DEHNtrack

  • Metal oxide arrester for d.c. systems up to 4.8 kV
  • Nominal discharge current of 10 kA (8/20 µs)
  • High current withstand capability of 100 kA (4/10 µs)
  • For indoor and outdoor use
  • Maximum protection under conditions of pollution
  • Maximum protection against mechanical vibrations
  • Break resistance in case of overload
  • Freely selectable mounting position

Surge Arrester for d.c. Voltage Systems > 1 kV

4 Produkte

Art.-Nr. 990301 DTR 1.2 10 3

GTIN 4013364103085, Zolltarifnr.: 85354000, Bruttogewicht: 3.00 kg, VPE: 1.00 pc(s)


Abbildungen

Weitere Information

Surge arrester DTR 1.2 10 3
Surge arrester
for protection of dc networks and
rectifiers against atmospheric
and switching surges
according to IEC 99-4 / EN 60099-4
High temperature vulcanised (HTV), hydrophobic
silicon enclosure
Pregreg sheet
High bending resistance
Unbreakable at overloads
Rated voltage: Ur = 1.2 kV
Continuous operating voltage: Uc = 1 kV
Nominal discharge current: In = 10 kA (8/20)
Line discharge class: 3
Ambient temperature: (-55...+55) °C
Creepage distance: 230 mm
HTV-silicon enclosure:: h = 173 mm;
RAL 7040

Brand: DEHN
Type: DTR 1.2 10 3
Part No.: 990301
or equivalent.

 

Technische Daten

Rated voltage (d.c.) (Ur ) 1.2 kV
Continuous operating voltage (d.c.) (MCOV) (UC ) 1.0 kV
Height (H ) 173 mm
Creepage distance (+/- 5%) 230 mm

Artikel 990301 wurde zum Merkzettel hinzugefügt.

Zum Merkzettel

Artikel 990301 wurde zum Warenkorb hinzugefügt.

Zum Warenkorb

Art.-Nr. 990302 DTR 2.4 10 3

GTIN 4013364103092, Zolltarifnr.: 85354000, Bruttogewicht: 5.38 kg, VPE: 1.00 pc(s)


Abbildungen

Weitere Information

Surge arrester DTR 2.4 10 3
Surge arrester
for protection of d.c. networks and
rectifiers against atmospheric
and switching surges
according to IEC 99-4 / EN 60099-4
High temperature vulcanised (HTV), hydrophobic
silicon enclosure
Pregreg sheet
High bending resistance
Unbreakable at overloads
Rated voltage: Ur = 2.4 kV
Continuous operating voltage: Uc = 2.0 kV
Nominal discharge current: In = 10 kA (8/20)
Line discharge class: 3
Ambient temperature: (-55...+55) °C
Creepage distance: 237 mm
HTV-silicon enclosure:: h = 180 mm;
RAL 7040

Brand: DEHN
Type: DTR 2.4 10 3
Part No.: 990302
or equivalent.

 

Technische Daten

Rated voltage (d.c.) (Ur ) 2.4 kV
Continuous operating voltage (d.c.) (MCOV) (UC ) 2.0 kV
Height (H ) 180 mm
Creepage distance (+/- 5%) 237 mm

Artikel 990302 wurde zum Merkzettel hinzugefügt.

Zum Merkzettel

Artikel 990302 wurde zum Warenkorb hinzugefügt.

Zum Warenkorb

Art.-Nr. 990303 DTR 3.6 10 3

GTIN 4013364103108, Zolltarifnr.: 85354000, Bruttogewicht: 3.00 kg, VPE: 1.00 pc(s)


Abbildungen

Weitere Information

Surge arrester DTR 3.6 10 3
Surge arrester
for protection of dc networks and
rectifiers against atmospheric
and switching surges
according to IEC 99-4 / EN 60099-4
High temperature vulcanised (HTV), hydrophobic
silicon enclosure
Pregreg sheet
High bending resistance
Unbreakable at overloads
Rated voltage: Ur = 3.6 kV
Continuous operating voltage: Uc = 3.0 kV
Nominal discharge current: In = 10 kA (8/20)
Line discharge class: 3
Ambient temperature: (-55...+55) °C
Creepage distance: 244 mm
HTV-silicon enclosure:: h = 187 mm;
RAL 7040
Shock resistance: 15 g
according to DIN IEC 68 Part 2.29
Vibration resistance: 3 g (10-500 Hz)
according to DIN IEC 68 Part 2-6
Supply and mount

Brand: DEHN
Type: DTR 3.6 10 3
Part No.: 990303
or equivalent.

 

Technische Daten

Rated voltage (d.c.) (Ur ) 3.6 kV
Continuous operating voltage (d.c.) (MCOV) (UC ) 3.0 kV
Height (H ) 187 mm
Creepage distance (+/- 5%) 244 mm

Artikel 990303 wurde zum Merkzettel hinzugefügt.

Zum Merkzettel

Artikel 990303 wurde zum Warenkorb hinzugefügt.

Zum Warenkorb

Art.-Nr. 990304 DTR 4.8 10 3

GTIN 4013364103115, Zolltarifnr.: 85354000, Bruttogewicht: 3.00 kg, VPE: 1.00 pc(s)


Abbildungen

Weitere Information

Surge arrester DTR 4.8 10 3
Surge arrester
for protection of dc systems and
rectifiers against atmospheric
and switching surges
according to IEC 99-4 / EN 60099-4
High temperature vulcanised (HTV), hydrophobic
silicon enclosure
Pregreg sheet
High bending resistance
Unbreakable at overloads
Rated voltage: Ur = 4.8 kV
Continuous operating voltage: Uc = 4.0 kV
Nominal discharge current: In = 10 kA (8/20)
Line discharge class: 3
Ambient temperature: (-55...+55) °C
Creepage distance: 250 mm
HTV-silicon enclosure:: h = 193 mm;
RAL 7040

Brand: DEHN
Type: DTR 4.8 10 3
Part No.: 990304
or equivalent.

 

Technische Daten

Rated voltage (d.c.) (Ur ) 4.8 kV
Continuous operating voltage (d.c.) (MCOV) (UC ) 4.0 kV
Height (H ) 193 mm
Creepage distance (+/- 5%) 250 mm

Artikel 990304 wurde zum Merkzettel hinzugefügt.

Zum Merkzettel

Artikel 990304 wurde zum Warenkorb hinzugefügt.

Zum Warenkorb

nach oben

Cookie-Einstellungen

Wir verwenden Cookies, um Ihnen ein optimales Webseiten-Erlebnis zu bieten. Dazu zählen Cookies, die für den Betrieb der Seite und für die Steuerung unserer kommerziellen Unternehmensziele notwendig sind, sowie solche, die lediglich zu anonymen Statistikzwecken, für Komforteinstellungen oder zur Anzeige personalisierter Inhalte genutzt werden. Sie können selbst entscheiden, welche Kategorien Sie zulassen möchten. Bitte beachten Sie, dass auf Basis Ihrer Einstellungen womöglich nicht mehr alle Funktionalitäten der Seite zur Verfügung stehen. Weitere Informationen finden Sie in unseren Datenschutzerklärung.
Wenn Sie in die Nutzung von Cookies eingewilligt haben, können Sie dies jederzeit nach Klick auf den Link "Cookie-Einstellungen ändern" im Footer der Seite widerrufen.

  • Details anzeigen Details ausblenden
    Notwendig

    Diese Cookies sind für den Betrieb der Seite unbedingt notwendig und ermöglichen beispielsweise sicherheitsrelevante Funktionalitäten. Außerdem können wir mit dieser Art von Cookies ebenfalls erkennen, ob Sie in Ihrem Profil eingeloggt bleiben möchten, um Ihnen unsere Dienste bei einem erneuten Besuch unserer Seite schneller zur Verfügung zu stellen.

    Statistik & Marketing

    Um unser Angebot und unsere Webseite weiter zu verbessern, erfassen wir anonymisierte Daten für Statistiken und Analysen. Mithilfe dieser Cookies können wir beispielsweise die Besucherzahlen und den Effekt bestimmter Seiten unseres Web-Auftritts ermitteln und unsere Inhalte optimieren.