DEHNbloc modular

  • Coordinated spark-gap-based lightning current arrester consisting of a base part and a plug-in protection module
  • Maximum system availability due to RADAX Flow follow current limitation
  • No tripping of 32 A gG fuses up to short-circuit currents of 50 kArms
  • Discharge capacity up to 50 kA (10/350 µs)
  • Directly coordinated with DEHNguard surge protective devices without additional cable length
  • Low voltage protection level
  • Operating state / fault indication by green / red indicator flag in the inspection window
  • Easy replacement of protection modules without tools due to module locking system with module release button

Details

lorem ipsum

DEHNbloc M 1 ...

Coordinated and modular single-pole lightning current arrester with a high discharge capacity.

3 Produkte

Art.-Nr. 961110 DB M 1 150

GTIN 4013364118560, Zolltarifnr.: 85363090, Bruttogewicht: 333.40 g, VPE: 1.00 pc(s)

Vorgänger

Abbildungen

Weitere Information

Coordinated DEHNbloc M 1 150 lightning current arrester
Pluggable, coordinated and modular single-pole
lightning current arrester, width: 2 mod.
with high follow current limitation
Type 1 SPD according to EN 61643-11
RADAX Flow spark gap technology
for follow current limitation
Fault indication
Max. continuous operating voltage: 150 V a.c.
Voltage protection level: <= 1.5 kV
Lightning impulse current (10/350): 35 kA
Follow current extinguishing capability: up to 50 kArms
Energy-coordinated according to IEC 62305-4
with arresters of the Red/Line series

Brand: DEHN
Type: DB M 1 150
Part No.: 961110
or equivalent.

Zertifikate

 

Technische Daten

SPD according to EN 61643-11 / IEC 61643-11 type 1 / class I
Max. continuous operating voltage (a.c.) (UC ) 150 V (50 / 60 Hz)
Lightning impulse current (10/350 µs) (Iimp ) 35 kA
Voltage protection level (UP ) ≤ 1.5 kV
Max. backup fuse (L) up to IK = 35 kArms (ta ≤ 0.2 s) 500 A gG
Max. backup fuse (L) up to IK = 35 kArms (ta ≤ 5 s) 315 A gG
Approvals UL, CSA

Artikel 961110 wurde zum Merkzettel hinzugefügt.

Zum Merkzettel

Artikel 961110 wurde zum Warenkorb hinzugefügt.

Zum Warenkorb

Art.-Nr. 961120 DB M 1 255

GTIN 4013364118614, Zolltarifnr.: 85363090, Bruttogewicht: 355.80 g, VPE: 1.00 pc(s)

Vorgänger

Abbildungen

Weitere Information

Coordinated DEHNbloc M 1 255 lightning current arrester
Pluggable, coordinated and modular single-pole l
ightning current arrester, width: 2 mod.
with high follow current limitation
Type 1 SPD according to EN 61643-11
RADAX Flow spark gap technology
for follow current limitation
Fault indication
Max. continuous operating voltage: 255 V a.c.
Voltage protection level: <= 2.5 kV
Lightning impulse current (10/350): 50 kA
Follow current extinguishing capability: up to 100 kArms
Energy-coordinated according to IEC 62305-4
with arresters of the Red/Line series

Brand: DEHN
Type: DB M 1 255
Part No.: 961120
or equivalent.

Zertifikate

 

Technische Daten

SPD according to EN 61643-11 / IEC 61643-11 type 1 / class I
Max. continuous operating voltage (a.c.) (UC ) 255 V (50 / 60 Hz)
Lightning impulse current (10/350 µs) (Iimp ) 50 kA
Voltage protection level (UP ) ≤ 2.5 kV
Max. backup fuse (L) up to IK = 50 kArms (ta ≤ 0.2 s) 500 A gG
Max. backup fuse (L) up to IK = 50 kArms (ta ≤ 5 s) 315 A gG
Approvals VDE, KEMA, UL

Artikel 961120 wurde zum Merkzettel hinzugefügt.

Zum Merkzettel

Artikel 961120 wurde zum Warenkorb hinzugefügt.

Zum Warenkorb

Art.-Nr. 961130 DB M 1 320

GTIN 4013364118638, Zolltarifnr.: 85363090, Bruttogewicht: 341.00 g, VPE: 1.00 pc(s)

Vorgänger

Abbildungen

Weitere Information

Coordinated DEHNbloc M 1 320 lightning current arrester
Pluggable, coordinated and modular single-pole
lightning current arrester, width: 2 mod.
with high follow current limitation
Type 1 SPD according to EN 61643-11
RADAX Flow spark gap technology
for follow current limitation
Fault indication
Max. continuous operating voltage: 320 V a.c.
Voltage protection level: <= 2.5 kV
Lightning impulse current (10/350): 25 kA
Follow current extinguishing capability: up to 50 kArms
Energy-coordinated according to IEC 62305-4
with arresters of the Red/Line series

Brand: DEHN
Type: DB M 1 320
Part No.: 961130
or equivalent.

Zertifikate

 

Technische Daten

SPD according to EN 61643-11 / IEC 61643-11 type 1 / class I
Max. continuous operating voltage (a.c.) (UC ) 320 V (50 / 60 Hz)
Lightning impulse current (10/350 µs) (Iimp ) 25 kA
Voltage protection level (UP ) ≤ 2.5 kV
Max. backup fuse (L) up to IK = 50 kArms (ta ≤ 0.2 s) 315 A gG
Max. backup fuse (L) up to IK = 50 kArms (ta ≤ 5 s) 315 A gG
Approvals UL

Artikel 961130 wurde zum Merkzettel hinzugefügt.

Zum Merkzettel

Artikel 961130 wurde zum Warenkorb hinzugefügt.

Zum Warenkorb

DEHNbloc M 1 ... FM

Coordinated and modular single-pole lightning current arrester with a high discharge capacity; with remote signalling contact for monitoring system (floating changeover contact).

3 Produkte

Art.-Nr. 961115 DB M 1 150 FM

GTIN 4013364118577, Zolltarifnr.: 85363090, Bruttogewicht: 337.30 g, VPE: 1.00 pc(s)

Vorgänger

Abbildungen

Weitere Information

Coordinated DEHNbloc M 1 150 FM lightning current arrester
Pluggable, coordinated and modular single-pole
lightning current arrester, width: 2 mod.
with high follow current limitation and remote signalling contact
Type 1 SPD according to EN 61643-11
RADAX Flow spark gap technology
for follow current limitation
Fault indication
Max. continuous operating voltage: 150 V a.c.
Voltage protection level: <= 1.5 kV
Lightning impulse current (10/350): 35 kA
Follow current extinguishing capability: up to 50 kArms
Energy-coordinated according to IEC 62305-4
with arresters of the Red/Line series

Brand: DEHN
Type: DB M 1 150 FM
Part No.: 961115
or equivalent.

Zertifikate

 

Technische Daten

SPD according to EN 61643-11 / IEC 61643-11 type 1 / class I
Max. continuous operating voltage (a.c.) (UC ) 150 V (50 / 60 Hz)
Lightning impulse current (10/350 µs) (Iimp ) 35 kA
Voltage protection level (UP ) ≤ 1.5 kV
Max. backup fuse (L) up to IK = 35 kArms (ta ≤ 0.2 s) 500 A gG
Max. backup fuse (L) up to IK = 35 kArms (ta ≤ 5 s) 315 A gG
Approvals UL, CSA

Artikel 961115 wurde zum Merkzettel hinzugefügt.

Zum Merkzettel

Artikel 961115 wurde zum Warenkorb hinzugefügt.

Zum Warenkorb

Art.-Nr. 961125 DB M 1 255 FM

GTIN 4013364118621, Zolltarifnr.: 85363090, Bruttogewicht: 359.30 g, VPE: 1.00 pc(s)


Abbildungen

Weitere Information

Coordinated DEHNbloc M 1 255 FM lightning current arrester
Pluggable, coordinated and modular
single-pole lightning current arrester
with high follow current limitation and remote signalling contact
Type 1 SPD according to EN 61643-11
RADAX Flow spark gap technology
for follow current limitation
Fault indication
Max. continuous operating voltage: 255 V a.c.
Voltage protection level: <= 2.5 kV
Lightning impulse current (10/350): 50 kA
Follow current extinguishing capability: up to 100 kArms
Energy-coordinated according to IEC 62305-4
with arresters of the Red/Line series

Brand: DEHN
Type: DB M 1 255 FM
Part No.: 961125
or equivalent.

Zertifikate

 

Technische Daten

SPD according to EN 61643-11 / IEC 61643-11 type 1 / class I
Max. continuous operating voltage (a.c.) (UC ) 255 V (50 / 60 Hz)
Lightning impulse current (10/350 µs) (Iimp ) 50 kA
Voltage protection level (UP ) ≤ 2.5 kV
Max. backup fuse (L) up to IK = 50 kArms (ta ≤ 0.2 s) 500 A gG
Max. backup fuse (L) up to IK = 50 kArms (ta ≤ 5 s) 315 A gG
Approvals VDE, KEMA, UL

Artikel 961125 wurde zum Merkzettel hinzugefügt.

Zum Merkzettel

Artikel 961125 wurde zum Warenkorb hinzugefügt.

Zum Warenkorb

Art.-Nr. 961135 DB M 1 320 FM

GTIN 4013364118645, Zolltarifnr.: 85363090, Bruttogewicht: 346.00 g, VPE: 1.00 pc(s)

Vorgänger

Abbildungen

Weitere Information

Coordinated DEHNbloc M 1 320 FM lightning current arrester
Pluggable, coordinated and modular
single-pole lightning current arrester
with high follow current limitation and remote signalling contact
Type 1 SPD according to EN 61643-11
RADAX Flow spark gap technology
for follow current limitation
Fault indication
Max. continuous operating voltage: 320 V a.c.
Voltage protection level: <= 2.5 kV
Lightning impulse current (10/350): 25 kA
Follow current extinguishing capability: up to 100 kArms
Energy-coordinated according to IEC 62305-4
with arresters of the Red/Line series

Brand: DEHN
Type: DB M 1 320 FM
Part No.: 961135
or equivalent.

Zertifikate

 

Technische Daten

SPD according to EN 61643-11 / IEC 61643-11 type 1 / class I
Max. continuous operating voltage (a.c.) (UC ) 320 V (50 / 60 Hz)
Lightning impulse current (10/350 µs) (Iimp ) 25 kA
Voltage protection level (UP ) ≤ 2.5 kV
Max. backup fuse (L) up to IK = 50 kArms (ta ≤ 0.2 s) 315 A gG
Max. backup fuse (L) up to IK = 50 kArms (ta ≤ 5 s) 315 A gG
Approvals UL

Artikel 961135 wurde zum Merkzettel hinzugefügt.

Zum Merkzettel

Artikel 961135 wurde zum Warenkorb hinzugefügt.

Zum Warenkorb

nach oben

Cookie-Einstellungen

Wir verwenden Cookies, um Ihnen ein optimales Webseiten-Erlebnis zu bieten. Dazu zählen Cookies, die für den Betrieb der Seite und für die Steuerung unserer kommerziellen Unternehmensziele notwendig sind, sowie solche, die lediglich zu anonymen Statistikzwecken, für Komforteinstellungen oder zur Anzeige personalisierter Inhalte genutzt werden. Sie können selbst entscheiden, welche Kategorien Sie zulassen möchten. Bitte beachten Sie, dass auf Basis Ihrer Einstellungen womöglich nicht mehr alle Funktionalitäten der Seite zur Verfügung stehen. Weitere Informationen finden Sie in unseren Datenschutzerklärung.
Wenn Sie in die Nutzung von Cookies eingewilligt haben, können Sie dies jederzeit nach Klick auf den Link "Cookie-Einstellungen ändern" im Footer der Seite widerrufen.

  • Details anzeigen Details ausblenden
    Notwendig

    Diese Cookies sind für den Betrieb der Seite unbedingt notwendig und ermöglichen beispielsweise sicherheitsrelevante Funktionalitäten. Außerdem können wir mit dieser Art von Cookies ebenfalls erkennen, ob Sie in Ihrem Profil eingeloggt bleiben möchten, um Ihnen unsere Dienste bei einem erneuten Besuch unserer Seite schneller zur Verfügung zu stellen.

    Statistik & Marketing

    Um unser Angebot und unsere Webseite weiter zu verbessern, erfassen wir anonymisierte Daten für Statistiken und Analysen. Mithilfe dieser Cookies können wir beispielsweise die Besucherzahlen und den Effekt bestimmter Seiten unseres Web-Auftritts ermitteln und unsere Inhalte optimieren.