DEHNventil modular

  • Prewired spark-gap-based type 1 and type 2 combined lightning current and surge arrester consisting of a base part and plug-in protection modules
  • Maximum system availability due to RADAX Flow follow current limitation
  • No tripping of 20 A gG fuses up to short-circuit currents of 50 kArms
  • Discharge capacity up to 100 kA (10/350 µs)
  • Capable of protecting terminal equipment
  • Operating state / fault indication by green / red indicator flag in the inspection window
  • Easy replacement of protection modules without tools due to module locking system with module release button
  • Vibration and shock-tested according to EN 60068-2

Details

lorem ipsum


DEHNventil M TNC (FM)

Modular combined lightning current and surge arrester for TN-C systems with a nominal voltage of 230 / 400 V (3+0 configuration); FM version with floating remote signalling contact.

2 Produkte

Art.-Nr. 951300 DV M TNC 255

GTIN 4013364108134, Zolltarifnr.: 85363090, Bruttogewicht: 1004.00 g, VPE: 1.00 pc(s)

Vorgänger

Abbildungen

Weitere Information

Modular DEHNventil M TNC 255 combined arrester
Modular and pluggable three-pole combined arrester for
230/400 V TN-C systems, width: 6 modules
Type 1 + type 2 according to EN 61643-11
RADAX Flow spark gap technology
for follow current limitation
Max. continuous operating voltage: 264 a.c.
Voltage protection level: <= 1.5 kV
Lightning impulse current (10/350): 75 kA
Follow current extinguishing capability: up to 100 kArms
Energy-coordinated according to IEC 62305-4
with arresters of the Red/Line series and terminal equipment

Brand: DEHN
Type: DV M TNC 255
Part No.: 951300
or equivalent.

Zertifikate

 

Technische Daten

Use for 16.7 Hz traction power supply systems
– Nominal voltage (a.c.) (UN ) 230 / 400 V
– Nominal frequency (a.c.) (fN ) 16.7 Hz
– Max. backup fuse 125 A gG @ 16,7 Hz
SPD according to EN 61643-11 / IEC 61643-11 type 1 + type 2 / class I + class II
Max. continuous operating voltage (a.c.) (UC ) 264 V (50 / 60 Hz)
Lightning impulse current (10/350 µs) [L1+L2+L3-PEN] (Itotal ) 75 kA
Lightning impulse current (10/350 µs) [L-PEN] (Iimp ) 25 kA
Voltage protection level (UP ) 1.5 kV
Max. backup fuse (L) up to IK = 50 kArms 315 A gG
Approvals KEMA, VDE, UL
Extended technical data: For use in switchgear installations with prospective short-circuit currents of more than 50 kArms (tested by the German VDE)
– Max. prospective short-circuit current 100 kArms (220 kApeak)

Artikel 951300 wurde zum Merkzettel hinzugefügt.

Zum Merkzettel

Artikel 951300 wurde zum Warenkorb hinzugefügt.

Zum Warenkorb

Art.-Nr. 951305 DV M TNC 255 FM

GTIN 4013364108141, Zolltarifnr.: 85363090, Bruttogewicht: 1020.00 g, VPE: 1.00 pc(s)

Vorgänger

Abbildungen

Weitere Information

Modular DEHNventil M TNC 255 FM combined arrester
Pluggable and modular three-pole combined arrester
for use in 230/400 V TN-C systems, width: 6 mod.
with remote signalling contact
Type 1 + type 2 SPD according to EN 61643-11
RADAX Flow spark gap technology
for follow current limitation
Max. continuous operating voltage: 264 V a.c.
Voltage protection level: <= 1.5 kV
Lightning impulse current (10/350 µs): 75 kA
Follow current extinguishing capability: up to 100 kArms
Energy-coordinated according to IEC 62305-4 with
arresters of the Red/Line series and terminal equipment

Brand: DEHN
Type: DV M TNC 255 FM
Part No.: 951305
or equivalent.

Zertifikate

 

Technische Daten

Use for 16.7 Hz traction power supply systems
– Nominal voltage (a.c.) (UN ) 230 / 400 V
– Nominal frequency (a.c.) (fN ) 16.7 Hz
– Max. backup fuse 125 A gG @ 16,7 Hz
SPD according to EN 61643-11 / IEC 61643-11 type 1 + type 2 / class I + class II
Max. continuous operating voltage (a.c.) (UC ) 264 V (50 / 60 Hz)
Lightning impulse current (10/350 µs) [L1+L2+L3-PEN] (Itotal ) 75 kA
Lightning impulse current (10/350 µs) [L-PEN] (Iimp ) 25 kA
Voltage protection level (UP ) ≤ 1.5 kV
Max. backup fuse (L) up to IK = 50 kArms 315 A gG
Approvals KEMA, VDE, UL
Type of remote signalling contact changeover contact
Extended technical data: For use in switchgear installations with prospective short-circuit currents of more than 50 kArms (tested by the German VDE)
– Max. prospective short-circuit current 100 kArms (220 kApeak)

Artikel 951305 wurde zum Merkzettel hinzugefügt.

Zum Merkzettel

Artikel 951305 wurde zum Warenkorb hinzugefügt.

Zum Warenkorb

DEHNventil M TNS (FM)

Modular combined lightning current and surge arrester for TN-S systems with a nominal voltage of 230 / 400 V (4+0 configuration); FM version with floating remote signalling contact.

2 Produkte

Art.-Nr. 951400 DV M TNS 255

GTIN 4013364108158, Zolltarifnr.: 85363090, Bruttogewicht: 1.40 kg, VPE: 1.00 pc(s)

Vorgänger

Abbildungen

Weitere Information

Modular DEHNventil M TNS 255 combined arrester
Pluggable and modular four-pole combined arrester
for use in 230/400 V TN(C)-S systems, width: 8 mod.
Type 1 + type 2 SPD according to EN 61643-11
RADAX Flow spark gap technology
for follow current limitation
Max. continuous operating voltage: 264 V a.c.
Voltage protection level: <= 1.5 kV
Lightning impulse current (10/350 µs): 100 kA
Follow current extinguishing capability: up to 100 kArms
Energy-coordinated according to IEC 62305-4 with
arresters of the Red/Line series and terminal equipment

Brand: DEHN
Type: DV M TNS 255
Part No.: 951400
or equivalent.

Zertifikate

 

Technische Daten

Use for 16.7 Hz traction power supply systems
– Nominal voltage (a.c.) (UN ) 230 / 400 V
– Nominal frequency (a.c.) (fN ) 16.7 Hz
– Max. backup fuse 125 A gG @ 16,7 Hz
SPD according to EN 61643-11 / IEC 61643-11 type 1 + type 2 / class I + class II
Max. continuous operating voltage (a.c.) (UC ) 264 V (50 / 60 Hz)
Lightning impulse current (10/350 µs) [L1+L2+L3+N-PE] (Itotal ) 100 kA
Lightning impulse current (10/350 µs) [L, N-PE] (Iimp ) 25 kA
Voltage protection level [L-PE]/[N-PE] (UP ) ≤ 1.5 / ≤ 1.5 kV
Max. backup fuse (L) up to IK = 50 kArms 315 A gG
Approvals KEMA, VDE, UL
Extended technical data: For use in switchgear installations with prospective short-circuit currents of more than 50 kArms (tested by the German VDE)
– Max. prospective short-circuit current 100 kArms (220 kApeak)

Artikel 951400 wurde zum Merkzettel hinzugefügt.

Zum Merkzettel

Artikel 951400 wurde zum Warenkorb hinzugefügt.

Zum Warenkorb

Art.-Nr. 951405 DV M TNS 255 FM

GTIN 4013364108165, Zolltarifnr.: 85363090, Bruttogewicht: 1.40 kg, VPE: 1.00 pc(s)

Vorgänger

Abbildungen

Weitere Information

Modular DEHNventil M TNS 255 FM combined arrester
Pluggable and modular four-pole combined arrester
for use in 230/400 V TN(C)-S systems, width: 8 mod.
with remote signalling contact
Type 1 + type 2 SPD according to EN 61643-11
RADAX Flow spark gap technology
for follow current limitation
Max. continuous operating voltage: 264 V a.c.
Voltage protection level: <= 1.5 kV
Lightning impulse current (10/350 µs): 100 kA
Follow current extinguishing capability: up to 100 kArms
Energy-coordinated according to IEC 62305-4 with
arresters of the Red/Line series and terminal equipment

Brand: DEHN
Type: DV M TNS 255 FM
Part No.: 951405
or equivalent.

Zertifikate

 

Technische Daten

Use for 16.7 Hz traction power supply systems
– Nominal voltage (a.c.) (UN ) 230 / 400 V
– Nominal frequency (a.c.) (fN ) 16.7 Hz
– Max. backup fuse 125 A gG @ 16,7 Hz
SPD according to EN 61643-11 / IEC 61643-11 type 1 + type 2 / class I + class II
Max. continuous operating voltage (a.c.) (UC ) 264 V (50 / 60 Hz)
Lightning impulse current (10/350 µs) [L1+L2+L3+N-PE] (Itotal ) 100 kA
Lightning impulse current (10/350 µs) [L, N-PE] (Iimp ) 25 kA
Voltage protection level [L-PE]/[N-PE] (UP ) ≤ 1.5 / ≤ 1.5 kV
Max. backup fuse (L) up to IK = 50 kArms 315 A gG
Approvals KEMA, VDE, UL
Type of remote signalling contact changeover contact
Extended technical data: For use in switchgear installations with prospective short-circuit currents of more than 50 kArms (tested by the German VDE)
– Max. prospective short-circuit current 100 kArms (220 kApeak)

Artikel 951405 wurde zum Merkzettel hinzugefügt.

Zum Merkzettel

Artikel 951405 wurde zum Warenkorb hinzugefügt.

Zum Warenkorb

DEHNventil M TT (FM)

Modular combined lightning current and surge arrester for TT and TN-S systems with a nominal voltage of 230 / 400 V (3+1 configuration); FM version with floating remote signalling contact.

2 Produkte

Art.-Nr. 951310 DV M TT 255

GTIN 4013364108172, Zolltarifnr.: 85363090, Bruttogewicht: 1.31 kg, VPE: 1.00 pc(s)

Vorgänger

Abbildungen

Weitere Information

Modular DEHNventil M TT 255 combined arrester
Pluggable and modular four-pole combined arrester
for use in 230/400 V TT and TN(C)-S systems, width: 8 mod.
Type 1 + type 2 SPD according to EN 61643-11
RADAX Flow spark gap technology
for follow current limitation
Max. continuous operating voltage: 264 V a.c.
Voltage protection level: <= 1.5 kV
Lightning impulse current (10/350 µs): 100 kA
Follow current extinguishing capability: up to 100 kArms
Energy-coordinated according to IEC 62305-4 with
arresters of the Red/Line series and terminal equipment

Brand: DEHN
Type: DV M TT 255
Part No.: 951310
or equivalent.

Zertifikate

 

Technische Daten

SPD according to EN 61643-11 / IEC 61643-11 type 1 + type 2 / class I + class II
Max. continuous operating voltage (a.c.) [L-N] (UC ) 264 V (50 / 60 Hz)
Lightning impulse current (10/350 µs) [L1+L2+L3+N-PE] (Itotal ) 100 kA
Lightning impulse current (10/350 µs) [L-N]/[N-PE] (Iimp ) 25 / 100 kA
Voltage protection level [L-N]/[N-PE] (UP ) ≤ 1.5 / ≤ 1.5 kV
Max. backup fuse (L) up to IK = 50 kArms 315 A gG
Approvals KEMA, VDE, UL
Extended technical data: ---------------------------------
Voltage protection level [L-PE] (UP ) 2.2 kV
For use in switchgear installations with prospective short-circuit currents of more than 50 kArms (tested by the German VDE) ---------------------------------
– Max. prospective short-circuit current 100 kArms (220 kApeak)
Use for 16.7 Hz traction power supply systems
– Nominal voltage (a.c.) (UN ) 230 / 400 V
– Nominal frequency (a.c.) (fN ) 16.7 Hz
– Max. backup fuse 125 A gG @ 16,7 Hz

Artikel 951310 wurde zum Merkzettel hinzugefügt.

Zum Merkzettel

Artikel 951310 wurde zum Warenkorb hinzugefügt.

Zum Warenkorb

Art.-Nr. 951315 DV M TT 255 FM

GTIN 4013364108189, Zolltarifnr.: 85363090, Bruttogewicht: 1.32 kg, VPE: 1.00 pc(s)

Vorgänger

Abbildungen

Weitere Information

Modular DEHNventil M TT 255 FM combined arrester
Pluggable and modular four-pole combined arrester
for use in 230/400 V TT and TN(C)-S systems, width: 8 mod.
with remote signalling contact
Type 1 + type 2 SPD according to EN 61643-11
RADAX Flow spark gap technology
for follow current limitation
Max. continuous operating voltage: 264 V a.c.
Voltage protection level: <= 1.5 kV
Lightning impulse current (10/350 µs): 100 kA
Follow current extinguishing capability: up to 100 kArms
Energy-coordinated according to IEC 62305-4 with
arresters of the Red/Line series and terminal equipment

Brand: DEHN
Type: DV M TT 255 FM
Part No.: 951315
or equivalent.

Zertifikate

 

Technische Daten

SPD according to EN 61643-11 / IEC 61643-11 type 1 + type 2 / class I + class II
Max. continuous operating voltage (a.c.) [L-N] (UC ) 264 V (50 / 60 Hz)
Lightning impulse current (10/350 µs) [L1+L2+L3+N-PE] (Itotal ) 100 kA
Lightning impulse current (10/350 µs) [L-N]/[N-PE] (Iimp ) 25 / 100 kA
Voltage protection level [L-N]/[N-PE] (UP ) ≤ 1.5 / ≤ 1.5 kV
Max. backup fuse (L) up to IK = 50 kArms 315 A gG
Approvals KEMA, VDE, UL
Type of remote signalling contact changeover contact
Extended technical data: ---------------------------------
Voltage protection level [L-PE] (UP ) 2.2 kV
For use in switchgear installations with prospective short-circuit currents of more than 50 kArms (tested by the German VDE) ---------------------------------
– Max. prospective short-circuit current 100 kArms (220 kApeak)
Use for 16.7 Hz traction power supply systems
– Nominal voltage (a.c.) (UN ) 230 / 400 V
– Nominal frequency (a.c.) (fN ) 16.7 Hz
– Max. backup fuse 125 A gG @ 16,7 Hz

Artikel 951315 wurde zum Merkzettel hinzugefügt.

Zum Merkzettel

Artikel 951315 wurde zum Warenkorb hinzugefügt.

Zum Warenkorb

DEHNventil M TN (FM)

Modular combined lightning current and surge arrester for single-phase TN systems with a nominal voltage of 230 V (2+0 configuration); FM version with floating remote signalling contact.

2 Produkte

Art.-Nr. 951200 DV M TN 255

GTIN 4013364108097, Zolltarifnr.: 85363090, Bruttogewicht: 754.00 g, VPE: 1.00 pc(s)

Vorgänger

Abbildungen

Weitere Information

Modular DEHNventil M TN 255 combined arrester
Pluggable and modular two-pole combined arrester
for use in single-phase TN systems, width: 4 mod.
Type 1 + type 2 SPD according to EN 61643-11
RADAX Flow spark gap technology
for follow current limitation
Max. continuous operating voltage: 264 V a.c.
Voltage protection level: <= 1.5 kV
Lightning impulse current (10/350 µs): 50 kA
Follow current extinguishing capability: up to 100 kArms
Energy-coordinated according to IEC 62305-4 with
arresters of the Red/Line series and terminal equipment

Brand: DEHN
Type: DV M TN 255
Part No.: 951200
or equivalent.

Zertifikate

 

Technische Daten

Use for 16.7 Hz traction power supply systems
– Nominal voltage (a.c.) (UN ) 230 V
– Nominal frequency (a.c.) (fN ) 16.7 Hz
– Max. backup fuse 125 A gG @ 16,7 Hz
SPD according to EN 61643-11 / IEC 61643-11 type 1 + type 2 / class I + class II
Max. continuous operating voltage (a.c.) (UC ) 264 V (50 / 60 Hz)
Lightning impulse current (10/350 µs) [L+N-PE] (Itotal ) 50 kA
Lightning impulse current (10/350 µs) [L, N-PE] (Iimp ) 25 kA
Voltage protection level [L-PE]/[N-PE] (UP ) ≤ 1.5 / ≤ 1.5 kV
Max. backup fuse (L) up to IK = 50 kArms 315 A gG
Approvals KEMA, VDE, UL
Extended technical data: For use in switchgear installations with prospective short-circuit currents of more than 50 kArms (tested by the German VDE)
– Max. prospective short-circuit current 100 kArms (220 kApeak)

Artikel 951200 wurde zum Merkzettel hinzugefügt.

Zum Merkzettel

Artikel 951200 wurde zum Warenkorb hinzugefügt.

Zum Warenkorb

Art.-Nr. 951205 DV M TN 255 FM

GTIN 4013364108103, Zolltarifnr.: 85363090, Bruttogewicht: 698.50 g, VPE: 1.00 pc(s)

Vorgänger

Abbildungen

Weitere Information

Modular DEHNventil M TN 255 FM combined arrester
Pluggable and modular two-pole combined arrester
for use in single-phase TN systems, width: 4 mod.
with remote signalling contact
Type 1 SPD according to EN 61643-11
RADAX Flow spark gap technology
for follow current limitation
Max. continuous operating voltage: 264 V a.c.
Voltage protection level: <= 1.5 kV
Lightning impulse current (10/350 µs): 50 kA
Follow current extinguishing capability: up to 100 kArms
Energy-coordinated according to IEC 62305-4 with
arresters of the Red/Line series and terminal equipment

Brand: DEHN
Type: DV M TN 255 FM
Part No.: 951205
or equivalent.

Zertifikate

 

Technische Daten

Use for 16.7 Hz traction power supply systems
– Nominal voltage (a.c.) (UN ) 230 V
– Nominal frequency (a.c.) (fN ) 16.7 Hz
– Max. backup fuse 125 A gG @ 16,7 Hz
SPD according to EN 61643-11 / IEC 61643-11 type 1 + type 2 / class I + class II
Max. continuous operating voltage (a.c.) (UC ) 264 V (50 / 60 Hz)
Lightning impulse current (10/350 µs) [L+N-PE] (Itotal ) 50 kA
Lightning impulse current (10/350 µs) [L, N-PE] (Iimp ) 25 kA
Voltage protection level [L-PE]/[N-PE] (UP ) ≤ 1.5 / ≤ 1.5 kV
Max. backup fuse (L) up to IK = 50 kArms 315 A gG
Approvals KEMA, VDE, UL
Type of remote signalling contact changeover contact
Extended technical data: For use in switchgear installations with prospective short-circuit currents of more than 50 kArms (tested by the German VDE)
– Max. prospective short-circuit current 100 kArms (220 kApeak)

Artikel 951205 wurde zum Merkzettel hinzugefügt.

Zum Merkzettel

Artikel 951205 wurde zum Warenkorb hinzugefügt.

Zum Warenkorb

DEHNventil M TT 2P (FM)

Modular combined lightning current and surge arrester for single-phase TT and TN-S systems with a nominal voltage of 230 V (1+1 configuration); FM version with floating remote signalling contact.

2 Produkte

Art.-Nr. 951110 DV M TT 2P 255

GTIN 4013364108110, Zolltarifnr.: 85363090, Bruttogewicht: 688.59 g, VPE: 1.00 pc(s)

Vorgänger

Abbildungen

Weitere Information

Modular DEHNventil M TT 2P 255 combined arrester
Pluggable and modular two-pole combined arrester
for use in single-phase TT and TN systems, width: 4 mod.
Type 1 + type 2 SPD according to EN 61643-11
RADAX Flow spark gap technology
for follow current limitation
Max. continuous operating voltage: 264 V a.c.
Voltage protection level: <= 1.5 kV
Lightning impulse current (10/350 µs): 50 kA
Follow current extinguishing capability: up to 100 kArms
Energy-coordinated according to IEC 62305-4 with
arresters of the Red/Line series and terminal equipment

Brand: DEHN
Type: DV M TT 2P 255
Part No.: 951110
or equivalent.

Zertifikate

 

Technische Daten

SPD according to EN 61643-11 / IEC 61643-11 type 1 + type 2 / class I + class II
Max. continuous operating voltage (a.c.) [L-N] (UC ) 264 V (50 / 60 Hz)
Lightning impulse current (10/350 µs) [L+N-PE] (Itotal ) 50 kA
Lightning impulse current (10/350 µs) [L-N]/[N-PE] (Iimp ) 25 / 50 kA
Voltage protection level [L-N]/[N-PE] (UP ) ≤ 1.5 / ≤ 1.5 kV
Max. backup fuse (L) up to IK = 50 kArms 315 A gG
Approvals KEMA, VDE, UL
Extended technical data: ---------------------------------
Voltage protection level [L-PE] (UP ) 2.2 kV
For use in switchgear installations with prospective short-circuit currents of more than 50 kArms (tested by the German VDE) ---------------------------------
– Max. prospective short-circuit current 100 kArms (220 kApeak)
Use for 16.7 Hz traction power supply systems
– Nominal voltage (a.c.) (UN ) 230 V
– Nominal frequency (a.c.) (fN ) 16.7 Hz
– Max. backup fuse 125 A gG @ 16,7 Hz

Artikel 951110 wurde zum Merkzettel hinzugefügt.

Zum Merkzettel

Artikel 951110 wurde zum Warenkorb hinzugefügt.

Zum Warenkorb

Art.-Nr. 951115 DV M TT 2P 255 FM

GTIN 4013364108127, Zolltarifnr.: 85363090, Bruttogewicht: 694.38 g, VPE: 1.00 pc(s)

Vorgänger

Abbildungen

Weitere Information

Modular DEHNventil M TT 2P 255 FM combined arrester
Pluggable and modular two-pole combined arrester
for use in single-phase TT and TN systems, width: 4 mod.
with remote signalling contact
Type 1+ type 2 SPD according to EN 61643-11
RADAX Flow spark gap technology
for follow current limitation
Max. continuous operating voltage: 264 V a.c.
Voltage protection level: <= 1.5 kV
Lightning impulse current (10/350 µs): 50 kA
Follow current extinguishing capability: up to 100 kArms
No tripping of 20 A gG fuses up to 50 kArms
Energy-coordinated according to IEC 62305-4 with
arresters of the Red/Line series and terminal equipment

Brand: DEHN
Type: DV M TT 2P 255 FM
Part No.: 951115
or equivalent.

Zertifikate

 

Technische Daten

SPD according to EN 61643-11 / IEC 61643-11 type 1 + type 2 / class I + class II
Max. continuous operating voltage (a.c.) [L-N] (UC ) 264 V (50 / 60 Hz)
Lightning impulse current (10/350 µs) [L+N-PE] (Itotal ) 50 kA
Lightning impulse current (10/350 µs) [L-N]/[N-PE] (Iimp ) 25 / 50 kA
Voltage protection level [L-N]/[N-PE] (UP ) ≤ 1.5 / ≤ 1.5 kV
Max. backup fuse (L) up to IK = 50 kArms 315 A gG
Approvals KEMA, VDE, UL
Type of remote signalling contact changeover contact
Extended technical data: ---------------------------------
Voltage protection level [L-PE] (UP ) 2.2 kV
For use in switchgear installations with prospective short-circuit currents of more than 50 kArms (tested by the German VDE) ---------------------------------
– Max. prospective short-circuit current 100 kArms (220 kApeak)
Use for 16.7 Hz traction power supply systems
– Nominal voltage (a.c.) (UN ) 230 V
– Nominal frequency (a.c.) (fN ) 16.7 Hz
– Max. backup fuse 125 A gG @ 16,7 Hz

Artikel 951115 wurde zum Merkzettel hinzugefügt.

Zum Merkzettel

Artikel 951115 wurde zum Warenkorb hinzugefügt.

Zum Warenkorb

nach oben

Cookie-Einstellungen

Wir verwenden Cookies, um Ihnen ein optimales Webseiten-Erlebnis zu bieten. Dazu zählen Cookies, die für den Betrieb der Seite und für die Steuerung unserer kommerziellen Unternehmensziele notwendig sind, sowie solche, die lediglich zu anonymen Statistikzwecken, für Komforteinstellungen oder zur Anzeige personalisierter Inhalte genutzt werden. Sie können selbst entscheiden, welche Kategorien Sie zulassen möchten. Bitte beachten Sie, dass auf Basis Ihrer Einstellungen womöglich nicht mehr alle Funktionalitäten der Seite zur Verfügung stehen. Weitere Informationen finden Sie in unseren Datenschutzerklärung.
Wenn Sie in die Nutzung von Cookies eingewilligt haben, können Sie dies jederzeit nach Klick auf den Link "Cookie-Einstellungen ändern" im Footer der Seite widerrufen.

  • Details anzeigen Details ausblenden
    Notwendig

    Diese Cookies sind für den Betrieb der Seite unbedingt notwendig und ermöglichen beispielsweise sicherheitsrelevante Funktionalitäten. Außerdem können wir mit dieser Art von Cookies ebenfalls erkennen, ob Sie in Ihrem Profil eingeloggt bleiben möchten, um Ihnen unsere Dienste bei einem erneuten Besuch unserer Seite schneller zur Verfügung zu stellen.

    Statistik & Marketing

    Um unser Angebot und unsere Webseite weiter zu verbessern, erfassen wir anonymisierte Daten für Statistiken und Analysen. Mithilfe dieser Cookies können wir beispielsweise die Besucherzahlen und den Effekt bestimmter Seiten unseres Web-Auftritts ermitteln und unsere Inhalte optimieren.