DEHNrail modular

  • Two-pole surge arrester consisting of a base part and a plug-in protection module
  • High discharge capacity due to heavy-duty zinc oxide varistor / spark gap combination
  • Energy coordination with other arresters of the Red/Line product family
  • Operating state / fault indication by green / red indicator flag in the inspection window
  • Narrow (modular) design according to DIN 43880
  • Easy replacement of protection modules due to module locking system with module release button
  • Vibration and shock-tested according to EN 60068-2

Details

lorem ipsum

DEHNrail M 2P ...

Two-pole surge arrester consisting of a base part and a plug-in protection module.

5 Produkte

Art.-Nr. 953201 DR M 2P 30

GTIN 4013364109674, Zolltarifnr.: 85363030, Bruttogewicht: 90.60 g, VPE: 1.00 pc(s)

Vorgänger

Abbildungen

Weitere Information

DEHNrail M 2P 30 surge arrester
Modular and pluggable two-pole
surge arrester for protecting
terminal devices of industrial electronics equipment
Width: 1 module, Fault indication
Type 3 SPD according to EN 61643-11
Max. continuous operating voltage: 30 V a.c./d.c.
Total discharge current: 2 kA
Voltage protection level (L/N): < 0.18 kV
Backup fuse: 25 A gG or B 25 A
Energy-coordinated according to IEC 62305-4
with arresters of the Red/Line family

Brand: DEHN
Type: DR M 2P 30
Part No.: 953201
or equivalent.

Zertifikate

 

Technische Daten

SPD according to EN 61643-11 / IEC 61643-11 type 3 / class III
Max. continuous operating voltage (a.c.) (UC ) 30 V (50 / 60 Hz)
Max. continuous operating voltage (d.c.) (UC ) 30 V
Nominal discharge current (8/20 µs) (In ) 1 kA
Total discharge current (8/20 µs) [L+N-PE] (Itotal ) 2 kA
Voltage protection level [L-N] / [L/N-PE] (UP ) ≤ 180 / ≤ 630 V
Max. mains-side overcurrent protection 25 A gG or B 25 A
Approvals KEMA, VDE, UL, CSA

Artikel 953201 wurde zum Merkzettel hinzugefügt.

Zum Merkzettel

Artikel 953201 wurde zum Warenkorb hinzugefügt.

Zum Warenkorb

Art.-Nr. 953202 DR M 2P 60

GTIN 4013364109681, Zolltarifnr.: 85363030, Bruttogewicht: 91.80 g, VPE: 1.00 pc(s)

Vorgänger

Abbildungen

Weitere Information

DEHNrail M 2P 60 surge arrester
Modular and pluggable two-pole
surge arrester for protecting
terminal devices of industrial electronics equipment
Width: 1 module, Fault indication
Type 3 SPD according to EN 61643-11
Max. continuous operating voltage: 60 V a.c./d.c.
Total discharge current: 2 kA
Voltage protection level (L/N): < 0.35 kV
Backup fuse: 25 A gG or B 25 A
Energy-coordinated according to IEC 62305-4
with arresters of the Red/Line series

Brand: DEHN
Type: DR M 2P 60
Part No.: 953202
or equivalent.

Zertifikate

 

Technische Daten

SPD according to EN 61643-11 / IEC 61643-11 type 3 / class III
Max. continuous operating voltage (a.c.) (UC ) 60 V (50 / 60 Hz)
Max. continuous operating voltage (d.c.) (UC ) 60 V
Nominal discharge current (8/20 µs) (In ) 1 kA
Total discharge current (8/20 µs) [L+N-PE] (Itotal ) 2 kA
Voltage protection level [L-N] / [L/N-PE] (UP ) ≤ 350 / ≤ 730 V
Max. mains-side overcurrent protection 25 A gG or B 25 A
Approvals KEMA, VDE, UL, CSA

Artikel 953202 wurde zum Merkzettel hinzugefügt.

Zum Merkzettel

Artikel 953202 wurde zum Warenkorb hinzugefügt.

Zum Warenkorb

Art.-Nr. 953203 DR M 2P 75

GTIN 4013364109698, Zolltarifnr.: 85363030, Bruttogewicht: 89.80 g, VPE: 1.00 pc(s)

Vorgänger

Abbildungen

Weitere Information

DEHNrail M 2P 75 surge arrester
Modular and pluggable two-pole
surge arrester for protecting
terminal devices of industrial electronics equipment
Width: 1 module, Fault indication
Type 3 SPD according to EN 61643-11
Max. continuous operating voltage: 75 V a.c./d.c.
Total discharge current: 4 kA
Voltage protection level (L/N): < 0.4 kV
Backup fuse: 25 A gG or B 25 A
Energy-coordinated according to IEC 62305-4
with arresters of the Red/Line series

Brand: DEHN
Type: DR M 2P 75
Part No.: 953203
or equivalent.

Zertifikate

 

Technische Daten

SPD according to EN 61643-11 / IEC 61643-11 type 3 / class III
Max. continuous operating voltage (a.c.) (UC ) 75 V (50 / 60 Hz)
Max. continuous operating voltage (d.c.) (UC ) 75 V
Nominal discharge current (8/20 µs) (In ) 2 kA
Total discharge current (8/20 µs) [L+N-PE] (Itotal ) 4 kA
Voltage protection level [L-N] / [L/N-PE] (UP ) ≤ 400 / ≤ 730 V
Max. mains-side overcurrent protection 25 A gG or B 25 A
Approvals KEMA, VDE, UL, CSA

Artikel 953203 wurde zum Merkzettel hinzugefügt.

Zum Merkzettel

Artikel 953203 wurde zum Warenkorb hinzugefügt.

Zum Warenkorb

Art.-Nr. 953204 DR M 2P 150

GTIN 4013364109704, Zolltarifnr.: 85363030, Bruttogewicht: 90.00 g, VPE: 1.00 pc(s)

Vorgänger

Abbildungen

Weitere Information

DEHNrail M 2P 150 surge arrester
Modular and pluggable two-pole
surge arrester for protecting
terminal devices of industrial electronics equipment
Width: 1 module, Fault indication
Type 3 SPD according to EN 61643-11
Max. continuous operating voltage: 150 V a.c./d.c.
Total discharge current: 4 kA
Voltage protection level (L/N): < 0.64 kV
Backup fuse: 25 A gG or B 25 A
Energy-coordinated according to IEC 62305-4
with arresters of the Red/Line series

Brand: DEHN
Type: DR M 2P 150
Part No.: 953204
or equivalent.

Zertifikate

 

Technische Daten

SPD according to EN 61643-11 / IEC 61643-11 type 3 / class III
Max. continuous operating voltage (a.c.) (UC ) 150 V (50 / 60 Hz)
Max. continuous operating voltage (d.c.) (UC ) 150 V
Nominal discharge current (8/20 µs) (In ) 2 kA
Total discharge current (8/20 µs) [L+N-PE] (Itotal ) 4 kA
Voltage protection level [L-N] / [L/N-PE] (UP ) ≤ 640 / ≤ 800 V
Max. mains-side overcurrent protection 25 A gG or B 25 A
Approvals KEMA, VDE, UL, CSA

Artikel 953204 wurde zum Merkzettel hinzugefügt.

Zum Merkzettel

Artikel 953204 wurde zum Warenkorb hinzugefügt.

Zum Warenkorb

Art.-Nr. 953200 DR M 2P 255

GTIN 4013364108301, Zolltarifnr.: 85363030, Bruttogewicht: 91.70 g, VPE: 1.00 pc(s)

Vorgänger

Abbildungen

Weitere Information

DEHNrail M 2P 255 surge arrester
Modular and pluggable two-pole
surge arrester for protecting
terminal devices of industrial electronics equipment
Width: 1 module, Fault indication
Type 3 SPD according to EN 61643-11
Max. continuous operating voltage: 255 V a.c./d.c.
Total discharge current: 5 kA
Voltage protection level (L/N): < 1.25 kV
Backup fuse: 25 A gG or B 25 A
Energy-coordinated according to IEC 62305-4
with arresters of the Red/Line series

Brand: DEHN
Type: DR M 2P 255
Part No.: 953200
or equivalent.

Zertifikate

 

Technische Daten

SPD according to EN 61643-11 / IEC 61643-11 type 3 / class III
Max. continuous operating voltage (a.c.) (UC ) 255 V (50 / 60 Hz)
Max. continuous operating voltage (d.c.) (UC ) 255 V
Nominal discharge current (8/20 µs) (In ) 3 kA
Total discharge current (8/20 µs) [L+N-PE] (Itotal ) 5 kA
Voltage protection level [L-N] / [L/N-PE] (UP ) ≤ 1250 / ≤ 1500 V
Max. mains-side overcurrent protection 25 A gG or B 25 A
Approvals KEMA, VDE, UL, CSA

Artikel 953200 wurde zum Merkzettel hinzugefügt.

Zum Merkzettel

Artikel 953200 wurde zum Warenkorb hinzugefügt.

Zum Warenkorb

DEHNrail M 2P ... FM

Two-pole surge arrester consisting of a base part and a plug-in protection module; with floating remote signalling contact.

5 Produkte

Art.-Nr. 953206 DR M 2P 30 FM

GTIN 4013364109711, Zolltarifnr.: 85363030, Bruttogewicht: 94.50 g, VPE: 1.00 pc(s)

Vorgänger

Abbildungen

Weitere Information

DEHNrail M 2P 30 FM surge arrester
Modular and pluggable two-pole surge arrester for protecting
terminal devices of industrial electronics equipment
Width: 1 module, Fault indication
With remote signalling contact
Type 3 SPD according to EN 61643-11
Max. continuous operating voltage: 30 V a.c./d.c.
Total discharge current: 2 kA
Voltage protection level (L/N): < 0.18 kV
Backup fuse: 25 A gG or B 25 A
Energy-coordinated according to IEC 62305-4
with arresters of the Red/Line series

Brand: DEHN
Type: DR M 2P 30 FM
Part No.: 953206
or equivalent.

Zertifikate

 

Technische Daten

SPD according to EN 61643-11 / IEC 61643-11 type 3 / class III
Max. continuous operating voltage (a.c.) (UC ) 30 V (50 / 60 Hz)
Max. continuous operating voltage (d.c.) (UC ) 30 V
Nominal discharge current (8/20 µs) (In ) 1 kA
Total discharge current (8/20 µs) [L+N-PE] (Itotal ) 2 kA
Voltage protection level [L-N] / [L/N-PE] (UP ) ≤ 180 / ≤ 630 V
Max. mains-side overcurrent protection 25 A gG or B 25 A
Approvals KEMA, VDE, UL, CSA
Type of remote signalling contact changeover contact

Artikel 953206 wurde zum Merkzettel hinzugefügt.

Zum Merkzettel

Artikel 953206 wurde zum Warenkorb hinzugefügt.

Zum Warenkorb

Art.-Nr. 953207 DR M 2P 60 FM

GTIN 4013364109728, Zolltarifnr.: 85363030, Bruttogewicht: 95.40 g, VPE: 1.00 pc(s)

Vorgänger

Abbildungen

Weitere Information

Two-pole DEHNrail M 2P 60 FM surge arrester
Modular and pluggable two-pole
surge arrester for protecting
terminal devices of industrial electronics equipment
Width: 1 module, Fault indication
With remote signalling contact
Type 3 SPD according to EN 61643-11
Max. continuous operating voltage: 60 V a.c./d.c.
Total discharge current: 2 kA
Voltage protection level (L/N): < 0.35 kV
Backup fuse: 25 A gG or B 25 A
Energy-coordinated according to IEC 62305-4
with arresters of the Red/Line series

Brand: DEHN
Type: DR M 2P 60 FM
Part No.: 953207
or equivalent.

Zertifikate

 

Technische Daten

SPD according to EN 61643-11 / IEC 61643-11 type 3 / class III
Max. continuous operating voltage (a.c.) (UC ) 60 V (50 / 60 Hz)
Max. continuous operating voltage (d.c.) (UC ) 60 V
Nominal discharge current (8/20 µs) (In ) 1 kA
Total discharge current (8/20 µs) [L+N-PE] (Itotal ) 2 kA
Voltage protection level [L-N] / [L/N-PE] (UP ) ≤ 350 / ≤ 730 V
Max. mains-side overcurrent protection 25 A gG or B 25 A
Approvals KEMA, VDE, UL, CSA
Type of remote signalling contact changeover contact

Artikel 953207 wurde zum Merkzettel hinzugefügt.

Zum Merkzettel

Artikel 953207 wurde zum Warenkorb hinzugefügt.

Zum Warenkorb

Art.-Nr. 953208 DR M 2P 75 FM

GTIN 4013364109735, Zolltarifnr.: 85363030, Bruttogewicht: 93.70 g, VPE: 1.00 pc(s)

Vorgänger

Abbildungen

Weitere Information

Two-pole DEHNrail M 2P 75 FM surge arrester
Modular and pluggable two-pole
surge arrester for protecting
terminal devices of industrial electronics equipment
Width: 1 module, Fault indication
With remote signalling contact
Type 3 SPD according to EN 61643-11
Max. continuous operating voltage: 75 V a.c./d.c.
Total discharge current: 4 kA
Voltage protection level (L/N): < 0.4 kV
Backup fuse: 25 A gG or B 25 A
Energy-coordinated according to IEC 62305-4
with arresters of the Red/Line series

Brand: DEHN
Type: DR M 2P 75 FM
Part No.: 953208
or equivalent.

Zertifikate

 

Technische Daten

SPD according to EN 61643-11 / IEC 61643-11 type 3 / class III
Max. continuous operating voltage (a.c.) (UC ) 75 V (50 / 60 Hz)
Max. continuous operating voltage (d.c.) (UC ) 75 V
Nominal discharge current (8/20 µs) (In ) 2 kA
Total discharge current (8/20 µs) [L+N-PE] (Itotal ) 4 kA
Voltage protection level [L-N] / [L/N-PE] (UP ) ≤ 400 / ≤ 730 V
Max. mains-side overcurrent protection 25 A gG or B 25 A
Approvals KEMA, VDE, UL, CSA
Type of remote signalling contact changeover contact

Artikel 953208 wurde zum Merkzettel hinzugefügt.

Zum Merkzettel

Artikel 953208 wurde zum Warenkorb hinzugefügt.

Zum Warenkorb

Art.-Nr. 953209 DR M 2P 150 FM

GTIN 4013364109742, Zolltarifnr.: 85363030, Bruttogewicht: 93.00 g, VPE: 1.00 pc(s)

Vorgänger

Abbildungen

Weitere Information

DEHNrail M 2P 150 FM surge arrester
Modular and pluggable two-pole
surge arrester for protecting
terminal devices of industrial electronics equipment
Width: 1 module, Fault indication
With remote signalling contact
Type 3 SPD according to EN 61643-11
Max. continuous operating voltage: 150 V a.c./d.c.
Total discharge current: 4 kA
Voltage protection level (L/N): < 0.64 kV
Backup fuse: 25 A gG or B 25 A
Energy-coordinated according to IEC 62305-4
with arresters of the Red/Line series
Fault indication

Brand: DEHN
Type: DR M 2P 150 FM
Part No.: 953209
or equivalent.

Zertifikate

 

Technische Daten

SPD according to EN 61643-11 / IEC 61643-11 type 3 / class III
Max. continuous operating voltage (a.c.) (UC ) 150 V (50 / 60 Hz)
Max. continuous operating voltage (d.c.) (UC ) 150 V
Nominal discharge current (8/20 µs) (In ) 2 kA
Total discharge current (8/20 µs) [L+N-PE] (Itotal ) 4 kA
Voltage protection level [L-N] / [L/N-PE] (UP ) ≤ 640 / ≤ 800 V
Max. mains-side overcurrent protection 25 A gG or B 25 A
Approvals KEMA, VDE, UL, CSA
Type of remote signalling contact changeover contact

Artikel 953209 wurde zum Merkzettel hinzugefügt.

Zum Merkzettel

Artikel 953209 wurde zum Warenkorb hinzugefügt.

Zum Warenkorb

Art.-Nr. 953205 DR M 2P 255 FM

GTIN 4013364108318, Zolltarifnr.: 85363030, Bruttogewicht: 98.88 g, VPE: 1.00 pc(s)

Vorgänger

Abbildungen

Weitere Information

Two-pole DEHNrail M 2P 255 FM surge arrester
Modular and pluggable two-pole
surge arrester for protecting
terminal devices of industrial electronics equipment
Width: 1 module, Fault indication
With remote signalling contact
Type 3 SPD according to EN 61643-11
Max. continuous operating voltage: 255 V a.c./d.c.
Total discharge current: 5 kA
Voltage protection level (L/N): < 1.25 kV
Backup fuse: 25 A gG or B 25 A
Energy-coordinated according to IEC 62305-4
with arresters of the Red/Line series

Brand: DEHN
Type: DR M 2P 255 FM
Part No.: 953205
or equivalent.

Zertifikate

 

Technische Daten

SPD according to EN 61643-11 / IEC 61643-11 type 3 / class III
Max. continuous operating voltage (a.c.) (UC ) 255 V (50 / 60 Hz)
Max. continuous operating voltage (d.c.) (UC ) 255 V
Nominal discharge current (8/20 µs) (In ) 3 kA
Total discharge current (8/20 µs) [L+N-PE] (Itotal ) 5 kA
Voltage protection level [L-N] / [L/N-PE] (UP ) ≤ 1250 / ≤ 1500 V
Max. mains-side overcurrent protection 25 A gG or B 25 A
Approvals KEMA, VDE, UL, CSA
Type of remote signalling contact changeover contact

Artikel 953205 wurde zum Merkzettel hinzugefügt.

Zum Merkzettel

Artikel 953205 wurde zum Warenkorb hinzugefügt.

Zum Warenkorb

DEHNrail M 2P SN1802

Two-pole surge arrester consisting of a base part and a plug-in protection module. Usable for systems with a load current up to 32 A.

1 Produkt

Art.-Nr. 953228 DR M 2P 255 SN1802

GTIN 4013364158986, Zolltarifnr.: 85363030, Bruttogewicht: 89.70 g, VPE: 1.00 pc(s)


Abbildungen

Weitere Information

DEHNrail M 2P 255 SN1802 surge arrester
2-pole modular pluggable surge arrester
for protecting industrial electronic terminal devices
Width: 1 module, Fault indication
Arrester Type 3 acc- to EN 61643-11
Max. contin. operating voltage: 255 V ac/dc
Total discharge current: 5 kA
Protection level L/N: < 1.25 kV
Backup fuse: 32 A gG or B 32 A
Energy-coordinated acc. to IEC 62305-4
with arrester of the Red/Line family

Brand: DEHN
Type: DR M 2P 255 SN1802
Part No.: 953228
or equivalent.

Zertifikate

 

Technische Daten

SPD according to EN 61643-11 / IEC 61643-11 type 3 / class III
Max. continuous operating voltage (a.c.) (UC ) 255 V (50 / 60 Hz)
Max. continuous operating voltage (d.c.) (UC ) 255 V
Nominal discharge current (8/20 µs) (In ) 3 kA
Total discharge current (8/20 µs) [L+N-PE] (Itotal ) 5 kA
Voltage protection level [L-N] / [L/N-PE] (UP ) ≤ 1250 / ≤ 1500 V
Max. mains-side overcurrent protection 32 A gG or B 32 A

Artikel 953228 wurde zum Merkzettel hinzugefügt.

Zum Merkzettel

Artikel 953228 wurde zum Warenkorb hinzugefügt.

Zum Warenkorb

DEHNrail M 2P SN1803FM

Two-pole surge arrester consisting of a base part and a plug-in protection module; with floating remote signalling contact. Usable for systems with a load current up to 32 A.

1 Produkt

Art.-Nr. 953229 DR M 2P 255 SN1803FM

GTIN 4013364158993, Zolltarifnr.: 85363030, Bruttogewicht: 93.40 g, VPE: 1.00 pc(s)


Abbildungen

Weitere Information

DEHNrail M 2P 255 SN1803FM surge arrester
2-pole modular pluggable surge arrester
for protecting industrial electronic terminal devices
Width: 1 module, Fault indication
With remote signalling contact
Arrester Type 3 acc. to EN 61643-11
Max. cont. operating voltage: 255 V ac/dc
Total discharge curremt: 5 kA
Protection level L/N: < 1.25 kV
Backup fuse: 32 A gG or B 32 A
Energy-coordinated acc. to IEC 62305-4
with arresters of the Red/Line family

Brand: DEHN
Type: DR M 2P 255 SN1803FM
Part No.: 953229
or equivalent.

Zertifikate

 

Technische Daten

SPD according to EN 61643-11 / IEC 61643-11 type 3 / class III
Max. continuous operating voltage (a.c.) (UC ) 255 V (50 / 60 Hz)
Max. continuous operating voltage (d.c.) (UC ) 255 V
Nominal discharge current (8/20 µs) (In ) 3 kA
Total discharge current (8/20 µs) [L+N-PE] (Itotal ) 5 kA
Voltage protection level [L-N] / [L/N-PE] (UP ) ≤ 1250 / ≤ 1500 V
Max. mains-side overcurrent protection 32 A gG or B 32 A
Type of remote signalling contact changeover contact

Artikel 953229 wurde zum Merkzettel hinzugefügt.

Zum Merkzettel

Artikel 953229 wurde zum Warenkorb hinzugefügt.

Zum Warenkorb

nach oben

Cookie-Einstellungen

Wir verwenden Cookies, um Ihnen ein optimales Webseiten-Erlebnis zu bieten. Dazu zählen Cookies, die für den Betrieb der Seite und für die Steuerung unserer kommerziellen Unternehmensziele notwendig sind, sowie solche, die lediglich zu anonymen Statistikzwecken, für Komforteinstellungen oder zur Anzeige personalisierter Inhalte genutzt werden. Sie können selbst entscheiden, welche Kategorien Sie zulassen möchten. Bitte beachten Sie, dass auf Basis Ihrer Einstellungen womöglich nicht mehr alle Funktionalitäten der Seite zur Verfügung stehen. Weitere Informationen finden Sie in unseren Datenschutzerklärung.
Wenn Sie in die Nutzung von Cookies eingewilligt haben, können Sie dies jederzeit nach Klick auf den Link "Cookie-Einstellungen ändern" im Footer der Seite widerrufen.

  • Details anzeigen Details ausblenden
    Notwendig

    Diese Cookies sind für den Betrieb der Seite unbedingt notwendig und ermöglichen beispielsweise sicherheitsrelevante Funktionalitäten. Außerdem können wir mit dieser Art von Cookies ebenfalls erkennen, ob Sie in Ihrem Profil eingeloggt bleiben möchten, um Ihnen unsere Dienste bei einem erneuten Besuch unserer Seite schneller zur Verfügung zu stellen.

    Statistik & Marketing

    Um unser Angebot und unsere Webseite weiter zu verbessern, erfassen wir anonymisierte Daten für Statistiken und Analysen. Mithilfe dieser Cookies können wir beispielsweise die Besucherzahlen und den Effekt bestimmter Seiten unseres Web-Auftritts ermitteln und unsere Inhalte optimieren.