrester for use in TT and TN-S systems (3+1 configuration).

4 Produkte

Art.-Nr. 952323 DG M TT 150

GTIN 4013364133235, Zolltarifnr.: 85363030, Bruttogewicht: 406.90 g, VPE: 1.00 pc(s)


Abbildungen

Weitere Information

DEHNguard M TT 150 surge arrester
Modular and pluggable four-pole surge arrester
for TT and TN-S systems, width: 4 modules
Type 2 SPD according to EN 61643-11
Fault indication
Max. continuous operating voltage: 150 V a.c.
Voltage protection level: <= 0.7 kV
Nominal discharge current: 15 kA
Short circuit strength: 50 kArms
Energy-coordinated according to IEC 62305-4
with arresters of the Red/Line series

Brand: DEHN
Type: DG M TT 150
Part No.: 952323
or equivalent.

Zertifikate

 

Technische Daten

SPD according to EN 61643-11 / IEC 61643-11 type 2 / class II
Max. continuous operating voltage (a.c.) [L-N] (UC ) 150 V (50 / 60 Hz)
Nominal discharge current (8/20 µs) (In ) 15 kA
Max. discharge current (8/20 µs) (Imax ) 40 kA
Lightning impulse current (10/350 µs) [N-PE] (Iimp ) 12 kA
Voltage protection level [L-N]/[N-PE] (UP ) ≤ 0.7 / ≤ 1.5 kV
Max. mains-side overcurrent protection 125 A gG

Artikel 952323 wurde zum Merkzettel hinzugefügt.

Zum Merkzettel

Artikel 952323 wurde zum Warenkorb hinzugefügt.

Zum Warenkorb

Art.-Nr. 952310 DG M TT 275

GTIN 4013364108479, Zolltarifnr.: 85363030, Bruttogewicht: 435.03 g, VPE: 1.00 pc(s)

Vorgänger

Abbildungen

Weitere Information

DEHNguard M TT 275 surge arrester
Modular and pluggable four-pole surge arrester
for 230/400 V TT and TN-S systems, width: 4 modules
Type 2 SPD according to EN 61643-11
Fault indication
Max. continuous operating voltage: 275 V a.c.
Voltage protection level: <= 1.25 kV
Nominal discharge current: 20 kA
Short circuit strength: 50 kArms
Energy-coordinated according to IEC 62305-4
with arresters of the Red/Line series

Brand: DEHN
Type: DG M TT 275
Part No.: 952310
or equivalent.

Zertifikate

 

Technische Daten

SPD according to EN 61643-11 / IEC 61643-11 type 2 / class II
Max. continuous operating voltage (a.c.) [L-N] (UC ) 275 V (50 / 60 Hz)
Nominal discharge current (8/20 µs) (In ) 20 kA
Max. discharge current (8/20 µs) (Imax ) 40 kA
Lightning impulse current (10/350 µs) [N-PE] (Iimp ) 12 kA
Voltage protection level [L-N]/[N-PE] (UP ) ≤ 1.5 / ≤ 1.5 kV
Max. mains-side overcurrent protection 125 A gG
Approvals KEMA, VDE, UL

Artikel 952310 wurde zum Merkzettel hinzugefügt.

Zum Merkzettel

Artikel 952310 wurde zum Warenkorb hinzugefügt.

Zum Warenkorb

Art.-Nr. 952320 DG M TT 320

GTIN 4013364126794, Zolltarifnr.: 85363030, Bruttogewicht: 442.08 g, VPE: 1.00 pc(s)

Vorgänger

Abbildungen

Weitere Information

DEHNguard M TT 320 surge arrester
Modular and pluggable four-pole surge arrester
for TT and TN-S systems, width: 4 modules
Fault indication
Max. continuous operating voltage: 320 V a.c.
Voltage protection level: <= 1.5 kV
Nominal discharge current: 20 kA
Short circuit strength: 25 kArms
Energy-coordinated according to IEC 62305-4
with arresters of the Red/Line series

Brand: DEHN
Type: DG M TT 320
Part No.: 952320
or equivalent.

Zertifikate

 

Technische Daten

SPD according to EN 61643-11 / IEC 61643-11 type 2 / class II
Max. continuous operating voltage (a.c.) [L-N] (UC ) 320 V (50 / 60 Hz)
Nominal discharge current (8/20 µs) (In ) 20 kA
Max. discharge current (8/20 µs) (Imax ) 40 kA
Lightning impulse current (10/350 µs) [N-PE] (Iimp ) 12 kA
Voltage protection level [L-N]/[N-PE] (UP ) ≤ 1.5 / ≤ 1.5 kV
Max. mains-side overcurrent protection 125 A gG
Approvals KEMA

Artikel 952320 wurde zum Merkzettel hinzugefügt.

Zum Merkzettel

Artikel 952320 wurde zum Warenkorb hinzugefügt.

Zum Warenkorb

Art.-Nr. 952311 DG M TT 385

GTIN 4013364119390, Zolltarifnr.: 85363030, Bruttogewicht: 458.20 g, VPE: 1.00 pc(s)

Vorgänger

Abbildungen

Weitere Information

DEHNguard M TT 385 surge arrester
Modular and pluggable four-pole surge arrester
for TT and TN-S systems, width: 4 modules
Fault indication
Type 2 SPD according to EN 61643-11
Max. continuous operating voltage: 385 V a.c.
Voltage protection level: <= 1.75 kV
Nominal discharge current: 20 kA
Short circuit strength: 25 kArms
Energy-coordinated according to IEC 62305-4
with arresters of the Red/Line series

Brand: DEHN
Type: DG M TT 385
Part No.: 952311
or equivalent.

Zertifikate

 

Technische Daten

SPD according to EN 61643-11 / IEC 61643-11 type 2 / class II
Max. continuous operating voltage (a.c.) [L-N] (UC ) 385 V (50 / 60 Hz)
Nominal discharge current (8/20 µs) (In ) 20 kA
Max. discharge current (8/20 µs) (Imax ) 40 kA
Lightning impulse current (10/350 µs) [N-PE] (Iimp ) 12 kA
Voltage protection level [L-N]/[N-PE] (UP ) ≤ 1.75 / ≤ 1.5 kV
Max. mains-side overcurrent protection 125 A gG
Approvals KEMA, UL

Artikel 952311 wurde zum Merkzettel hinzugefügt.

Zum Merkzettel

Artikel 952311 wurde zum Warenkorb hinzugefügt.

Zum Warenkorb

DEHNguard M TT ... FM

Modular surge arrester for use in TT and TN-S systems (3+1 configuration); with floating remote signalling contact.

4 Produkte

Art.-Nr. 952328 DG M TT 150 FM

GTIN 4013364133242, Zolltarifnr.: 85363030, Bruttogewicht: 416.40 g, VPE: 1.00 pc(s)


Abbildungen

Weitere Information

DEHNguard M TT 150 FM surge arrester
Modular and pluggable four-pole surge arrester
for TT and TN-S systems, width: 4 modules
With remote signalling contact
Type 2 SPD according to EN 61643-11
Fault indication
Max. continuous operating voltage: 150 V a.c.
Voltage protection level: <= 0.7 kV
Nominal discharge current: 15 kA
Short circuit strength: 50 kArms
Energy-coordinated according to IEC 62305-4
with arresters of the Red/Line series

Brand: DEHN
Type: DG M TT 150 FM
Part No.: 952328
or equivalent.

Zertifikate

 

Technische Daten

SPD according to EN 61643-11 / IEC 61643-11 type 2 / class II
Max. continuous operating voltage (a.c.) [L-N] (UC ) 150 V (50 / 60 Hz)
Nominal discharge current (8/20 µs) (In ) 15 kA
Max. discharge current (8/20 µs) (Imax ) 40 kA
Lightning impulse current (10/350 µs) [N-PE] (Iimp ) 12 kA
Voltage protection level [L-N]/[N-PE] (UP ) ≤ 0.7 / ≤ 1.5 kV
Max. mains-side overcurrent protection 125 A gG
Approvals UL
Type of remote signalling contact changeover contact

Artikel 952328 wurde zum Merkzettel hinzugefügt.

Zum Merkzettel

Artikel 952328 wurde zum Warenkorb hinzugefügt.

Zum Warenkorb

Art.-Nr. 952315 DG M TT 275 FM

GTIN 4013364108486, Zolltarifnr.: 85363030, Bruttogewicht: 441.30 g, VPE: 1.00 pc(s)

Vorgänger

Abbildungen

Weitere Information

DEHNguard M TT 275 FM surge arrester
Modular and pluggable four-pole surge arrester
for 230/400 V TT and TN-S systems, width: 4 modules
With remote signalling contact
Type 2 SPD according to EN 61643-11
Fault indication
Max. continuous operating voltage: 275 V a.c.
Voltage protection level: <= 1.5 kV
Nominal discharge current: 20 kA
Short circuit strength: 50 kArms
Energy-coordinated according to IEC 62305-4
with arresters of the Red/Line series

Brand: DEHN
Type: DG M TT 275 FM
Part No.: 952315
or equivalent.

Zertifikate

 

Technische Daten

SPD according to EN 61643-11 / IEC 61643-11 type 2 / class II
Max. continuous operating voltage (a.c.) [L-N] (UC ) 275 V (50 / 60 Hz)
Nominal discharge current (8/20 µs) (In ) 20 kA
Max. discharge current (8/20 µs) (Imax ) 40 kA
Lightning impulse current (10/350 µs) [N-PE] (Iimp ) 12 kA
Voltage protection level [L-N]/[N-PE] (UP ) ≤ 1.5 / ≤ 1.5 kV
Max. mains-side overcurrent protection 125 A gG
Approvals KEMA, VDE, UL
Type of remote signalling contact changeover contact

Artikel 952315 wurde zum Merkzettel hinzugefügt.

Zum Merkzettel

Artikel 952315 wurde zum Warenkorb hinzugefügt.

Zum Warenkorb

Art.-Nr. 952325 DG M TT 320 FM

GTIN 4013364126800, Zolltarifnr.: 85363030, Bruttogewicht: 450.80 g, VPE: 1.00 pc(s)

Vorgänger

Abbildungen

Weitere Information

DEHNguard M TT 320 FM surge arrester
Modular and pluggable four-pole surge arrester
for TT and TN-S systems, width: 4 modules
With remote signalling contact
Type 2 SPD according to EN 61643-11
Fault indication
Max. continuous operating voltage: 320 V a.c.
Voltage protection level: <= 1.5 kV
Nominal discharge current: 20 kA
Short circuit strength: 25 kArms
Energy-coordinated according to IEC 62305-4
with arresters of the Red/Line series

Brand: DEHN
Type: DG M TT 320 FM
Part No.: 952325
or equivalent.

Zertifikate

 

Technische Daten

SPD according to EN 61643-11 / IEC 61643-11 type 2 / class II
Max. continuous operating voltage (a.c.) [L-N] (UC ) 320 V (50 / 60 Hz)
Nominal discharge current (8/20 µs) (In ) 20 kA
Max. discharge current (8/20 µs) (Imax ) 40 kA
Lightning impulse current (10/350 µs) [N-PE] (Iimp ) 12 kA
Voltage protection level [L-N]/[N-PE] (UP ) ≤ 1.5 / ≤ 1.5 kV
Max. mains-side overcurrent protection 125 A gG
Approvals KEMA
Type of remote signalling contact changeover contact

Artikel 952325 wurde zum Merkzettel hinzugefügt.

Zum Merkzettel

Artikel 952325 wurde zum Warenkorb hinzugefügt.

Zum Warenkorb

Art.-Nr. 952316 DG M TT 385 FM

GTIN 4013364119406, Zolltarifnr.: 85363030, Bruttogewicht: 462.10 g, VPE: 1.00 pc(s)

Vorgänger

Abbildungen

Weitere Information

DEHNguard M TT 385 FM surge arrester
Modular and pluggable four-pole surge arrester
for TT and TN-S systems, width: 4 modules
With remote signalling contact
Type 2 SPD according to EN 61643-11
Fault indication
Max. continuous operating voltage: 385 V a.c.
Voltage protection level: <= 1.75 kV
Nominal discharge current: 20 kA
Short circuit strength: 25 kArms
Energy-coordinated according to IEC 62305-4
with arresters of the Red/Line series

Brand: DEHN
Type: DG M TT 385 FM
Part No.: 952316
or equivalent.

Zertifikate

 

Technische Daten

SPD according to EN 61643-11 / IEC 61643-11 type 2 / class II
Max. continuous operating voltage (a.c.) [L-N] (UC ) 385 V (50 / 60 Hz)
Nominal discharge current (8/20 µs) (In ) 20 kA
Max. discharge current (8/20 µs) (Imax ) 40 kA
Lightning impulse current (10/350 µs) [N-PE] (Iimp ) 12 kA
Voltage protection level [L-N]/[N-PE] (UP ) ≤ 1.75 / ≤ 1.5 kV
Max. mains-side overcurrent protection 125 A gG
Approvals KEMA, UL
Type of remote signalling contact changeover contact

Artikel 952316 wurde zum Merkzettel hinzugefügt.

Zum Merkzettel

Artikel 952316 wurde zum Warenkorb hinzugefügt.

Zum Warenkorb