DEHNguard Modular for North America

  • Prewired complete unit consisting of a base part and plug-in protection modules
  • No need for additional overcurrent protection devices
  • Short circuit current rating (SCCR) 200 kA
  • ANSI/UL 1449 – 4th Ed. Open-Type 1 SPD
  • High discharge capacity due to heavy-duty zinc oxide varistors (Imax 50 kA 8x20 μs)
  • High reliability due to "Thermo Dynamic Control" SPD monitoring device

DEHNguard MU 3PY ... 3W+G

DIN rail mount, pluggable surge arrester consisting of a base part and plug-in protection modules for application in 3 Phase Wye electrical systems

3 Produkte

Art.-Nr. 908300 DG MU 3PY 208 3W+G

GTIN 4013364148680, Zolltarifnr.: 85363030, Bruttogewicht: 323.70 g, VPE: 1.00 pc(s)


Abbildungen

Weitere Information

DEHNguard MU 3PY 208 3W+G surge arrester
3-pole, modular surge arrester for wye 120/208 V systems
ANSI/UL 1449 – 4th Ed. Open-Type 1 SPD
No need for additional overcurrent protection devices
Nominal system voltage: 120/208 V Wye
Voltage Protection Rating [L-G]/[L-L]: 600 Vpk / 1200 Vpk
Nominal discharge current (8/20): 20 kA
Maximal discharge current (8/20): 50 kA
Short circuit current rating (SCCR): 200 kA
Fault indication
Width: 3 mod.

Brand: DEHN
Type: DG MU 3PY 208 3W+G
Part No.: 908300
or equivalent.

Zertifikate

 

Technische Daten

SPD classification acc. to ANSI/UL 1449 4th Ed. Open-Type 1 SPD
SPD classification acc. to CSA - C22.2 No. 269.1-14 Type 4-1 Component Assembly
Max. continuous operating voltage AC [L-G] / [L-L] (MCOV ) 180 V a.c. / 360 V a.c.
Nominal discharge current (8x 20 µs) (In ) 20 kA
Max. discharge current (8/20) (Imax ) 50 kA
Voltage protection rating [L-G] / [L-L] (VPR ) 600 Vpk / 1200 Vpk
Max. mains-side overcurrent protection Not needed
Approvals UL, CSA

Artikel 908300 wurde zum Merkzettel hinzugefügt.

Zum Merkzettel

Artikel 908300 wurde zum Warenkorb hinzugefügt.

Zum Warenkorb

Art.-Nr. 908314 DG MU 3PY 480 3W+G

GTIN 4013364148703, Zolltarifnr.: 85363030, Bruttogewicht: 360.30 g, VPE: 1.00 pc(s)


Abbildungen

Weitere Information

DEHNguard MU 3PY 480 3W+G surge arrester
3-pole, modular surge arrester for wye 277/480 V systems
ANSI/UL 1449 – 4th Ed. Open-Type 1 SPD
No need for additional overcurrent protection devices
Nominal system voltage: 277/480 V Wye
Voltage Protection Rating [L-G]/[L-L]: 1200 Vpk / 2400 Vpk
Nominal discharge current (8/20): 20 kA
Maximal discharge current (8/20): 50 kA
Short circuit current rating (SCCR): 200 kA
Fault indication
Width: 3 mod.

Brand: DEHN
Type: DG MU 3PY 480 3W+G
Part No.: 908314
or equivalent.

Zertifikate

 

Technische Daten

SPD classification acc. to ANSI/UL 1449 4th Ed. Open-Type 1 SPD
SPD classification acc. to CSA - C22.2 No. 269.1-14 Type 4-1 Component Assembly
Max. continuous operating voltage AC [L-G] / [L-L] (MCOV ) 385 V a.c. / 770 V a.c.
Nominal discharge current (8x 20 µs) (In ) 20 kA
Max. discharge current (8/20) (Imax ) 50 kA
Voltage protection rating [L-G] / [L-L] (VPR ) 1200 Vpk / 2500 Vpk
Max. mains-side overcurrent protection Not needed
Approvals UL, CSA

Artikel 908314 wurde zum Merkzettel hinzugefügt.

Zum Merkzettel

Artikel 908314 wurde zum Warenkorb hinzugefügt.

Zum Warenkorb

Art.-Nr. 908301 DG MU 3PY 600 3W+G

GTIN 4013364148727, Zolltarifnr.: 85363030, Bruttogewicht: 383.70 g, VPE: 1.00 pc(s)


Abbildungen

Weitere Information

DEHNguard MU 3PY 600 3W+G surge arrester
3-pole, modular surge arrester for wye 347/600 V systems
ANSI/UL 1449 – 4th Ed. Open-Type 1 SPD
No need for additional overcurrent protection devices
Nominal system voltage: 347/600 V Wye
Voltage Protection Rating [L-G]/[L-L]: 1500 Vpk/3000 Vpk
Nominal discharge current (8/20): 20 kA
Maximal discharge current (8/20): 50 kA
Short circuit current rating (SCCR): 200 kA
Fault indication
Width: 3 mod.

Brand: DEHN
Type: DG MU 3PY 600 3W+G
Part No.: 908301
or equivalent.

Zertifikate

 

Technische Daten

SPD classification acc. to ANSI/UL 1449 4th Ed. Open-Type 1 SPD
SPD classification acc. to CSA - C22.2 No. 269.1-14 Type 4-1 Component Assembly
Max. continuous operating voltage AC [L-G] / [L-L] (MCOV ) 510 V a.c. / 1020 V a.c.
Nominal discharge current (8x 20 µs) (In ) 20 kA
Max. discharge current (8/20) (Imax ) 50 kA
Voltage protection rating [L-G] / [L-L] (VPR ) 1500 Vpk / 3000 Vpk
Max. mains-side overcurrent protection Not needed
Approvals UL, CSA

Artikel 908301 wurde zum Merkzettel hinzugefügt.

Zum Merkzettel

Artikel 908301 wurde zum Warenkorb hinzugefügt.

Zum Warenkorb

DEHNguard MU 3PY ... 3W+G R

DIN rail mount, pluggable surge arrester consisting of a base part and plug-in protection modules for application in 3 Phase Wye electrical systems; has floating Form C (SPDT) remote status contacts

3 Produkte

Art.-Nr. 908305 DG MU 3PY 208 3W+G R

GTIN 4013364148697, Zolltarifnr.: 85363030, Bruttogewicht: 330.90 g, VPE: 1.00 pc(s)


Abbildungen

Weitere Information

DEHNguard MU 3PY 208 3W+G R surge arrester
3-pole, modular surge arrester for wye 120/208 V systems
with floating Form C (SPDT) remote status contact
ANSI/UL 1449 – 4th Ed. Open-Type 1 SPD
No need for additional overcurrent protection devices
Nominal system voltage: 120/208 V Wye
Voltage Protection Rating [L-G]/[L-L]: 600 Vpk / 1200 Vpk
Nominal discharge current (8/20): 20 kA
Maximal discharge current (8/20): 50 kA
Short circuit current rating (SCCR): 200 kA
Fault indication
Width: 3 mod.

Brand: DEHN
Type: DG MU 3PY 208 3W+G R
Part No.: 908305
or equivalent.

Zertifikate

 

Technische Daten

SPD classification acc. to ANSI/UL 1449 4th Ed. Open-Type 1 SPD
SPD classification acc. to CSA - C22.2 No. 269.1-14 Type 4-1 Component Assembly
Max. continuous operating voltage AC [L-G] / [L-L] (MCOV ) 180 V a.c. / 360 V a.c.
Nominal discharge current (8x 20 µs) (In ) 20 kA
Max. discharge current (8/20) (Imax ) 50 kA
Voltage protection rating [L-G] / [L-L] (VPR ) 600 Vpk / 1200 Vpk
Max. mains-side overcurrent protection Not needed
Approvals UL, CSA
Remote status contact Floating (dry), Form C (SPDT)

Artikel 908305 wurde zum Merkzettel hinzugefügt.

Zum Merkzettel

Artikel 908305 wurde zum Warenkorb hinzugefügt.

Zum Warenkorb

Art.-Nr. 908319 DG MU 3PY 480 3W+G R

GTIN 4013364148710, Zolltarifnr.: 85363030, Bruttogewicht: 368.10 g, VPE: 1.00 pc(s)


Abbildungen

Weitere Information

DEHNguard MU 3PY 480 3W+G R surge arrester
3-pole, modular surge arrester for wye 277/480 V systems
with floating Form C (SPDT) remote status contact
ANSI/UL 1449 – 4th Ed. Open-Type 1 SPD
No need for additional overcurrent protection devices
Nominal system voltage: 277/480 V Wye
Voltage Protection Rating [L-G]/[L-L]: 1200 Vpk / 2500 Vpk
Nominal discharge current (8/20): 20 kA
Maximal discharge current (8/20): 50 kA
Short circuit current rating (SCCR): 200 kA
Fault indication
Width: 3 mod.

Brand: DEHN
Type: DG MU 3PY 480 3W+G R
Part No.: 908319
or equivalent.

Zertifikate

 

Technische Daten

SPD classification acc. to ANSI/UL 1449 4th Ed. Open-Type 1 SPD
SPD classification acc. to CSA - C22.2 No. 269.1-14 Type 4-1 Component Assembly
Max. continuous operating voltage AC [L-G] / [L-L] (MCOV ) 385 V a.c. / 770 V a.c.
Nominal discharge current (8x 20 µs) (In ) 20 kA
Max. discharge current (8/20) (Imax ) 50 kA
Voltage protection rating [L-G] / [L-L] (VPR ) 1200 Vpk / 2500 Vpk
Max. mains-side overcurrent protection Not needed
Approvals UL, CSA
Remote status contact Floating (dry), Form C (SPDT)

Artikel 908319 wurde zum Merkzettel hinzugefügt.

Zum Merkzettel

Artikel 908319 wurde zum Warenkorb hinzugefügt.

Zum Warenkorb

Art.-Nr. 908306 DG MU 3PY 600 3W+G R

GTIN 4013364148734, Zolltarifnr.: 85363030, Bruttogewicht: 391.20 g, VPE: 1.00 pc(s)


Abbildungen

Weitere Information

DEHNguard MU 3PY 600 3W+G R surge arrester
3-pole, modular surge arrester for wye 347/600 V systems
With floating Form C (SPDT) remote status contact
ANSI/UL 1449 – 4th Ed. Open-Type 1 SPD
No need for additional overcurrent protection devices
Nominal system voltage: 347/600 V Wye
Voltage Protection Rating [L-G]/[L-L]: 1500 Vpk/3000 Vpk
Nominal discharge current (8/20): 20 kA
Maximal discharge current (8/20): 50 kA
Short circuit current rating (SCCR): 200 kA
Fault indication
Width: 3 mod.

Brand: DEHN
Type: DG MU 3PY 600 3W+G R
Part No.: 908306
or equivalent.

Zertifikate

 

Technische Daten

SPD classification acc. to ANSI/UL 1449 4th Ed. Open-Type 1 SPD
SPD classification acc. to CSA - C22.2 No. 269.1-14 Type 4-1 Component Assembly
Max. continuous operating voltage AC [L-G] / [L-L] (MCOV ) 510 V a.c. / 1020 V a.c.
Nominal discharge current (8x 20 µs) (In ) 20 kA
Max. discharge current (8/20) (Imax ) 50 kA
Voltage protection rating [L-G] / [L-L] (VPR ) 1500 Vpk / 3000 Vpk
Max. mains-side overcurrent protection Not needed
Approvals UL, CSA
Remote status contact Floating (dry), Form C (SPDT)

Artikel 908306 wurde zum Merkzettel hinzugefügt.

Zum Merkzettel

Artikel 908306 wurde zum Warenkorb hinzugefügt.

Zum Warenkorb

DEHNguard MU 3PD ... 3W+G

DIN rail mount, pluggable surge arrester consisting of a base part and plug-in protection modules for application in 3 Phase Delta electrical systems

2 Produkte

Art.-Nr. 908350 DG MU 3PD 480 3W+G

GTIN 4013364148741, Zolltarifnr.: 85363030, Bruttogewicht: 393.70 g, VPE: 1.00 pc(s)


Abbildungen

Weitere Information

DEHNguard MU 3PD 480 3W+G surge arrester
3-pole, modular surge arrester for delta 480 V systems
ANSI/UL 1449 – 4th Ed. Open-Type 1 SPD
No need for additional overcurrent protection devices
Nominal system voltage: 480 V Delta
Voltage Protection Rating [L-G]/[L-L]: 1800 Vpk/3000 Vpk
Nominal discharge current (8/20): 20 kA
Maximal discharge current (8/20): 50 kA
Short circuit current rating (SCCR): 200 kA
Fault indication
Width: 3 mod.

Brand: DEHN
Type: DG MU 3PD 480 3W+G
Part No.: 908350
or equivalent.

Zertifikate

 

Technische Daten

SPD classification acc. to ANSI/UL 1449 4th Ed. Open-Type 1 SPD
SPD classification acc. to CSA - C22.2 No. 269.1-14 Type 4-1 Component Assembly
Max. continuous operating voltage AC [L-G] / [L-L] (MCOV ) 550 V a.c. / 1100 V a.c.
Nominal discharge current (8x 20 µs) (In ) 20 kA
Max. discharge current (8/20) (Imax ) 50 kA
Voltage protection rating [L-G] / [L-L] (VPR ) 1800 Vpk / 3000 Vpk
Max. mains-side overcurrent protection Not needed
Approvals UL, CSA

Artikel 908350 wurde zum Merkzettel hinzugefügt.

Zum Merkzettel

Artikel 908350 wurde zum Warenkorb hinzugefügt.

Zum Warenkorb

Art.-Nr. 908351 DG MU 3PD 240 3W+G

GTIN 4013364148826, Zolltarifnr.: 85363030, Bruttogewicht: 339.90 g, VPE: 1.00 pc(s)


Abbildungen

Weitere Information

DEHNguard DG MU 3PD 240 3W+G surge arrester
3-pole, modular surge arrester for delta 240 V systems
ANSI/UL 1449 – 4th Ed. Open-Type 1 SPD
No need for additional overcurrent protection devices
Nominal system voltage: 240 V Delta
Voltage Protection Rating [L-G]/[L-L]: 800 Vpk / 1500 Vpk
Nominal discharge current (8/20): 20 kA
Maximal discharge current (8/20): 50 kA
Short circuit current rating (SCCR): 200 kA
Fault indication
Width: 3 mod.

Brand: DEHN
Type: DG MU 3PD 240 3W+G
Part No.: 908351
or equivalent.

Zertifikate

 

Technische Daten

SPD classification acc. to ANSI/UL 1449 4th Ed. Open-Type 1 SPD
SPD classification acc. to CSA - C22.2 No. 269.1-14 Type 4-1 Component Assembly
Max. continuous operating voltage AC [L-G] / [L-L] (MCOV ) 275 V a.c. / 550 V a.c.
Nominal discharge current (8x 20 µs) (In ) 20 kA
Max. discharge current (8/20) (Imax ) 50 kA
Voltage protection rating [L-G] / [L-L] (VPR ) 800 Vpk / 1500 Vpk
Max. mains-side overcurrent protection Not needed
Approvals UL, CSA

Artikel 908351 wurde zum Merkzettel hinzugefügt.

Zum Merkzettel

Artikel 908351 wurde zum Warenkorb hinzugefügt.

Zum Warenkorb

DEHNguard MU 3PD ... 3W+G R

DIN rail mount, pluggable surge arrester consisting of a base part and plug-in protection modules for application in 3 Phase Delta electrical systems; has floating Form C (SPDT) remote status contacts

2 Produkte

Art.-Nr. 908355 DG MU 3PD 480 3W+G R

GTIN 4013364148758, Zolltarifnr.: 85363030, Bruttogewicht: 400.50 g, VPE: 1.00 pc(s)


Abbildungen

Weitere Information

DEHNguard MU 3PD 480 3W+G R surge arrester
3-pole, modular surge arrester for delta 480 V systems
With floating Form C (SPDT) remote status contact
ANSI/UL 1449 – 4th Ed. Open-Type 1 SPD
No need for additional overcurrent protection devices
Nominal system voltage: 480 V Delta
Voltage Protection Rating [L-G]/[L-L]: 1800 Vpk/3000 Vpk
Nominal discharge current (8/20): 20 kA
Maximal discharge current (8/20): 50 kA
Short circuit current rating (SCCR): 200 kA
Fault indication
Width: 3 mod.

Brand: DEHN
Type: DG MU 3PD 480 3W+G R
Part No.: 908355
or equivalent.

Zertifikate

 

Technische Daten

SPD classification acc. to ANSI/UL 1449 4th Ed. Open-Type 1 SPD
SPD classification acc. to CSA - C22.2 No. 269.1-14 Type 4-1 Component Assembly
Max. continuous operating voltage AC [L-G] / [L-L] (MCOV ) 550 V a.c. / 1100 V a.c.
Nominal discharge current (8x 20 µs) (In ) 20 kA
Max. discharge current (8/20) (Imax ) 50 kA
Voltage protection rating [L-G] / [L-L] (VPR ) 1800 Vpk / 3000 Vpk
Max. mains-side overcurrent protection Not needed
Approvals UL, CSA
Remote status contact Floating (dry), Form C (SPDT)

Artikel 908355 wurde zum Merkzettel hinzugefügt.

Zum Merkzettel

Artikel 908355 wurde zum Warenkorb hinzugefügt.

Zum Warenkorb

Art.-Nr. 908356 DG MU 3PD 240 3W+G R

GTIN 4013364148833, Zolltarifnr.: 85363030, Bruttogewicht: 346.30 g, VPE: 1.00 pc(s)


Abbildungen

Weitere Information

DEHNguard DG MU 3PD 240 3W+G R surge arrester
3-pole, modular surge arrester for delta 240 V systems
With floating Form C (SPDT) remote status contact
ANSI/UL 1449 – 4th Ed. Open-Type 1 SPD
No need for additional overcurrent protection devices
Nominal system voltage: 240 V Delta
Voltage Protection Rating [L-G]/[L-L]: 800 Vpk / 1500 Vpk
Nominal discharge current (8/20): 20 kA
Maximal discharge current (8/20): 50 kA
Short circuit current rating (SCCR): 200 kA
Fault indication
Width: 3 mod.

Brand: DEHN
Type: DG MU 3PD 240 3W+G R
Part No.: 908356
or equivalent.

Zertifikate

 

Technische Daten

SPD classification acc. to ANSI/UL 1449 4th Ed. Open-Type 1 SPD
SPD classification acc. to CSA - C22.2 No. 269.1-14 Type 4-1 Component Assembly
Max. continuous operating voltage AC [L-G] / [L-L] (MCOV ) 275 V a.c. / 550 V a.c.
Nominal discharge current (8x 20 µs) (In ) 20 kA
Max. discharge current (8/20) (Imax ) 50 kA
Voltage protection rating [L-G] / [L-L] (VPR ) 800 Vpk / 1500 Vpk
Max. mains-side overcurrent protection Not needed
Approvals UL, CSA
Remote status contact Floating (dry), Form C (SPDT)

Artikel 908356 wurde zum Merkzettel hinzugefügt.

Zum Merkzettel

Artikel 908356 wurde zum Warenkorb hinzugefügt.

Zum Warenkorb

DEHNguard MU 3PY ... 4W+G

DIN rail mount, pluggable surge arrester consisting of a base part and plug-in protection modules for application in 3 Phase Wye Systems

3 Produkte

Art.-Nr. 908340 DG MU 3PY 208 4W+G

GTIN 4013364148840, Zolltarifnr.: 85363030, Bruttogewicht: 412.30 g, VPE: 1.00 pc(s)


Abbildungen

Weitere Information

DEHNguard MU 3PY 208 4W+G surge arrester
4-pole, modular surge arrester for wye 120/208 V systems
ANSI/UL 1449 – 4th Ed. Open-Type 1 SPD
No need for additional overcurrent protection devices
Nominal system voltage: 120/208 V Wye
Voltage Protection Rating [L-N]/[L-G]/[L-L]/[N-G]:
600 Vpk / 1200 Vpk / 1200 Vpk / 600 Vpk
Nominal discharge current (8/20): 20 kA
Maximal discharge current (8/20): 50 kA
Short circuit current rating (SCCR): 200 kA
Fault indication
Width: 4 mod.

Brand: DEHN
Type: DG MU 3PY 208 4W+G
Part No.: 908340
or equivalent.

Zertifikate

 

Technische Daten

SPD classification acc. to ANSI/UL 1449 4th Ed. Open-Type 1 SPD
SPD classification acc. to CSA - C22.2 No. 269.1-14 Type 4-1 Component Assembly
Max. continuous operating voltage AC [L-N] / [L-G] / [L-L] / [N-G] (MCOV ) 180 V a.c. / 360 V a.c. / 360 V a.c. / 180 V a.c.
Nominal discharge current (8x 20 µs) (In ) 20 kA
Max. discharge current (8/20) (Imax ) 50 kA
Voltage protection rating [L-N] / [L-G] / [L-L] / [N-G] (VPR ) 600 Vpk / 1200 Vpk / 1200 Vpk / 600 Vpk
Max. mains-side overcurrent protection Not needed
Approvals UL, CSA

Artikel 908340 wurde zum Merkzettel hinzugefügt.

Zum Merkzettel

Artikel 908340 wurde zum Warenkorb hinzugefügt.

Zum Warenkorb

Art.-Nr. 908341 DG MU 3PY 480 4W+G

GTIN 4013364148864, Zolltarifnr.: 85363030, Bruttogewicht: 449.40 g, VPE: 1.00 pc(s)


Abbildungen

Weitere Information

DEHNguard MU 3PY 480 4W+G surge arrester
4-pole, modular surge arrester for wye 277/480 V systems
ANSI/UL 1449 – 4th Ed. Open-Type 1 SPD
No need for additional overcurrent protection devices
Nominal system voltage: 277/480 V Wye
Voltage Protection Rating [L-N]/[L-G]/[L-L]/[N-G]:
1200 Vpk / 1800 Vpk / 2500 Vpk / 600 Vpk
Nominal discharge current (8/20): 20 kA
Maximal discharge current (8/20): 50 kA
Short circuit current rating (SCCR): 200 kA
Fault indication
Width: 4 mod.

Brand: DEHN
Type: DG MU 3PY 480 4W+G
Part No.: 908341
or equivalent.

Zertifikate

 

Technische Daten

SPD classification acc. to ANSI/UL 1449 4th Ed. Open-Type 1 SPD
SPD classification acc. to CSA - C22.2 No. 269.1-14 Type 4-1 Component Assembly
Max. continuous operating voltage AC [L-N] / [L-G] / [L-L] / [N-G] (MCOV ) 385 V a.c. / 565 V a.c. / 770 V a.c./ 180 V a.c.
Nominal discharge current (8x 20 µs) (In ) 20 kA
Max. discharge current (8/20) (Imax ) 50 kA
Voltage protection rating [L-N] / [L-G] / [L-L] / [N-G] (VPR ) 1200 Vpk / 1800 Vpk / 2500 Vpk / 600 Vpk
Max. mains-side overcurrent protection Not needed
Approvals UL, CSA

Artikel 908341 wurde zum Merkzettel hinzugefügt.

Zum Merkzettel

Artikel 908341 wurde zum Warenkorb hinzugefügt.

Zum Warenkorb

Art.-Nr. 908342 DG MU 3PY 600 4W+G

GTIN 4013364148765, Zolltarifnr.: 85363030, Bruttogewicht: 473.60 g, VPE: 1.00 pc(s)


Abbildungen

Weitere Information

DEHNguard MU 3PY 600 4W+G surge arrester
4-pole, modular surge arrester for wye 347/600 V systems
ANSI/UL 1449 – 4th Ed. Open-Type 1 SPD
No need for additional overcurrent protection devices
Nominal system voltage: 347/600 V Wye
Voltage Protection Rating [L-N]/[L-G]/[L-L]/[N-G]:
1500 Vpk / 2000 Vpk / 3000 Vpk / 600 Vpk
Nominal discharge current (8/20): 20 kA
Maximal discharge current (8/20): 50 kA
Short circuit current rating (SCCR): 200 kA
Fault indication
Width: 4 mod.

Brand: DEHN
Type: DG MU 3PY 600 4W+G
Part No.: 908342
or equivalent.

Zertifikate

 

Technische Daten

SPD classification acc. to ANSI/UL 1449 4th Ed. Open-Type 1 SPD
SPD classification acc. to CSA - C22.2 No. 269.1-14 Type 4-1 Component Assembly
Max. continuous operating voltage AC [L-N] / [L-G] / [L-L] / [N-G] (MCOV ) 510 V a.c. / 690 V a.c. / 1020 V a.c. / 180 V a.c.
Nominal discharge current (8x 20 µs) (In ) 20 kA
Max. discharge current (8/20) (Imax ) 50 kA
Voltage protection rating [L-N] / [L-G] / [L-L] / [N-G] (VPR ) 1500 Vpk / 2000 Vpk / 3000 Vpk / 600 Vpk
Max. mains-side overcurrent protection Not needed
Approvals UL, CSA

Artikel 908342 wurde zum Merkzettel hinzugefügt.

Zum Merkzettel

Artikel 908342 wurde zum Warenkorb hinzugefügt.

Zum Warenkorb

DEHNguard MU 3PY ... 4W+ G R

DIN rail mount, pluggable surge arrester consisting of a base part and plug-in protection modules for application in 3 Phase Wye Systems; has floating Form C (SPDT) remote status contacts

3 Produkte

Art.-Nr. 908345 DG MU 3PY 208 4W+G R

GTIN 4013364148857, Zolltarifnr.: 85363030, Bruttogewicht: 419.50 g, VPE: 1.00 pc(s)


Abbildungen

Weitere Information

DEHNguard MU 3PY 208 4W+G R surge arrester
4-pole, modular surge arrester for wye 120/208 V systems
With floating Form C (SPDT) remote status contact
ANSI/UL 1449 – 4th Ed. Open-Type 1 SPD
No need for additional overcurrent protection devices
Nominal system voltage: 120/208 V Wye
Voltage Protection Rating [L-N]/[L-G]/[L-L]/[N-G]:
600 Vpk / 1200 Vpk / 1200 Vpk / 600 Vpk
Nominal discharge current (8/20): 20 kA
Maximal discharge current (8/20): 50 kA
Short circuit current rating (SCCR): 200 kA
Fault indication
Width: 4 mod.

Brand: DEHN
Type: DG MU 3PY 208 4W+G R
Part No.: 908345
or equivalent.

Zertifikate

 

Technische Daten

SPD classification acc. to ANSI/UL 1449 4th Ed. Open-Type 1 SPD
SPD classification acc. to CSA - C22.2 No. 269.1-14 Type 4-1 Component Assembly
Max. continuous operating voltage AC [L-N] / [L-G] / [L-L] / [N-G] (MCOV ) 180 V a.c. / 360 V a.c. / 360 V a.c. / 180 V a.c.
Nominal discharge current (8x 20 µs) (In ) 20 kA
Max. discharge current (8/20) (Imax ) 50 kA
Voltage protection rating [L-N] / [L-G] / [L-L] / [N-G] (VPR ) 600 Vpk / 1200 Vpk / 1200 Vpk / 600 Vpk
Max. mains-side overcurrent protection Not needed
Approvals UL, CSA
Remote status contact Floating (dry), Form C (SPDT)

Artikel 908345 wurde zum Merkzettel hinzugefügt.

Zum Merkzettel

Artikel 908345 wurde zum Warenkorb hinzugefügt.

Zum Warenkorb

Art.-Nr. 908346 DG MU 3PY 480 4W+G R

GTIN 4013364148871, Zolltarifnr.: 85363030, Bruttogewicht: 458.30 g, VPE: 1.00 pc(s)


Abbildungen

Weitere Information

DEHNguard MU 3PY 480 4W+G R surge arrester
4-pole, modular surge arrester for wye 277/480 V systems
With floating Form C (SPDT) remote status contact
ANSI/UL 1449 – 4th Ed. Open-Type 1 SPD
No need for additional overcurrent protection devices
Nominal system voltage: 277/480 V Wye
Voltage Protection Rating [L-N]/[L-G]/[L-L]/[N-G]:
1200 Vpk / 1800 Vpk / 2500 Vpk / 600 Vpk
Nominal discharge current (8/20): 20 kA
Maximal discharge current (8/20): 50 kA
Short circuit current rating (SCCR): 200 kA
Fault indication
Width: 4 mod.

Brand: DEHN
Type: DG MU 3PY 480 4W+G R
Part No.: 908346
or equivalent.

Zertifikate

 

Technische Daten

SPD classification acc. to ANSI/UL 1449 4th Ed. Open-Type 1 SPD
SPD classification acc. to CSA - C22.2 No. 269.1-14 Type 4-1 Component Assembly
Max. continuous operating voltage AC [L-N] / [L-G] / [L-L] / [N-G] (MCOV ) 385 V a.c. / 565 V a.c. / 770 V a.c. / 180 V a.c.
Nominal discharge current (8x 20 µs) (In ) 20 kA
Max. discharge current (8/20) (Imax ) 50 kA
Voltage protection rating [L-N] / [L-G] / [L-L] / [N-G] (VPR ) 1200 Vpk / 1800 Vpk / 2500 Vpk / 600 Vpk
Max. mains-side overcurrent protection Not needed
Approvals UL, CSA
Remote status contact Floating (dry), Form C (SPDT)

Artikel 908346 wurde zum Merkzettel hinzugefügt.

Zum Merkzettel

Artikel 908346 wurde zum Warenkorb hinzugefügt.

Zum Warenkorb

Art.-Nr. 908347 DG MU 3PY 600 4W+G R

GTIN 4013364148772, Zolltarifnr.: 85363030, Bruttogewicht: 481.50 g, VPE: 1.00 pc(s)


Abbildungen

Weitere Information

DEHNguard MU 3PY 600 4W+G R surge arrester
4-pole, modular surge arrester for wye 347/600 V systems
With floating Form C (SPDT) remote status contact
ANSI/UL 1449 – 4th Ed. Open-Type 1 SPD
No need for additional overcurrent protection devices
Nominal system voltage: 347/600 V Wye
Voltage Protection Rating [L-N]/[L-G]/[L-L]/[N-G]:
1500 Vpk / 2000 Vpk / 3000 Vpk / 600 Vpk
Nominal discharge current (8/20): 20 kA
Maximal discharge current (8/20): 50 kA
Short circuit current rating (SCCR): 200 kA
Fault indication
Width: 4 mod.

Brand: DEHN
Type: DG MU 3PY 600 4W+G R
Part No.: 908347
or equivalent.

Zertifikate

 

Technische Daten

SPD classification acc. to ANSI/UL 1449 4th Ed. Open-Type 1 SPD
SPD classification acc. to CSA - C22.2 No. 269.1-14 Type 4-1 Component Assembly
Max. continuous operating voltage AC [L-N] / [L-G] / [L-L] / [N-G] (MCOV ) 510V a.c. / 690 V a.c. / 1020 V a.c. / 180 V a.c.
Nominal discharge current (8x 20 µs) (In ) 20 kA
Max. discharge current (8/20) (Imax ) 50 kA
Voltage protection rating [L-N] / [L-G] / [L-L] / [N-G] (VPR ) 1500 Vpk / 2000pk V / 3000pk V / 600 Vpk
Max. mains-side overcurrent protection Not needed
Approvals UL, CSA
Remote status contact Floating (dry), Form C (SPDT)

Artikel 908347 wurde zum Merkzettel hinzugefügt.

Zum Merkzettel

Artikel 908347 wurde zum Warenkorb hinzugefügt.

Zum Warenkorb

DEHNguard MU 3PH ... 4W+G

DIN rail mount, pluggable surge arrester consisting of a base part and plug-in protection modules for application in 3 Phase High-leg Delta Systems

2 Produkte

Art.-Nr. 908343 DG MU 3PH 240 4W+G

GTIN 4013364148789, Zolltarifnr.: 85363030, Bruttogewicht: 424.80 g, VPE: 1.00 pc(s)


Abbildungen

Weitere Information

DEHNguard MU 3PH 240 4W+G surge arrester
4-pole, modular surge arrester for high leg delta 120/240 V systems
ANSI/UL 1449 – 4th Ed. Open-Type 1 SPD
No need for additional overcurrent protection devices
Nominal system voltage: 120/240 V High Leg Delta
Voltage Protection Rating [L-N]/[H-N]/[L-G]/[H-G]/[L-L]/[L-H]/[N-G]:
700 Vpk / 800 Vpk / 1200 Vpk / 1500 Vpk / 1500 Vpk / 1500 Vpk / 600 Vpk
Nominal discharge current (8/20): 20 kA
Maximal discharge current (8/20): 50 kA
Short circuit current rating (SCCR): 200 kA
Fault indication
Width: 4 mod.

Brand: DEHN
Type: DG MU 3PH 240 4W+G
Part No.: 908343
or equivalent.

Zertifikate

 

Technische Daten

SPD classification acc. to ANSI/UL 1449 4th Ed. Open-Type 1 SPD
SPD classification acc. to CSA - C22.2 No. 269.1-14 Type 4-1 Component Assembly
Max. continuous operating voltage AC [L-N] / [H-N] / [L-G] / [H-G] / [L-L] / [L-H] / [N-G] 230 V a.c. / 275 V a.c. / 410 V a.c. / 455 V a.c. / 460 V a.c. / 505 V a.c. / 180 V a.c.
Nominal discharge current (8x 20 µs) (In ) 20 kA
Max. discharge current (8/20) (Imax ) 50 kA
Voltage protection rating [L-N] / [H-N] / [L-G] / [H-G] / [L-L] / [L-H] / [N-G] (VPR ) 700 Vpk / 800 Vpk / 1200 Vpk / 1500 Vpk / 1500 Vpk / 1500 Vpk / 600 Vpk
Max. mains-side overcurrent protection Not needed
Approvals UL, CSA

Artikel 908343 wurde zum Merkzettel hinzugefügt.

Zum Merkzettel

Artikel 908343 wurde zum Warenkorb hinzugefügt.

Zum Warenkorb

Art.-Nr. 908344 DG MU 3PH 480 4W+G

GTIN 4013364148802, Zolltarifnr.: 85363030, Bruttogewicht: 456.50 g, VPE: 1.00 pc(s)


Abbildungen

Weitere Information

DEHNguard MU 3PH 480 4W+G surge arrester
4-pole, modular surge arrester for high leg delta 240/480 V systems
ANSI/UL 1449 – 4th Ed. Open-Type 1 SPD
No need for additional overcurrent protection devices
Nominal system voltage: 240/480 V High Leg Delta
Voltage Protection Rating [L-N]/[H-N]/[L-G]/[H-G]/[L-L]/[L-H]/[N-G]:
1200 Vpk / 1500 Vpk / 1800 Vpk / 2000 Vpk / 2500 Vpk / 2500 Vpk / 600 Vpk
Nominal discharge current (8/20): 20 kA
Maximal discharge current (8/20): 50 kA
Short circuit current rating (SCCR): 200 kA
Fault indication
Width: 4 mod.

Brand: DEHN
Type: DG MU 3PH 480 4W+G
Part No.: 908344
or equivalent.

Zertifikate

 

Technische Daten

SPD classification acc. to ANSI/UL 1449 4th Ed. Open-Type 1 SPD
SPD classification acc. to CSA - C22.2 No. 269.1-14 Type 4-1 Component Assembly
Max. continuous operating voltage AC [L-N] / [H-N] / [L-G] / [H-G] / [L-L] / [L-H] / [N-G] 385V a.c. / 510 V a.c. / 565 V a.c. / 690 V a.c. / 770 V a.c. / 895 V a.c. / 180 V a.c.
Nominal discharge current (8x 20 µs) (In ) 20 kA
Max. discharge current (8/20) (Imax ) 50 kA
Voltage protection rating [L-N] / [H-N] / [L-G] / [H-G] / [L-L] / [L-H] / [N-G] (VPR ) 1200 Vpk / 1500 Vpk / 1800 Vpk / 2000 Vpk / 2500 Vpk / 2500 Vpk / 600 Vpk
Max. mains-side overcurrent protection Not needed
Approvals UL, CSA

Artikel 908344 wurde zum Merkzettel hinzugefügt.

Zum Merkzettel

Artikel 908344 wurde zum Warenkorb hinzugefügt.

Zum Warenkorb

DEHNguard MU 3PH ... 4W+G R

DIN rail mount, pluggable surge arrester consisting of a base part and plug-in protection modules for application in 3 Phase High-leg Delta Systems; has floating Form C (SPDT) remote status contacts

2 Produkte

Art.-Nr. 908348 DG MU 3PH 240 4W+G R

GTIN 4013364148796, Zolltarifnr.: 85363030, Bruttogewicht: 432.50 g, VPE: 1.00 pc(s)


Abbildungen

Weitere Information

DEHNguard MU 3PH 240 4W+G R surge arrester
4-pole, modular surge arrester for high leg delta 120/240 V systems
With floating Form C (SPDT) remote status contact
ANSI/UL 1449 – 4th Ed. Open-Type 1 SPD
No need for additional overcurrent protection devices
Nominal system voltage: 120/240 V High Leg Delta
Voltage Protection Rating [L-N]/[H-N]/[L-G]/[H-G]/[L-L]/[L-H]/[N-G]:
700 Vpk / 800 Vpk / 1200 Vpk / 1500 Vpk / 1500 Vpk / 1500 Vpk / 600 Vpk
Nominal discharge current (8/20): 20 kA
Maximal discharge current (8/20): 50 kA
Short circuit current rating (SCCR): 200 kA
Fault indication
Width: 4 mod.

Brand: DEHN
Type: DG MU 3PH 240 4W+G R
Part No.: 908348
or equivalent.

Zertifikate

 

Technische Daten

SPD classification acc. to ANSI/UL 1449 4th Ed. Open-Type 1 SPD
SPD classification acc. to CSA - C22.2 No. 269.1-14 Type 4-1 Component Assembly
Max. continuous operating voltage AC [L-N] / [H-N] / [L-G] / [H-G] / [L-L] / [L-H] / [N-G] 230 V a.c. / 275 V a.c. / 410 V a.c. / 455 V a.c. / 460 V a.c. / 505 V a.c. / 180V a.c.
Nominal discharge current (8x 20 µs) (In ) 20 kA
Max. discharge current (8/20) (Imax ) 50 kA
Voltage protection rating [L-N] / [H-N] / [L-G] / [H-G] / [L-L] / [L-H] / [N-G] (VPR ) 700 Vpk / 800 Vpk / 1200 Vpk / 1500 Vpk / 1500 Vpk / 1500 Vpk / 600 Vpk
Max. mains-side overcurrent protection Not needed
Approvals UL, CSA
Remote status contact Floating (dry), Form C (SPDT)

Artikel 908348 wurde zum Merkzettel hinzugefügt.

Zum Merkzettel

Artikel 908348 wurde zum Warenkorb hinzugefügt.

Zum Warenkorb

Art.-Nr. 908349 DG MU 3PH 480 4W+G R

GTIN 4013364148819, Zolltarifnr.: 85363030, Bruttogewicht: 464.40 g, VPE: 1.00 pc(s)


Abbildungen

Weitere Information

DEHNguard MU 3PH 480 4W+G R surge arrester
4-pole, modular surge arrester for high leg delta 240/480 V systems
With floating Form C (SPDT) remote status contact
ANSI/UL 1449 – 4th Ed. Open-Type 1 SPD
No need for additional overcurrent protection devices
Nominal system voltage: 240/480 V High Leg Delta
Voltage Protection Rating [L-N]/[H-N]/[L-G]/[H-G]/[L-L]/[L-H]/[N-G]:
1200 Vpk / 1500 Vpk / 1800 Vpk / 2000 Vpk / 2500 Vpk / 2500 Vpk / 600 Vpk
Nominal discharge current (8/20): 20 kA
Maximal discharge current (8/20): 50 kA
Short circuit current rating (SCCR): 200 kA
Fault indication
Width: 4 mod.

Brand: DEHN
Type: DG MU 3PH 480 4W+G R
Part No.: 908349
or equivalent.

Zertifikate

 

Technische Daten

SPD classification acc. to ANSI/UL 1449 4th Ed. Open-Type 1 SPD
SPD classification acc. to CSA - C22.2 No. 269.1-14 Type 4-1 Component Assembly
Max. continuous operating voltage AC [L-N] / [H-N] / [L-G] / [H-G] / [L-L] / [L-H] / [N-G] 385 V a.c. / 510 V a.c. / 565 V a.c. / 690 V a.c. / 770 V a.c. / 895 V a.c. / 180 V a.c.
Nominal discharge current (8x 20 µs) (In ) 20 kA
Max. discharge current (8/20) (Imax ) 50 kA
Voltage protection rating [L-N] / [H-N] / [L-G] / [H-G] / [L-L] / [L-H] / [N-G] (VPR ) 1200 Vpk / 1500 Vpk / 1800 Vpk / 2000 Vpk / 2500 Vpk / 2500 Vpk / 600 Vpk
Max. mains-side overcurrent protection Not needed
Approvals UL, CSA
Remote status contact Floating (dry), Form C (SPDT)

Artikel 908349 wurde zum Merkzettel hinzugefügt.

Zum Merkzettel

Artikel 908349 wurde zum Warenkorb hinzugefügt.

Zum Warenkorb

DEHNguard MU SP ... 3W+G

DIN rail mount, pluggable surge arrester consisting of a base part and plug-in protection modules for application in Split Phase systems

2 Produkte

Art.-Nr. 908190 DG MU SP 240 3W+G

GTIN 4013364148604, Zolltarifnr.: 85363030, Bruttogewicht: 235.10 g, VPE: 1.00 pc(s)


Abbildungen

Weitere Information

DEHNguard MU SP 240 3W+G surge arrester
2-pole, modular surge arrester for split phase 120/240 V
- 127/254 V systems
ANSI/UL 1449 – 4th Ed. Open-Type 1 SPD
No need for additional overcurrent protection devices
Nominal system voltage: 120/240 V – 127/254 V
Split Phase
Voltage Protection Rating [L-G]/[L-L]: 700 Vpk / 1500 Vpk
Nominal discharge current (8/20): 20 kA
Maximal discharge current (8/20): 50 kA
Short circuit current rating (SCCR): 200 kA
Fault indication
Width: 2 mod.

Brand: DEHN
Type: DG MU SP 240 3W+G
Part No.: 908190
or equivalent.

Zertifikate

 

Technische Daten

SPD classification acc. to ANSI/UL 1449 4th Ed. Open-Type 1 SPD
SPD classification acc. to CSA - C22.2 No. 269.1-14 Type 4-1 Component Assembly
Max. continuous operating voltage AC [L-G] / [L-L] (MCOV ) 230 V a.c. / 460 V a.c.
Nominal discharge current (8x 20 µs) (In ) 20 kA
Max. discharge current (8/20) (Imax ) 50 kA
Voltage protection rating [L-G] / [L-L] (VPR ) 700 Vpk / 1500 Vpk
Max. mains-side overcurrent protection Not needed
Approvals UL, CSA

Artikel 908190 wurde zum Merkzettel hinzugefügt.

Zum Merkzettel

Artikel 908190 wurde zum Warenkorb hinzugefügt.

Zum Warenkorb

Art.-Nr. 908192 DG MU SP 480 3W+G

GTIN 4013364148628, Zolltarifnr.: 85363030, Bruttogewicht: 254.10 g, VPE: 1.00 pc(s)


Abbildungen

Weitere Information

DEHNguard MU SP 480 3W+G surge arrester
2-pole, modular surge arrester for split phase 240/480 V systems
ANSI/UL 1449 – 4th Ed. Open-Type 1 SPD
No need for additional overcurrent protection devices
Nominal system voltage: 240/480 V Split Phase
Voltage Protection Rating [L-G]/[L-L]: 1200 Vpk / 2500 Vpk
Nominal discharge current (8/20): 20 kA
Maximal discharge current (8/20): 50 kA
Short circuit current rating (SCCR): 200 kA
Fault indication
Width: 2 mod.

Brand: DEHN
Type: DG MU SP 480 3W+G
Part No.: 908192
or equivalent.

Zertifikate

 

Technische Daten

SPD classification acc. to ANSI/UL 1449 4th Ed. Open-Type 1 SPD
SPD classification acc. to CSA - C22.2 No. 269.1-14 Type 4-1 Component Assembly
Max. continuous operating voltage AC [L-G] / [L-L] (MCOV ) 385 V a.c. / 770 V a.c.
Nominal discharge current (8x 20 µs) (In ) 20 kA
Max. discharge current (8/20) (Imax ) 50 kA
Voltage protection rating [L-G] / [L-L] (VPR ) 1200 Vpk / 2500 Vpk
Max. mains-side overcurrent protection Not needed
Approvals UL, CSA

Artikel 908192 wurde zum Merkzettel hinzugefügt.

Zum Merkzettel

Artikel 908192 wurde zum Warenkorb hinzugefügt.

Zum Warenkorb

DEHNguard MU SP ... 3W+G R

DIN rail mount, pluggable surge arrester consisting of a base part and plug-in protection modules for application in Split Phase systems; has floating Form C (SPDT) remote status contacts

2 Produkte

Art.-Nr. 908195 DG MU SP 240 3W+G R

GTIN 4013364148611, Zolltarifnr.: 85363030, Bruttogewicht: 241.00 g, VPE: 1.00 pc(s)


Abbildungen

Weitere Information

DEHNguard MU SP 240 3W+G R surge arrester
2-pole, modular surge arrester for split phase 120/240 V
- 127/254 V systems
With floating Form C (SPDT) remote status contact
ANSI/UL 1449 – 4th Ed. Open-Type 1 SPD
No need for additional overcurrent protection devices
Nominal system voltage: 120/240 V Split Phase
Voltage Protection Rating [L-G]/[L-L]: 700 Vpk / 1500 Vpk
Nominal discharge current (8/20): 20 kA
Maximal discharge current (8/20): 50 kA
Short circuit current rating (SCCR): 200 kA
Fault indication
Width: 2 mod.

Brand: DEHN
Type: DG MU SP 240 3W+G R
Part No.: 908195
or equivalent.

Zertifikate

 

Technische Daten

SPD classification acc. to ANSI/UL 1449 4th Ed. Open-Type 1 SPD
SPD classification acc. to CSA - C22.2 No. 269.1-14 Type 4-1 Component Assembly
Max. continuous operating voltage AC [L-G] / [L-L] (MCOV ) 230 V a.c. / 460 V a.c.
Nominal discharge current (8x 20 µs) (In ) 20 kA
Max. discharge current (8/20) (Imax ) 50 kA
Voltage protection rating [L-G] / [L-L] (VPR ) 700 Vpk / 1500 Vpk
Max. mains-side overcurrent protection Not needed
Approvals UL, CSA
Remote status contact Floating (dry), Form C (SPDT)

Artikel 908195 wurde zum Merkzettel hinzugefügt.

Zum Merkzettel

Artikel 908195 wurde zum Warenkorb hinzugefügt.

Zum Warenkorb

Art.-Nr. 908197 DG MU SP 480 3W+G R

GTIN 4013364148635, Zolltarifnr.: 85363030, Bruttogewicht: 259.30 g, VPE: 1.00 pc(s)


Abbildungen

Weitere Information

DEHNguard MU SP 480 3W+G R surge arrester
2-pole, modular surge arrester for split phase 240/480 V systems
With floating Form C (SPDT) remote status contact
ANSI/UL 1449 – 4th Ed. Open-Type 1 SPD
No need for additional overcurrent protection devices
Nominal system voltage: 240/480 V Split Phase
Voltage Protection Rating [L-G]/[L-L]: 1200 Vpk / 2500 Vpk
Nominal discharge current (8/20): 20 kA
Maximal discharge current (8/20): 50 kA
Short circuit current rating (SCCR): 200 kA
Fault indication
Width: 2 mod.


Brand: DEHN
Type: DG MU SP 480 3W+G R
Part No.: 908197
or equivalent.

Zertifikate

 

Technische Daten

SPD classification acc. to ANSI/UL 1449 4th Ed. Open-Type 1 SPD
SPD classification acc. to CSA - C22.2 No. 269.1-14 Type 4-1 Component Assembly
Max. continuous operating voltage AC [L-G] / [L-L] (MCOV ) 385 V a.c. / 770 V a.c.
Nominal discharge current (8x 20 µs) (In ) 20 kA
Max. discharge current (8/20) (Imax ) 50 kA
Voltage protection rating [L-G] / [L-L] (VPR ) 1200 Vpk / 2500 Vpk
Max. mains-side overcurrent protection Not needed
Approvals UL, CSA
Remote status contact Floating (dry), Form C (SPDT)

Artikel 908197 wurde zum Merkzettel hinzugefügt.

Zum Merkzettel

Artikel 908197 wurde zum Warenkorb hinzugefügt.

Zum Warenkorb

DEHNguard MU SPN ... 3W+G

DIN rail mount, pluggable surge arrester consisting of a base part and plug-in protection modules for application in Split Phase systems

1 Produkt

Art.-Nr. 908214 DG MU SPN 240 3W+G

GTIN 4013364267961, Zolltarifnr.: 85363030, Bruttogewicht: 331.00 g, VPE: 1.00 pc(s)


Abbildungen

Weitere Information

DEHNguard MU SPN 240 3W+G surge arrester
3-pole, modular surge arrester for split phase 127/254 V systems
ANSI/UL 1449 – 4th Ed. Open-Type 1 SPD
No need for additional overcurrent protection devices
Nominal system voltage: 127/254 V Split Phase
Voltage Protection Rating [L-N]/[L-G]/[L-L]/[N-G]:
600 Vpk / 1200 Vpk / 1200 Vpk / 600 Vpk
Nominal discharge current (8/20): 20 kA
Maximal discharge current (8/20): 50 kA
Short circuit current rating (SCCR): 200 kA
Fault indication
Width: 3 mod.

Brand: DEHN
Type: DG MU SPN 240 3W+G
Part No.: 908214
or equivalent.

Zertifikate

 

Technische Daten

SPD classification acc. to ANSI/UL 1449 4th Ed. Open-Type 1 SPD
SPD classification acc. to CSA - C22.2 No. 269.1-14 Type 4-1 Component Assembly
Max. continuous operating voltage AC [L-N] / [L-G] / [L-L] / [N-G] (MCOV ) 180 V a.c. / 360 V a.c. / 360 V a.c. / 180 V a.c.
Nominal discharge current (8x 20 µs) (In ) 20 kA
Max. discharge current (8/20) (Imax ) 50 kA
Voltage protection rating [L-N] / [L-G] / [L-L] / [N-G] (VPR ) 600 Vpk / 1200 Vpk / 1200 Vpk / 600 Vpk
Max. mains-side overcurrent protection Not needed
Approvals UL, CSA

Artikel 908214 wurde zum Merkzettel hinzugefügt.

Zum Merkzettel

Artikel 908214 wurde zum Warenkorb hinzugefügt.

Zum Warenkorb

DEHNguard MU SPN ... 3W+G R

DIN rail mount, pluggable surge arrester consisting of a base part and plug-in protection modules for application in 3 Split Phase systems; has floating Form C (SPDT) remote status contacts

1 Produkt

Art.-Nr. 908219 DG MU SPN 240 3W+G R

GTIN 4013364267978, Zolltarifnr.: 85363030, Bruttogewicht: 338.00 g, VPE: 1.00 pc(s)


Abbildungen

Weitere Information

DEHNguard MU SPN 240 3W+G R surge arrester
3-pole, modular surge arrester for split phase 127/254 V systems
With floating Form C (SPDT) remote status contact
ANSI/UL 1449 – 4th Ed. Open-Type 1 SPD
No need for additional overcurrent protection devices
Nominal system voltage: 127/254 V Split Phase
Voltage Protection Rating [L-N]/[L-G]/[L-L]/[N-G]:
600 Vpk / 1200 Vpk / 1200 Vpk / 600 Vpk
Nominal discharge current (8/20): 20 kA
Maximal discharge current (8/20): 50 kA
Short circuit current rating (SCCR): 200 kA
Fault indication
Width: 3 mod.

Brand: DEHN
Type: DG MU SPN 240 3W+G R
Part No.: 908219
or equivalent.

Zertifikate

 

Technische Daten

SPD classification acc. to ANSI/UL 1449 4th Ed. Open-Type 1 SPD
SPD classification acc. to CSA - C22.2 No. 269.1-14 Type 4-1 Component Assembly
Max. continuous operating voltage AC [L-N] / [L-G] / [L-L] / [N-G] (MCOV ) 180 V a.c. / 360 V a.c. / 360 V a.c. / 180 V a.c.
Nominal discharge current (8x 20 µs) (In ) 20 kA
Max. discharge current (8/20) (Imax ) 50 kA
Voltage protection rating [L-N] / [L-G] / [L-L] / [N-G] (VPR ) 600 Vpk / 1200 Vpk / 1200 Vpk / 600 Vpk
Max. mains-side overcurrent protection Not needed
Approvals UL, CSA
Remote status contact Floating (dry), Form C (SPDT)

Artikel 908219 wurde zum Merkzettel hinzugefügt.

Zum Merkzettel

Artikel 908219 wurde zum Warenkorb hinzugefügt.

Zum Warenkorb

DEHNguard MU CGD ... 3W+G

DIN rail mount, pluggable surge arrester consisting of a base part and plug-in protection modules for application in Corner Grounded Delta systems

2 Produkte

Art.-Nr. 908203 DG MU CGD 240 3W+G

GTIN 4013364148642, Zolltarifnr.: 85363030,